What is the first step in the typical sequence of operation for most programming controllers described in the text?
What is the first step in the typical sequence of operation for most programming controllers described in the text?
- Start purge
- High airflow
- Pre-ignition interlocks (correct)
- Start draft fan
What component does the BMS start if all permissives and pre-ignition interlocks are satisfied?
What component does the BMS start if all permissives and pre-ignition interlocks are satisfied?
- Pilot SSOV
- Combustion air damper
- Draft fan or fans (correct)
- Igniter
When does the BMS start the igniter and open the pilot SSOV?
When does the BMS start the igniter and open the pilot SSOV?
- Once the pilot is stabilized (correct)
- Before the airflow reaches high fire
- When the fan speed is increased
- After the purge is complete
What is the purpose of the pilot trial for ignition period described in the text?
What is the purpose of the pilot trial for ignition period described in the text?
During which step does the BMS detect high airflow?
During which step does the BMS detect high airflow?
What initiates the purge counter in the BMS?
What initiates the purge counter in the BMS?
What initiates the shutdown sequence in the burner system described in the text?
What initiates the shutdown sequence in the burner system described in the text?
What action causes the flame to be extinguished in the burner system?
What action causes the flame to be extinguished in the burner system?
What is the purpose of the post-purge in the burner system?
What is the purpose of the post-purge in the burner system?
In the burner system, what does the programming controller do during standby mode?
In the burner system, what does the programming controller do during standby mode?
What conditions need to be satisfied for the programming controller to repeat the startup sequence in the burner system?
What conditions need to be satisfied for the programming controller to repeat the startup sequence in the burner system?
What is the purpose of the BMS shutting the pilot SSOV and locking out the burner system?
What is the purpose of the BMS shutting the pilot SSOV and locking out the burner system?
During which stage does the BMS go into a 'safety shutdown and lockout' if the main flame is not established within 10 seconds?
During which stage does the BMS go into a 'safety shutdown and lockout' if the main flame is not established within 10 seconds?
What happens if the pilot flame is not proven within 10 seconds during the Pilot Trial for Ignition period?
What happens if the pilot flame is not proven within 10 seconds during the Pilot Trial for Ignition period?
When does the main SSOV close during the Main Flame Trial for Ignition period?
When does the main SSOV close during the Main Flame Trial for Ignition period?
What does the BMS do if a burner safety limit opens during operation?
What does the BMS do if a burner safety limit opens during operation?
During which stage does the programming controller begin a safe start check?
During which stage does the programming controller begin a safe start check?
What triggers the purge timer to begin counting in the ignition trials?
What triggers the purge timer to begin counting in the ignition trials?
When does the controller return to standby mode during startup?
When does the controller return to standby mode during startup?
What determines if the primary controller enters the Standby stage?
What determines if the primary controller enters the Standby stage?
What occurs if there are poor voltage conditions lasting greater than 4 minutes during initiation?
What occurs if there are poor voltage conditions lasting greater than 4 minutes during initiation?
What happens when a safety shutdown and lockout occurs during the SAFE START CHECK period?
What happens when a safety shutdown and lockout occurs during the SAFE START CHECK period?
What does the programming controller do during a 15-second post-purge after a limit switch opens?
What does the programming controller do during a 15-second post-purge after a limit switch opens?
In which period would a safety shutdown and lockout NOT occur if the main SSOV is energized and there is no flame present?
In which period would a safety shutdown and lockout NOT occur if the main SSOV is energized and there is no flame present?
What is indicated directly on the programming controller during a safety shutdown and lockout?
What is indicated directly on the programming controller during a safety shutdown and lockout?
Which condition does NOT cause a safety shutdown and lockout during the PILOT TRIAL-FOR-IGNITION PERIOD?
Which condition does NOT cause a safety shutdown and lockout during the PILOT TRIAL-FOR-IGNITION PERIOD?
What type of boiler does NOT require controllers with the ability to start draft fans and prove purge conditions?
What type of boiler does NOT require controllers with the ability to start draft fans and prove purge conditions?
What does the burner management system do if it detects an internal fault at any stage of operation?
What does the burner management system do if it detects an internal fault at any stage of operation?
What happens when an operating control like pressuretrol opens in an automatically fired boiler?
What happens when an operating control like pressuretrol opens in an automatically fired boiler?
'Call for heat' in natural draft gas-fired boilers refers to what action?
'Call for heat' in natural draft gas-fired boilers refers to what action?
'Uptake damper' is primarily opened by which component in natural draft gas-fired boilers?
'Uptake damper' is primarily opened by which component in natural draft gas-fired boilers?
What is necessary for the boiler if it is gas-fired according to the given text?
What is necessary for the boiler if it is gas-fired according to the given text?
What initiates the boiler ignition sequence according to the text?
What initiates the boiler ignition sequence according to the text?
What does the programming controller do after confirming the low-fire position?
What does the programming controller do after confirming the low-fire position?
What is a crucial step for oil-fired boilers before starting up according to the text?
What is a crucial step for oil-fired boilers before starting up according to the text?
When does the programming controller energize the main SSOV according to the text?
When does the programming controller energize the main SSOV according to the text?
