4BE3.5 U3 C5 Obj 2 EMH

WholesomeMaroon avatar
WholesomeMaroon
·
·
Download

Start Quiz

Study Flashcards

56 Questions

EASY What is the position of the air damper and firing rate valve when firing on gas?

High-fire

What determines the position of the modulating motor when the damper positioning switch is set to AUTO?

The error between the boiler pressure and the set point of the pressuretrol

What is the purpose of the manual flame control potentiometer when the damper positioning switch is set to AUTO and the manual-automatic switch is set to MANUAL?

To modulate the firing rate of the boiler

What is the result of warming a cold boiler on low-fire?

Reduced thermal stress

What is the function of the switches in the modulating motor when firing on oil?

To energize the remaining oil nozzles

What is the condition for the boiler to fully modulate?

The damper positioning switch is set to AUTO and the manual-automatic switch is set to AUTO

What is the function of the Burner On-Off switch?

To manually start and stop the boiler

What determines the load on the boiler when firing on gas?

The error between the boiler steam pressure and the set point

What is the effect of setting the damper positioning switch to LO?

The air damper and firing rate valve remain in low-fire

What happens when the damper positioning switch is set to HI?

The modulating motor drives to high-fire

What is the function of the manual-auto switch?

To switch between manual and automatic operation

What is the purpose of the manual flame control potentiometer?

To manually control the flame

How does the boiler operate when firing on oil?

Multi-position

What happens when the boiler is firing on oil and the damper positioning switch is set to LO?

The boiler operates in low-fire with one oil nozzle firing

MEDIUM What is the significance of the manual-automatic switch being set to MANUAL when the damper positioning switch is set to AUTO?

The boiler can be base loaded at any desired output.

What determines the firing rate of the boiler when the damper positioning switch is set to AUTO and the manual-automatic switch is set to AUTO?

The modulating controller signal

What is not affected by the type of fuel being used?

The boiler pressure

What is the result of the boiler being warmed up on low-fire?

Reduced thermal stress

What is the purpose of the modulating motor when the damper positioning switch is set to AUTO?

To position the damper

What is the condition for the boiler to operate on low-fire?

The pressuretrol signal is below the set point.

What is the primary function of the damper positioning switch on a dual-fuel boiler?

To position the air damper and firing rate control valve

What determines the load on a hot water boiler?

The error between the set point of the modulating temperature control and the boiler hot water outlet temperature

What is the effect of setting the damper positioning switch to LO when firing on gas?

The boiler operates at low-fire

What is the purpose of the internal switches in the modulating motor when firing on oil?

To successively energize oil nozzles

What is the function of the manual-auto switch on a dual-fuel boiler?

To switch between manual and automatic operation

What is the characteristic of a dual-fuel boiler when firing on oil?

Multi-position

What is the effect of the manual flame control potentiometer on the boiler's operation?

It controls the boiler's firing rate

What is the primary function of the Burner On-Off switch on a dual-fuel boiler?

To start and stop the boiler

What happens to the air damper and firing rate valve when the boiler is firing on gas and the damper positioning switch is set to HI?

They drive to high-fire.

What determines the load on the boiler when firing on oil?

The error between the set point of the modulating pressure control and the boiler steam pressure.

What is the purpose of the internal switches in the modulating motor when firing on oil?

To successively energize oil nozzles in accordance with load.

What is the result of setting the damper positioning switch to LO when firing on oil?

The boiler operates at low-fire.

What is the characteristic of the boiler when firing on gas?

The boiler is fully modulating.

What is the primary function of the manual flame control potentiometer?

To manually control the boiler's flame when the manual-auto switch is set to MANUAL.

What is the condition required for the boiler to operate on low-fire?

The damper positioning switch must be set to LO.

What is the purpose of the Burner On-Off switch?

To start and stop the boiler.

What is the relationship between the manual-automatic switch and the modulating motor signal when the damper positioning switch is set to AUTO?

The modulating motor signal is dependent on the manual-automatic switch being set to AUTO.

What is the purpose of the manual flame control potentiometer when the damper positioning switch is set to AUTO and the manual-automatic switch is set to MANUAL?

To control the firing rate of the boiler independent of the pressuretrol signal.

What is the characteristic of the boiler when the damper positioning switch is set to AUTO and the manual-automatic switch is set to AUTO?

The boiler fully modulates in response to the pressuretrol signal.

What is the result of warming a cold boiler on low-fire?

Reduced thermal stress on the boiler.

What is the relationship between the pressuretrol signal and the modulating motor position when the damper positioning switch is set to AUTO?

The modulating motor position is directly proportional to the pressuretrol signal.

What is the primary function of the damper positioning switch on a dual-fuel boiler?

To control the position of the air damper.

