What is the first step in the typical sequence of operation for most programming controllers when firing natural gas or oil?

  • Pre-ignition interlocks (correct)
  • Start draft fan
  • Start purge
  • High airflow

During the programming controller sequence of operation, when does the BMS start the draft fan?

  • When high airflow is detected
  • Upon satisfying permissives and pre-ignition interlocks (correct)
  • After completing the purge
  • After igniting the pilot

What does the BMS do after detecting high airflow in the programming controller sequence of operation?

  • Ignite pilot
  • Return combustion airflow to low fire
  • Increase fan speed or combustion air damper position to high-fire (correct)
  • Start purge

In the programming controller sequence of operation, what follows after completing the purge?

<p>Return combustion airflow to low fire (D)</p> Signup and view all the answers

What is the purpose of waiting for up to 10 seconds after igniting the pilot in the programming controller sequence of operation?

<p>To stabilize the pilot flame (D)</p> Signup and view all the answers

Which factor does NOT influence the variations in flame amplifiers, purge timers, and permissives on programming controllers according to the text provided?

<p>Boiler pressure (B)</p> Signup and view all the answers

What is the purpose of the post-purge mentioned in the text?

<p>To clear any remaining combustion gases (A)</p> Signup and view all the answers

In the shutdown sequence described, what happens if the SSOV proof-of-closure switches do not close within 5 seconds?

<p>The system goes into standby mode (A)</p> Signup and view all the answers

Which component shuts off the burner in the described scenario?

<p>Permissive switch (A)</p> Signup and view all the answers

What initiates the programming controller to de-energize the SSOVs in the shutdown sequence?

<p>Steam pressure reaching operating control set point (A)</p> Signup and view all the answers

If all permissives and pre-ignition interlocks are satisfied, what action does the programming controller take?

<p>Repeats the startup sequence (D)</p> Signup and view all the answers

What happens when a limit switch opens during operation of the burner?

<p>The burner conducts a 15-second post-purge and re-enters standby mode. (B)</p> Signup and view all the answers

What does the programming controller do in case of a safety shutdown and lockout?

<p>Closes all SSOVs and locks itself out. (C)</p> Signup and view all the answers

During which period would an airflow proving switch opening lead to a safety shutdown?

<p>During the PILOT TRIAL-FOR-IGNITION PERIOD (PTFI). (B)</p> Signup and view all the answers

What is the action of the BMS in case of detecting an internal fault?

<p>It initiates a safety shutdown and lockout. (D)</p> Signup and view all the answers

Which type of boilers may use stack temperature relays to detect flame failure?

<p>Oil-fired boilers. (A)</p> Signup and view all the answers

What is the condition referred to as when the operating control initiates a startup in natural draft gas-fired boilers with intermittent pilots?

<p>&quot;Call for heat.&quot; (B)</p> Signup and view all the answers

What action does the primary controller take after the pilot flame is established in natural draft gas-fired boilers?

<p>Opens the main gas SSOV. (B)</p> Signup and view all the answers

What happens if the pilot does not light within 15 to 90 seconds?

<p>The primary controller will retry ignition (B)</p> Signup and view all the answers

What does the primary control system do when the operating steam pressure or water temperature reaches the desired preset value?

<p>Opens the main SSOV (A)</p> Signup and view all the answers

In case of a main flame failure during operation, what is the immediate action taken by many primary controls?

<p>Begin the PTFI cycle (C)</p> Signup and view all the answers

What triggers the activation of the motor driving the draft fan and fuel oil pump in small mechanically-atomized packaged oil burners?

<p>Boiler pressuretrol (A)</p> Signup and view all the answers

What is the result if the programming control detects an ignition failure during boiler startup?

<p>Lockout (B)</p> Signup and view all the answers

How many pilot ignition retry attempts are usually permitted by primary controls?

<p>One (C)</p> Signup and view all the answers

What must occur before a steam or hot water boiler can be started by its programming controller?

<p>'Permissives' and pre-ignition interlocks must be satisfied (A)</p> Signup and view all the answers

If the main burner goes out during the run period, what is the next step?

<p>Safety shutdown and lockout (C)</p> Signup and view all the answers

What action does the primary controller take if pilot is not established on the second attempt?

<p>Safety shutdown and lockout (A)</p> Signup and view all the answers

What does a BMS do in small mechanically-atomized packaged oil burners when a call for heat is signaled?

<p>Activates ignition transformer and fuel oil SSOV (D)</p> Signup and view all the answers

What must be done if the boiler is gas-fired, according to the text?

<p>Ensure the fuel pressure is below the cutout point of the high gas pressure cut-off switch. (D)</p> Signup and view all the answers

What should be open if the boiler is so configured and requires low combustion air pressure?

<p>Low combustion air pressure fuel cut-off switch (D)</p> Signup and view all the answers

What initiates the boiler ignition sequence?

<p>Closing the main electrical disconnect switch (A)</p> Signup and view all the answers

What is required to be established before the programming controller starts counting the purge?

<p>At least 60% of the high-fire airflow (D)</p> Signup and view all the answers

Which component opens slowly after allowing 10 seconds for the pilot flame to be established?

<p>Main SSOV (A)</p> Signup and view all the answers

What does the flame detector sense after allowing 10 seconds for pilot flame establishment?

<p>Pilot flame (D)</p> Signup and view all the answers

Why is it important to have manual resets on the cut-offs?

<p>To reset limit controls (A)</p> Signup and view all the answers

'Any combustion air damper or air supply interlocks must be satisfied.' What does this statement imply?

<p>Verifying combustion air requirements (C)</p> Signup and view all the answers

'Often, draft fans have a separate electrical feed.' Why is this highlighted in the text?

<p>To indicate additional power sources needed (D)</p> Signup and view all the answers

What action does the BMS take if the pilot is of inadequate strength or too small to reliably light off the main burner?

<p>Shut the pilot SSOV and lock out the burner system (B)</p> Signup and view all the answers

During which stage does the controller determine power quality?

<p>Initiate (B)</p> Signup and view all the answers

What happens if the poor voltage conditions persist for more than 4 minutes?

<p>The primary controller locks out (B)</p> Signup and view all the answers

What occurs during the Main Flame Trial for Ignition (MTFI) period?

<p>The main SSOVs close (A)</p> Signup and view all the answers

If a permissive switch opens during the run period, what action does the BMS take?

<p>Shut off the SSOVs and conduct a post-purge of the furnace (A)</p> Signup and view all the answers

When does the pilot trial for ignition period begin?

<p>When the safe start check is complete (B)</p> Signup and view all the answers

What triggers a safety shutdown and lockout according to the text?

<p>Pilot flame not proven within 10 seconds (A)</p> Signup and view all the answers

What is the significance of the Safe Start stage within the BMS operation sequence?

<p>Begins a safe start check looking for a flame (D)</p> Signup and view all the answers

What is the role of permissive switches during BMS operation?

<p>Monitor elements of the safety circuit (A)</p> Signup and view all the answers

When does the controller enter 'Standby' mode according to the text?

<p>Once there is a call for heat and permissive switches are correct (D)</p> Signup and view all the answers