Podcast
Questions and Answers
What is the minimum slope required for horizontal drainage piping with a diameter less than 102 mm, according to plumbing regulations?
What is the minimum slope required for horizontal drainage piping with a diameter less than 102 mm, according to plumbing regulations?
- 10 mm per meter or 1%
- 20 mm per meter or 2% (correct)
- 15 mm per meter or 1.5%
- 5 mm per meter or 0.5%
When is the use of a septic tank permitted according to the regulations?
When is the use of a septic tank permitted according to the regulations?
- When a building is used for industrial purposes.
- When the building is a condominium complex.
- When the public sewer is not available within 62 meters distance. (correct)
- When the public sewer connection is more than 50 meters away.
What determines the acceptability of plumbing engineering practices on site?
What determines the acceptability of plumbing engineering practices on site?
- The use of burped pipes and tubing during installation.
- Whether the practices conceal cracks, holes, or imperfections.
- Adherence to accepted engineering practices and standards. (correct)
- The installers preferred method of connecting pipes.
Which fitting is prohibited in venting systems?
Which fitting is prohibited in venting systems?
What is the primary reason for protecting piping with polyethylene sheathing?
What is the primary reason for protecting piping with polyethylene sheathing?
What is the correct vertical distance range for a building sewer installation below the finished ground surface?
What is the correct vertical distance range for a building sewer installation below the finished ground surface?
What support interval is required for copper tubing in vertical piping systems?
What support interval is required for copper tubing in vertical piping systems?
How often should hubless or compression gasket joints be supported in horizontal piping?
How often should hubless or compression gasket joints be supported in horizontal piping?
If a trench is excavated deeper than the footing and runs parallel to it, at what angle must it be?
If a trench is excavated deeper than the footing and runs parallel to it, at what angle must it be?
When using driven pipes, what size should the drive pipe be relative to the pipe being laid?
When using driven pipes, what size should the drive pipe be relative to the pipe being laid?
Flashcards
Waste Water Disposal
Waste Water Disposal
Disposing of waste in unauthorized locations is strictly prohibited.
Horizontal Drainage Slope
Horizontal Drainage Slope
For pipes under 102 mm diameter, the slope should be 20mm per meter or 2%. For pipes 102 mm or larger, the slope should be 10 mm per meter or 1%.
Drainage Flow Direction
Drainage Flow Direction
Changes in direction of drainage flow use bends such as 1/16 (22.5 degrees), 1/8 (45 degrees), or 1/6 (60 degrees) bends.
Plumbing Fixture Connections
Plumbing Fixture Connections
Signup and view all the flashcards
Sewer Connection Requirements
Sewer Connection Requirements
Signup and view all the flashcards
Sewer System Damage
Sewer System Damage
Signup and view all the flashcards
Industrial Waste Disposal
Industrial Waste Disposal
Signup and view all the flashcards
Plumbing System Location
Plumbing System Location
Signup and view all the flashcards
Plumbing Workmanship
Plumbing Workmanship
Signup and view all the flashcards
Piping Protection
Piping Protection
Signup and view all the flashcards
Study Notes
- General regulations for plumbing cover waste disposal, drainage, and system installation
Waste Water Disposal (Section 301)
- Waste disposal is prohibited in any place
Horizontal Drainage Piping Grade (Section 302)
- The standard slope is 20mm per meter or 2%
- For pipes less than 102 mm in diameter the exception is smaller at 10mm per meter or 1%
- Exceptions to the standard slope include:
- Excessive drainage line depth
- Terrain features
- Existing building arrangements
Changes in Drainage Flow Direction (Section 303)
- Acceptable bends for directional changes include 1/16 (22.5 degrees), 1/8 (45 degrees), and 1/6 (60 degrees) bends
Horizontal-to-Vertical Direction Change (Section 303.2)
- Acceptable fittings include:
- Wye combination
- Double sanitary tee
- Sanitary tee
- Combination wye and 1/8 bend
Horizontal-to-Horizontal Direction Change (Section 303.3)