Match the following switches with their respective functions on a dual-fuel boiler:

Burner On-Off switch = Starts and stops the boiler Damper Positioning switch = Determines firing rate and air damper position Manual-Automatic switch = Toggles between manual and automatic control Manual flame control potentiometer = Adjusts firing rate in manual mode

Match the following fuel types with their respective firing characteristics on a dual-fuel boiler:

Gas = Multi-position Oil = Fully modulating

Match the following control panel components with their respective effects on the boiler's operation:

Damper Positioning switch set to LO = Limits firing rate to low-fire Manual-Automatic switch set to MANUAL = Enables manual control of firing rate Manual flame control potentiometer = Adjusts firing rate in automatic mode Burner On-Off switch set to OFF = Stops the boiler

Match the following operating conditions with their respective effects on the boiler's load:

Firing on gas = Load determined by error between set point and boiler temperature Firing on oil = Load determined by pressuretrol signal

Match the following control panel components with their respective purposes:

Modulating motor = Positions air damper and firing rate valve Internal switches = Energize oil nozzles in sequence Manual flame control potentiometer = Adjusts firing rate in manual mode Damper Positioning switch = Toggles between manual and automatic control

Match the following operating conditions with their respective effects on the boiler's firing rate:

Damper Positioning switch set to HI = Increases firing rate to high-fire Manual-Automatic switch set to MANUAL = Enables manual control of firing rate Firing on oil = Limits firing rate to low-fire Firing on gas = Maintains firing rate at low-fire

Match the following control panel components with their respective effects on the boiler's operation:

Manual-Automatic switch set to AUTO = Enables automatic control of firing rate Damper Positioning switch set to LO = Limits firing rate to low-fire Manual flame control potentiometer = Adjusts firing rate in manual mode Burner On-Off switch set to ON = Starts the boiler

Match the following operating conditions with their respective effects on the boiler's operation:

Warming a cold boiler on low-fire = Enables slow warm-up and continuous low-load operation Firing on gas = Maintains firing rate at low-fire Firing on oil = Permits slow warm-up and continuous low-load operation Damper Positioning switch set to AUTO = Enables automatic control of firing rate

Match the following settings with their effects on the boiler's operation:

Damper positioning switch set to AUTO and manual-automatic switch set to AUTO = The boiler fully modulates based on the pressuretrol signal Damper positioning switch set to AUTO and manual-automatic switch set to MANUAL = The boiler's firing rate is controlled by the manual flame control potentiometer Firing on gas = The air damper and firing rate valve remain in high-fire regardless of the boiler load Firing on oil = The switches in the modulating motor energize the remaining oil nozzles

Match the following components with their functions:

Modulating motor = Positions the air damper and firing rate valve based on the pressuretrol signal Manual flame control potentiometer = Controls the firing rate of the boiler when the damper positioning switch is set to AUTO and the manual-automatic switch is set to MANUAL Pressuretrol = Determines the position of the modulating motor when the damper positioning switch is set to AUTO Manual-automatic switch = Determines whether the boiler operates based on the pressuretrol signal or manual control

Match the following scenarios with their effects on the boiler's operation:

Warming a cold boiler on low-fire = Reduces harmful stress caused by uneven thermal expansion Firing on gas with the damper positioning switch set to HI = The air damper and firing rate valve remain in high-fire Firing on oil with the damper positioning switch set to LO = The boiler's firing rate is reduced Base loading a boiler with the damper positioning switch set to AUTO and the manual-automatic switch set to MANUAL = The boiler operates at a desired output regardless of the pressuretrol signal

Match the following settings with their characteristics:

Damper positioning switch set to AUTO = The boiler operates based on the pressuretrol signal Manual-automatic switch set to AUTO = The boiler fully modulates based on the pressuretrol signal Firing on gas = The boiler remains on high-fire regardless of the boiler load Firing on oil = The switches in the modulating motor energize the remaining oil nozzles

Match the following components with their effects on the boiler's operation:

Pressuretrol = Determines the position of the modulating motor when the damper positioning switch is set to AUTO Modulating motor = Positions the air damper and firing rate valve based on the pressuretrol signal Manual flame control potentiometer = Controls the firing rate of the boiler when the damper positioning switch is set to AUTO and the manual-automatic switch is set to MANUAL Manual-automatic switch = Determines whether the boiler operates based on the pressuretrol signal or manual control

Match the following scenarios with their required settings:

Base loading a boiler at a desired output = Damper positioning switch set to AUTO and manual-automatic switch set to MANUAL Warming a cold boiler on low-fire = Damper positioning switch set to AUTO and manual-automatic switch set to MANUAL Boiler operating on high-fire = Firing on gas with the damper positioning switch set to HI Boiler operating on low-fire = Firing on oil with the damper positioning switch set to LO

Study Notes

Boiler Control Panel

  • Equipped with switches: Burner On-Off, Damper positioning (Hi-Low-Auto), Manual-Automatic, and Manual flame control potentiometer

Burner Switch (On-Off)

  • Manually operated to start and stop the boiler

Damper Positioning Switch (Hi-Low-Auto)

