Electrical Engineering Standards and Methods
40 Questions
0 Views

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to lesson

Podcast

Play an AI-generated podcast conversation about this lesson

Questions and Answers

What is the first step required to lower the oil level in the tap changer head?

  • Open the sample valve of the return pipe
  • Loosen the screws at the coupling bracket
  • Close the stop valve between oil conservator and tap changer head (correct)
  • Open the drain valve of the tap changer head
  • Which precautions should be taken when handling the switching oil during maintenance?

  • Avoid any electrical equipment near the work area
  • Ensure open flames are present for safety
  • Use any type of pumping equipment available
  • Handle the oil as if it were a flammable liquid (correct)
  • What should be monitored through the inspection glass while draining oil from the tap changer head?

  • The oil level in the conservator
  • The color of the switching oil
  • The support plate of the diverter switch unit (correct)
  • The temperature of the oil
  • Which action is necessary to uncouple the drive shaft at the upper gear unit?

    <p>Loosen 6 screws M6/w.s.10 at the coupling bracket</p> Signup and view all the answers

    Why is it important to avoid open fire during the oil handling process?

    <p>Explosive gases can accumulate under the tap changer cover</p> Signup and view all the answers

    What quantity of oil should ideally be drained from the tap changer head?

    <p>10 liters</p> Signup and view all the answers

    What must be taken into consideration concerning the pumping equipment used during maintenance?

    <p>It must be suitable for flammable liquids</p> Signup and view all the answers

    Which component's operation should be initiated if an oil filter unit is present?

    <p>The sample valve of the return pipe</p> Signup and view all the answers

    What is the maximum allowable number of tap change operations for the diverter switch units of the tap changer before replacement is required?

    <p>800,000 operations</p> Signup and view all the answers

    For the M II 350 D on-load tap changer with a rated current of up to 350 A, how many tap change operations can it perform without requiring any MR oil filter?

    <p>40,000 operations</p> Signup and view all the answers

    If a transformer performs 15,000 tap change operations per year, when is the first mandatory inspection interval?

    <p>After 20,000 operations</p> Signup and view all the answers

    What is the recommended inspection interval after the first inspection is carried out?

    <p>4 years</p> Signup and view all the answers

    What should be done when a tap changer reaches approximately 1,000,000 switching operations?

    <p>Contact Technical Service</p> Signup and view all the answers

    Which of the following is a requirement for transformers operating under high switching operation conditions?

    <p>Use a stationary oil filter unit</p> Signup and view all the answers

    What measurement method is referenced for testing oil quality in transformers?

    <p>Karl-Fischer method</p> Signup and view all the answers

    How many tap change operations can the M III 600 D perform with an MR oil filter?

    <p>80,000 operations</p> Signup and view all the answers

    What action should be taken before removing the upper supporting cylinder?

    <p>Dismount the link for the tap change supervisory control system</p> Signup and view all the answers

    Which components are used to secure the link for the tap change supervisory control system?

    <p>Two studs M5 with lock nuts</p> Signup and view all the answers

    What should be avoided to prevent damage to the diverter switch unit?

    <p>Dropping any parts during disassembly</p> Signup and view all the answers

    What type of screws are used for the connection of the supporting cylinder?

    <p>M8 x 20 screws with lock nuts and washers</p> Signup and view all the answers

    What cleaning method is recommended for the supporting cylinder?

    <p>Cleaning with a brush and transformer oil</p> Signup and view all the answers

    What could lead to creeping paths that may damage the system?

    <p>Unclean surfaces of the support cylinder and insulating shaft</p> Signup and view all the answers

    Before starting the disassembly, what should be ensured regarding small parts?

    <p>The number of small parts is complete</p> Signup and view all the answers

    What type of risks does dropping parts during disassembly pose?

    <p>Potential blockage of the diverter switch and damage to system components</p> Signup and view all the answers

    What is the maximum torque specification for attaching the supporting cylinder with lock nuts?

    <p>22 Nm</p> Signup and view all the answers

    Which components must be securely fastened with lock nuts when assembling the diverter switch unit?

    <p>Supporting plate and supporting cylinder</p> Signup and view all the answers

    What is the purpose of the diverter switch pole W in the assembly process?

