Technical Data on VACUTAP® Tap-Changer
83 Questions
0 Views

Technical Data on VACUTAP® Tap-Changer

Created by
@BestSellingBeige

Questions and Answers

What do Gas-to-liquid oils (GTL oils) represent in this context?

  • Synthetic oils
  • Petroleum products (correct)
  • Renewable energy sources
  • Natural gas derivatives
  • What should be verified when selecting an on-load tap-changer?

  • The environmental impact of usage
  • The maximum operational efficiency
  • The initial installation costs
  • The highest voltage stresses do not exceed rated withstand voltages (correct)
  • In the context of insulation distances, which configuration indicates more stress?

  • With coarse change-over selector in position -
  • With reversing change-over selector
  • With coarse change-over selector in position + (correct)
  • Without change-over selector
  • What is necessary to consider regarding permitted voltage stresses on the on-load tap-changer?

    <p>The insulation distances</p> Signup and view all the answers

    What aspect is related to the 'rated step voltage Uir' mentioned in capacity diagrams?

    <p>The voltage ratings for equipment operation</p> Signup and view all the answers

    What does the step capacity diagram illustrate for VACUTAP® VM and VM 300?

    <p>The rated step voltage and current ratings</p> Signup and view all the answers

    Which of the following is NOT a condition described for voltage stresses?

    <p>Highest stresses exceed rated withstand voltages</p> Signup and view all the answers

    What does the term 'permitted voltage stresses' specifically refer to?

    <p>The maximum voltages that insulation can handle</p> Signup and view all the answers

    What is the main subject of the document?

    <p>On-load tap-changer specifications and designations</p> Signup and view all the answers

    Which language were the original operating instructions written in?

    <p>German</p> Signup and view all the answers

    What is indicated by the statement 'all rights reserved' in the document?

    <p>Reproduction and dissemination require explicit permission</p> Signup and view all the answers

    What does the term 'on-load tap-changer' refer to in this context?

    <p>A component used to adjust voltage in transformers</p> Signup and view all the answers

    What right is reserved in the event of granting patents or utility models?

    <p>Changes to the design and scope of supply</p> Signup and view all the answers

    What is the customer's responsibility when using the specified product?

    <p>To ensure compatibility with their scope of application</p> Signup and view all the answers

    What aspect of the document indicates its intended exclusivity?

    <p>The clear mention of legal rights and permissions</p> Signup and view all the answers

    What might be a consequence of unauthorized reproduction of the document?

    <p>Legal liability and potential compensation claims</p> Signup and view all the answers

    What is the maximum number of operating positions for the VACUTAP® VM without a change-over selector?

    <p>18</p> Signup and view all the answers

    Which selector size is not applicable with the VACUTAP® VM?

    <p>E</p> Signup and view all the answers

    What is the maximum temperature of the insulating fluid during normal operation of VACUTAP® VM?

    <p>+105 °C</p> Signup and view all the answers

    What is the transport temperature range for the VACUTAP® products?

    <p>-40 °C…+50 °C</p> Signup and view all the answers

    What is the compressive strength of the on-load tap-changer oil compartment?

    <p>0.3 bar</p> Signup and view all the answers

    How many equipped sectors does the VACUTAP® VMS® have?

    <p>3</p> Signup and view all the answers

    What is the maximum number of operating positions for the VACUTAP® VM with a change-over selector?

    <p>35</p> Signup and view all the answers

    Which dimension is mentioned in the mechanical data for the VACUTAP® products?

    <p>Dimensions</p> Signup and view all the answers

    When the transformer is in emergency operation, what is the maximum permitted temperature for the insulating fluid?

    <p>+115 °C</p> Signup and view all the answers

    Which VACUTAP® model has a selector size B and a maximum of 27 operating positions with a change-over selector?

    <p>VACUTAP® VM 300</p> Signup and view all the answers

    What is the maximum operating voltage for the VACUTAP® VMS®?

    <p>170 kV</p> Signup and view all the answers

    Which type of tap-changers are applicable according to the content?

    <p>Single-phase on-load tap-changers</p> Signup and view all the answers

    For selector size C, what is the rated insulation level for AC?

    <p>82</p> Signup and view all the answers

    What does the 'LI' stand for in the insulation distance table?

    <p>Lightning Impulse</p> Signup and view all the answers

    Which insulation type shows the highest value for selector size D?

    <p>LI</p> Signup and view all the answers

    What is the admissible maximum operating voltage for insulation distance 'a0' for size B?

    <p>150</p> Signup and view all the answers

    How many times is the voltage for insulation distances 'a' compared to the values listed for AC?

    <p>Twice</p> Signup and view all the answers

    What is the value for the varistor response voltage at a lightning impulse?

    <p>45 kV</p> Signup and view all the answers

    For selector size DE, what is the insulation distance value for LI?

    <p>550</p> Signup and view all the answers

    In the insulation distance table, which size has the lowest rating for SI?