  • Modulating motor positions air damper and firing rate control valve based on load on boiler
  • Modulating motor energizes oil nozzles in sequence according to load
  • Load determined by error between set point and boiler steam pressure (hot water temperature for hot water boilers)

Damper Positioning Switch Settings

  • LO: Modulating motor remains in low-fire position, unaffected by manual-auto switch and manual flame control potentiometer
  • HI: Modulating motor drives to high-fire, unaffected by manual-auto switch and manual flame control potentiometer
  • AUTO: Error between boiler pressure (or temperature) and set point determines modulating motor position

Manual-Automatic Switch and Manual Flame Control Potentiometer

  • When damper positioning switch is AUTO, and manual-automatic switch is AUTO, modulating controller signal positions modulating motor
  • When damper positioning switch is AUTO, and manual-automatic switch is MANUAL, manual flame control potentiometer controls firing rate independently of pressuretrol signal, allowing for base loading and cold boiler warm-up on low-fire

Boiler Control Panel

  • Equipped with switches: Burner On-Off, Damper positioning (Hi-Low-Auto), Manual-Automatic, and Manual flame control potentiometer

Burner Switch (On-Off)

  • Manually operated to start and stop the boiler

Damper Positioning Switch (Hi-Low-Auto)

  • Modulating motor positions air damper and firing rate control valve based on load on boiler
  • Modulating motor energizes oil nozzles in sequence according to load
  • Load determined by error between set point and boiler steam pressure (hot water temperature for hot water boilers)

Damper Positioning Switch Settings

  • LO: Modulating motor remains in low-fire position, unaffected by manual-auto switch and manual flame control potentiometer
  • HI: Modulating motor drives to high-fire, unaffected by manual-auto switch and manual flame control potentiometer
  • AUTO: Error between boiler pressure (or temperature) and set point determines modulating motor position

Manual-Automatic Switch and Manual Flame Control Potentiometer

  • When damper positioning switch is AUTO, and manual-automatic switch is AUTO, modulating controller signal positions modulating motor
  • When damper positioning switch is AUTO, and manual-automatic switch is MANUAL, manual flame control potentiometer controls firing rate independently of pressuretrol signal, allowing for base loading and cold boiler warm-up on low-fire

Boiler Control Panel

  • Equipped with switches: Burner On-Off, Damper positioning (Hi-Low-Auto), Manual-Automatic, and Manual flame control potentiometer

Burner Switch (On-Off)

  • Manually operated to start and stop the boiler

Damper Positioning Switch (Hi-Low-Auto)

  • Modulating motor positions air damper and firing rate control valve based on load on boiler
  • Modulating motor energizes oil nozzles in sequence according to load
  • Load determined by error between set point and boiler steam pressure (hot water temperature for hot water boilers)

Damper Positioning Switch Settings

  • LO: Modulating motor remains in low-fire position, unaffected by manual-auto switch and manual flame control potentiometer
  • HI: Modulating motor drives to high-fire, unaffected by manual-auto switch and manual flame control potentiometer
  • AUTO: Error between boiler pressure (or temperature) and set point determines modulating motor position

Manual-Automatic Switch and Manual Flame Control Potentiometer

  • When damper positioning switch is AUTO, and manual-automatic switch is AUTO, modulating controller signal positions modulating motor
  • When damper positioning switch is AUTO, and manual-automatic switch is MANUAL, manual flame control potentiometer controls firing rate independently of pressuretrol signal, allowing for base loading and cold boiler warm-up on low-fire

Boiler Control Panel

  • Equipped with switches: Burner On-Off, Damper positioning (Hi-Low-Auto), Manual-Automatic, and Manual flame control potentiometer

Burner Switch (On-Off)

  • Manually operated to start and stop the boiler

Damper Positioning Switch (Hi-Low-Auto)

  • Modulating motor positions air damper and firing rate control valve based on load on boiler
  • Modulating motor energizes oil nozzles in sequence according to load
  • Load determined by error between set point and boiler steam pressure (hot water temperature for hot water boilers)

Damper Positioning Switch Settings

  • LO: Modulating motor remains in low-fire position, unaffected by manual-auto switch and manual flame control potentiometer
  • HI: Modulating motor drives to high-fire, unaffected by manual-auto switch and manual flame control potentiometer
  • AUTO: Error between boiler pressure (or temperature) and set point determines modulating motor position

Manual-Automatic Switch and Manual Flame Control Potentiometer

  • When damper positioning switch is AUTO, and manual-automatic switch is AUTO, modulating controller signal positions modulating motor
  • When damper positioning switch is AUTO, and manual-automatic switch is MANUAL, manual flame control potentiometer controls firing rate independently of pressuretrol signal, allowing for base loading and cold boiler warm-up on low-fire

This quiz covers the components and functions of a boiler control panel, including switches and valves that regulate the boiler's operation.