    <p>To ensure alignment with diverter switch pole U</p> Signup and view all the answers

    How many screws are required to attach the lower supporting cylinder of pole W?

    <p>8 screws</p> Signup and view all the answers

    What should be checked regarding the resistor leads of diverter switch pole W during assembly?

    <p>Clearance to the upper screen ring</p> Signup and view all the answers

    Which part must be assembled first when setting up the diverter switch unit?

    <p>Lower insulating shaft</p> Signup and view all the answers

    Which operation should be performed to verify the mechanical function of the device?

    <p>Operate the diverter switch several times</p> Signup and view all the answers

    What is the role of the 2 washers provided with each screw in the assembly process?

    <p>To distribute load and prevent loosening</p> Signup and view all the answers

    What does the notation '50%' suggest in the context provided?

    <p>A maximum threshold for component wear</p> Signup and view all the answers

    When should the contacts be evaluated for replacement according to the value mentioned?

    <p>When the wear tolerance has reached a 50% level</p> Signup and view all the answers

    What consequence may arise from not replacing the contacts when necessary?

    <p>Increased operational costs due to inefficiency</p> Signup and view all the answers

    What is indicated by the letter 'R' appearing multiple times in the context?

    <p>Repeated instances of wear measurement</p> Signup and view all the answers

    What could the series of numbers '5555' signify in maintenance documentation?

    <p>A identification code for maintenance history</p> Signup and view all the answers

    What strategy should be implemented when the wear indicator reaches critical levels?

    <p>Conduct immediate inspections and potential replacements</p> Signup and view all the answers

    Why is it critical for documentation to indicate the need for replacement?

    <p>To maintain consistent operational efficiency</p> Signup and view all the answers

    What does the symbol 'x' followed by percent signs imply in the context?

    <p>A representation of variable operational levels</p> Signup and view all the answers

    Study Notes

    Transformer Tap Change Operations

    • Several transformers are detailed (M III 350 D, M III 500 D, M III 600 D), each rated for specific current capacities.
    • Inspection intervals are based on experience with conventional oil qualities and the number of tap change operations.
    • A tap selector in the tap changer is generally maintenance-free, but special cases may require Technical Service consultation after approximately 1,000,000 operations.
    • Diverter switch units must be replaced after 800,000 operations.

    Inspection and Maintenance Schedule

    • Initial inspection required after 20,000 tap change operations, if yearly operations exceed 15,000.
    • Further inspections occur every four years.
    • Recommended use of stationary oil filter units for upkeep.

    Handling Procedures

    • Switching oil is flammable; handle with care, avoiding open flames and using appropriate pumping equipment.
    • During maintenance, lower the oil level by closing the stop valve and opening the drain and bleeder valves.
    • Approximately 10 litres must be drained until the diverter switch unit support plate is free of oil.

    Diverter Switch Maintenance

    • Uncoupling of the drive shaft involves loosening screws at the coupling bracket for clearance.
    • Care must be taken to visually inspect and ensure cleanliness of surfaces to avoid damage from creeping paths.
    • Proper assembly of the diverter switch is vital; ensure all parts are clean and accounted for to prevent operational blockages.

    Important Assembly Steps

    • Remove supporting components in reverse order, checking for mechanical functionality during reassembly.
    • Max torque requirements are specified for attachment screws to prevent damage.
    • Final checks for sufficient clearance in electrical components are crucial before testing the diverter switch unit's operation.

    Safety Precautions

    • Strict measures need to be followed to avoid dropping parts into the switch unit which could lead to malfunctions.
    • Series of corrective actions and checks are outlined to confirm readiness before final installation of the diverter switch unit.

    Studying That Suits You

    Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

    Quiz Team

    Related Documents

    Description

    This quiz focuses on various electrical engineering standards and measurement methods, including tap change operations and oil quality assessments based on established publications. Deepen your knowledge of inspection intervals and IEC standards through this informative quiz.

    More Like This

    Railway Maintenance and Inspection
    120 questions
    On-Load Tap Changer Type V Inspection
    5 questions
    Inspección de Centros de Transformación
    10 questions
    Use Quizgecko on...
    Browser
    Browser