    <p>B</p> Signup and view all the answers

    Which connection type corresponds to the designation 10050?

    <p>Connection without change-over selector</p> Signup and view all the answers

    What is the unique factor for connections marked with 'W' in their designation?

    <p>They belong to reversing change-over selectors.</p> Signup and view all the answers

    Which of the following designations corresponds to a connection with a coarse change-over selector?

    <p>12101G</p> Signup and view all the answers

    How many unique connections are there for the changing over selector labeled 12111G?

    <p>2</p> Signup and view all the answers

    What is indicated by the presence of the 'G' designation in the context of VACUTAP connections?

    <p>It references connections with change-over selectors that have multiple mid-positions.</p> Signup and view all the answers

    What common feature do all connections identified under designation 10100 share?

    <p>They exist in the reversing change-over selector category.</p> Signup and view all the answers

    Which of the following options includes a connection that has more than three mid-positions?

    <p>12101G</p> Signup and view all the answers

    Which connection type is associated with the designation 14271W?

    <p>Connection with reversing change-over selector</p> Signup and view all the answers

    The original operating instructions for the product were written in French.

    <p>False</p> Signup and view all the answers

    The customer has no responsibility to ensure compatibility with their planned scope of application.

    <p>False</p> Signup and view all the answers

    The document allows for the reproduction and dissemination of its content with prior permission.

    <p>True</p> Signup and view all the answers

    The technical specifications of the product are based entirely on the manufacturer's information.

    <p>False</p> Signup and view all the answers

    The maximum number of operating positions for the VACUTAP® VM is greater than 30.

    <p>False</p> Signup and view all the answers

    The document reserves all rights in the event of damage claims related to the use of its content.

    <p>True</p> Signup and view all the answers

    The technical data presented in the document is final and will not change after publication.

    <p>False</p> Signup and view all the answers

    The designation system for on-load tap-changers includes numbers like 746224 and 10116560.

    <p>True</p> Signup and view all the answers

    The insulation distance f for a rated insulation level of 72.5 kV is 140 kV.

    <p>True</p> Signup and view all the answers

    The LI value for the rated insulation level of 245 kV is 1 150 kV.

    <p>False</p> Signup and view all the answers

    Insulation distance c2 is defined as the distance between change-over selector contacts of the same phase.

    <p>False</p> Signup and view all the answers

    For the insulation distance a, the maximum specified withstand voltage is important when exposed to impulse voltage.

    <p>True</p> Signup and view all the answers

    The AC value for the rated insulation level of 300 kV is 460 kV.

    <p>True</p> Signup and view all the answers

    The insulation distance b encompasses the contacts of different phases connected with the beginning and end of a tap winding.

    <p>True</p> Signup and view all the answers

    The SI value for the insulation level of 170 kV is 850 kV.

    <p>False</p> Signup and view all the answers

    The insulation distance a1 relates to tap selector contacts for different tap positions, regardless of connection.

    <p>False</p> Signup and view all the answers

    Gas-to-liquid oils (GTL oils) are classified as renewable energy sources.

    <p>False</p> Signup and view all the answers

    The rated step voltage Uir is related to both rated current and the type of tap-changer used.

    <p>True</p> Signup and view all the answers

    Permitted voltage stresses should exceed the rated withstand voltages for safety.

    <p>False</p> Signup and view all the answers

    Insulation distances vary significantly depending on whether a change-over selector is present.

    <p>True</p> Signup and view all the answers

    The maximum stress allowed under lightning impulse conditions is set at a specific insulation distance.

    <p>True</p> Signup and view all the answers

    A coarse change-over selector can only be positioned in the '+' position for optimal performance.

    <p>False</p> Signup and view all the answers

    The electrical arc furnace operation diagrams are unaffected by the load current specifications.

    <p>False</p> Signup and view all the answers

    The rated lightning impulse withstand voltage is a critical factor for electrical equipment insulation.

    <p>True</p> Signup and view all the answers

    Bridges on the selector connection contacts are optional for on-load tap-changers VACUTAP® VM I 802/1002.

    <p>False</p> Signup and view all the answers

    The connections listed under designation 12111W correspond to a change-over selector type that is not coarse.

    <p>False</p> Signup and view all the answers

    For current division, bridges are required only on the contacts of a single selector plane.

    <p>False</p> Signup and view all the answers

    The selector size with a maximum of 27 operating positions without a change-over selector is indicated by the designation 14140.

    <p>False</p> Signup and view all the answers

    The connections with designations ending in 'G' are associated exclusively with reversing change-over selectors.

    <p>False</p> Signup and view all the answers

    The insulation distance 'f' refers to the distance between the diverter switch output terminal and the ground.

    <p>True</p> Signup and view all the answers

    For selector size B, the insulation distance 'a0' has a maximum value of 20.

    <p>False</p> Signup and view all the answers

    The rated insulation level for AC for selector size C is 120.