What must be ensured if a boiler uses oil that requires preheating according to the text?
What must be ensured if a boiler uses oil that requires preheating according to the text?
Which action does NOT need to be performed for dual fuel boilers according to the text?
Which action does NOT need to be performed for dual fuel boilers according to the text?
What is the primary function of the pilot SSOV in a boiler system?
What is the primary function of the pilot SSOV in a boiler system?
If the pilot does not light within 15 to 90 seconds, what action will the primary controller take based on the text?
If the pilot does not light within 15 to 90 seconds, what action will the primary controller take based on the text?
What happens if the main flame goes out during the run period?
What happens if the main flame goes out during the run period?
In oil-fired boilers with no pilot, what signals a call for heat?
In oil-fired boilers with no pilot, what signals a call for heat?
What is the consequence of an ignition failure during boiler startup?
What is the consequence of an ignition failure during boiler startup?
What conditions must be satisfied before a steam or hot water boiler can be started by its programming controller?
What conditions must be satisfied before a steam or hot water boiler can be started by its programming controller?
What operation does a typical programming control perform in a fully automatic boiler system?
What operation does a typical programming control perform in a fully automatic boiler system?
How many main flame failures in a call for heat cycle may prompt a 5-minute natural draft purge based on the text?
How many main flame failures in a call for heat cycle may prompt a 5-minute natural draft purge based on the text?
Study Notes
Typical Sequence of Operation
- The first step involves checking all permissives and pre-ignition interlocks for safety before proceeding.
- If all checks are satisfactory, the burner management system (BMS) initiates the start of the main burner system.
Ignition and Flame Establishment
- The BMS starts the igniter and opens the pilot shut-off valve (SSOV) when all conditions for ignition are met.
- The pilot trial for ignition period is necessary to verify that a stable pilot flame is established before proceeding to the main flame.
- High airflow detection by the BMS occurs during the pre-ignition phase.
- The purge counter is initiated when there’s a need to clear the combustion chamber of unburned gas.
Shutdown Procedures
- The burner system shutdown sequence is triggered by failure to establish a flame or by exceeding safety limits.
- An action such as a failed flame detection or safety limit violation extinguishes the flame in the burner system.
- The post-purge ensures that residual gases are cleared from the system after shutdown for safety.
Operating Modes
- In standby mode, the programming controller continuously monitors system conditions and remains ready for ignition.
- The startup sequence can be repeated only if all safety conditions and pre-ignition checks are satisfied.
BMS Operations
- When the BMS shuts the pilot SSOV, it locks out the burner system to prevent unsafe operation.
- If the main flame is not established within 10 seconds, the BMS goes into safety shutdown and lockout.
- During the pilot trial for ignition period, if the pilot flame is not proven within 10 seconds, the BMS will execute a shutdown.
Timing and Conditions
- The main SSOV closes during the main flame trial for ignition period if the flame is not detected.
- If a burner safety limit opens during operation, the BMS will initiate a safety shutdown.
- The programming controller begins the safe start check during the startup sequence to ensure all systems are operational.
Lights and Indicators
- The controller returns to standby mode once ignition trials are satisfactorily completed, or safety conditions fail.
- Poor voltage conditions lasting over 4 minutes will prevent energizing the burner and could lead to a system lockout.
- During a safety shutdown and lockout, the programming controller displays an indicator to alert operators.
Boiler Operation Conditions
- A safety shutdown and lockout does not occur during the pilot trial for ignition if the main SSOV is energized with no flame present.
- Fire-tube boilers typically do not require controllers that start draft fans or prove purge conditions.
- The BMS detects internal faults at any operational stage and will perform necessary safety actions.
Common Actions and Conditions
- 'Call for heat' in natural draft gas-fired boilers triggers the ignition sequence.
- The uptake damper is primarily opened by the combustion air blower.
- Gas-fired boilers require adequate fuel and air supply for combustion initiation.
- The boiler ignition sequence begins with the command from the programming controller.
Specific Boiler Considerations
- After confirming the low-fire position, the programming controller prepares for fuel delivery.
- Oil-fired boilers necessitate pre-start checks for fuel viscosity and heater functionality.
- The main SSOV is energized once the air-fuel mixture is confirmed safe and ready for ignition.
Fuel Considerations
- If the boiler uses oil requiring preheating, the preheat condition must be ensured before ignition.
- Dual fuel boilers do not require specific actions to ensure functionality besides basic startup checks.
- The primary function of the pilot SSOV is to control the flow of fuel to the pilot burner.
Safety Measures
- If the pilot fails to ignite within 15 to 90 seconds, the primary controller will execute a safety shutdown.
- Main flame loss during the run period triggers an immediate system shutdown for safety.
- In oil-fired boilers without a pilot, the call for heat is managed directly by the control system.
- An ignition failure during startup results in a halt of operations, followed by troubleshooting protocols.
Starting Conditions
- Before initiating a steam or hot water boiler, all safety limits and operational conditions must be verified.
- A typical programming control in fully automatic boiler systems coordinates start-up, operation, and safety functions.
- More than two main flame failures in a single call for heat cycle may require a 5-minute natural draft purge to ensure safety before restart.