    <p>True</p> Signup and view all the answers

    The minimum varistor response voltage at 1.2/50 µs lightning impulse is recorded as 45 kV.

    <p>False</p> Signup and view all the answers

    For insulation distance 'c2', the value relates to different phases that are unconnected.

    <p>True</p> Signup and view all the answers

    The selector sizes B and C have identical values for insulation distance 'd1'.

    <p>False</p> Signup and view all the answers

    Between connected and adjacent coarse tap contacts in one phase, the insulation distance is referred to as 'd2'.

    <p>True</p> Signup and view all the answers

    The insulation distance 'b' measures between the tap selector contacts of the same phase.

    <p>False</p> Signup and view all the answers

    The insulation distance 'c1' is greater than or equal to 400 for selector size C.

    <p>True</p> Signup and view all the answers

    The residual voltage at 3 kA peak withstand current for varistor response is listed as 66 kV.

    <p>False</p> Signup and view all the answers

    Study Notes

    On-load Tap-Changer Overview

    • VACUTAP® VM®, VM 300, VMS® are on-load tap-changers used in transformers.
    • Designed for various applications, they allow adjustment of transformer output voltage without interrupting service.

    Mechanical Data for VACUTAP Models

    • VACUTAP® VM
      • Maximum operating positions: 18 (without change-over selector), 35 (with change-over selector), 107 (with multiple coarse change-over selector).
      • Equipped sectors: 1 to 3.
    • VACUTAP® VM 300
      • Maximum operating positions: 14 (without change-over selector), 27 (with change-over selector).
    • VACUTAP® VMS®
      • Maximum operating positions: 18 (without change-over selector), 35 (with change-over selector).
      • Equipped sectors: 3.

    Ambient Conditions

    • Operational air temperature: -25 °C to +50 °C.
    • Insulating fluid temperature during operation: -25 °C to +105 °C (up to +115 °C in emergencies).
    • Transport and storage temperature: -40 °C to +50 °C.
    • Oil compartment is pressure-resistant to 0.3 bar (continuous differential pressure).

    Step Capacity Diagrams

    • Step capacities are defined for network applications and electrical arc furnace operation for VACUTAP models.
    • Important for understanding rated step voltage (Uir) and current (Ir) capabilities.

    Permitted Voltage Stresses

    • Voltage stresses must respect rated withstand voltages based on insulation distances.
    • Admissible operating voltage is defined as half the values for applied voltage (AC).

    Insulation Levels and Selector Sizes

    • Rated insulation levels vary between models and include distinct performance metrics for insulation distance based on selector size (B, C, D, DE).
    • Admissible voltages are specified under various configurations, ensuring compatibility with system requirements.

    Connections for VACUTAP® VMS® III and VM 300

    • Realizable connections for VACUTAP® VM 300 and VMS® III may involve varying configurations, accommodating change-over selectors and coarse tap options.

    General Notes

    • Specifications are subject to change; technical data might differ from the initial document due to product alterations post-publication.
    • Customers must ensure product compatibility with their specific applications.

    Introduction to VACUTAP® Tap-Changers

    • VACUTAP® is a range of on-load tap-changers designed for various applications, including network and electrical arc furnace operations.
    • Key designs include VACUTAP® VM, VM 300, and VMS®.

    Technical Specifications

    • Document emphasizes strict protection of its content and intellectual property rights, including potential liabilities for infringement.
    • Ensure compatibility of the on-load tap-changer with specific customer applications.

    Insulation and Voltage Stresses

    • Insulation distances are critical to ensure the rated withstand voltages aren’t exceeded during operations.
    • Different types of insulation levels are specified for various components of the tap-changer including diverter switches and selectors.

    Step Capacity Diagrams

    • Diagrams outline the rated step voltage (Uir) and rated through-current (Ir) for network applications and arc furnace operations.
    • Detailed representations are crucial for assessing performance under different loads.

    Permissible Ambient Conditions

    • Specific ambient conditions must be maintained to ensure optimal functioning of the on-load tap-changer.

    Rated Insulation Levels

    • Ratings include:
      • Lightning impulse (LI), Chopped wave lightning impulse (LIC), Switching impulse (SI), and Applied voltage (AC).
    • Each rated insulation level has its specified insulation distance, critical for ensuring safety and performance.

    Realizable Connections

    • Detailed connections for VACUTAP® VMS® III are outlined for various configurations.
    • Specific requirements must be adhered to depending on the type of change-over selectors used.

    Special Designs

    • Bridges may be required for the parallel connection of selector planes to ensure current distribution in multi-branch tap windings.

    Conclusion

    • VACUTAP® tap-changers are engineered for reliability and performance under specified operating conditions, with careful attention to insulation ratings and connection configurations.

    Studying That Suits You

    Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

    Quiz Team

    Description

    This quiz explores the technical specifications and applications of the VACUTAP® VM, VM 300, and VMS® on-load tap-changers. Learn about the intricacies of these devices, their functioning principles, and essential data critical for understanding their role in electrical systems.