- Acceptable fittings include:
- 45 wye branch
- Combination wye and 1/8 branch
Vertical-to-Horizontal Direction Change (Section 303.4)
- Acceptable fittings include:
- 45 branches, long sweep 60, and offset
- Combination wye and 1/8 branch
Piping System Connections (Section 304)
- All plumbing fixtures must connect properly to the drainage system
Sewer Requirements (Section 305)
- Building sewer connections to a public sewer are mandatory
- Septic tanks are required if a public sewer is unavailable (farther than 62 meters)
Damage to Drainage/Sewer Systems (Section 306)
- Depositing harmful substances into systems is prohibited
- Storm sewers are exclusive to rainwater
- Soil and waste pipes are for public or sanitary sewers
- Septic tanks for houses should be watertight
Industrial Waste (Section 307)
- Industrial waste must be treated and not discharged into the ground or waterways
System Location (Section 308)
- Plumbing systems are restricted to the building they serve
Improper Location (Section 309)
- Plumbing that interferes with normal operations is prohibited
Workmanship (Section 310)
- Installations should use accepted engineering practices
- Cracks, holes, and imperfections are not allowed
- Pipe and tubing ends must be "REAMED"
Prohibited Practices & Fittings (Section 311)
- Prohibited fittings for venting include double hub fittings, single or double tee branch, single or double tapped tee branch, side inlet quarter bends, running threads, and band or saddles
- Hubless pipes should not use neoprene gaskets
- Drainage or vents should not be drilled and tapped
- Cast iron soil pipes should not be threaded
- Waste connections to closet bends or stubs of water closets are prohibited
- Vent pipes shouldn't be used as soil or waste pipes, and vice versa
- Single drainage and venting systems must have a vent
- Piping connections that obstruct air, water, and sewage flow are prohibited
- Increasing closet bend or stub diameter from 72 mm to 102 mm is not considered an obstruction
Valves and Accessibility
- Gate and check valves must be accessible
- Valves, pipes, and fittings are to be installed according to flow direction
Independent System (Section 312)
- Independent connections to private or public sewers are required
Repairs and Alterations (Section 313)
- Notify administrators of necessary changes
- All drainage and vent system openings must be capped or plugged
Piping Protection (Section 314)
- Piping must be protected from breakage by embedded metal pipe sleeves
- Polyethylene sheaths protect from external corrosion
- Voids between pipes and sleeves should be sealed with bitumen
- Pipes cannot be directly embedded in concrete or masonry
- Structural members cannot be weakened
- Trenches deeper than footings and parallel to them must be at a 45-degree angle
- Zone of Effluence line at 45 degrees
- Building sewer installation should be 0.3 to 0.6 meters below the finish ground surface
- Pipes must be protected from corrosion, erosion, or mechanical damage by inside lining, outside coating, proper bedding, and top shielding with concrete blocks
Hangers and Supports (Section 315)
- Vertical piping should be supported at every storey for cast iron soil pipes, at every other storey height for screwed pipes, every storey at 3 meters on center for copper tubing, every storey at 1.2 meters for lead pipes, and 1 meter for plastic pipes
Horizontal Piping
- Horizontal piping must be supported at close intervals to maintain alignment and prevent sagging
- Cast iron soil pipes must be supported at every joint (1.5 meters) or 3 meters when exceeding 1.5 meters in length
- Hubless or compression gasket joints need support every other joint (0.45 meters for hub joints)
- Developed lengths exceeding 1.2 meters need support at each joint
- Each horizontal branch connection and suspended line needs support
- Screwed pipes should be supported at 3 meters for 19 mm and smaller, and at 3.6 meters for 25 mm and larger
- Copper tubing should be supported at 1.8 meters for 38 mm and smaller, and at 3 meters for 51 mm and larger
- Lead pipes should be supported along their entire length
- Piping in the ground should have firm bedding for the entire length or concrete cradle support
- Plastic tubes should be supported with stiff metal or wood backing for 38 mm and smaller and metal hangers for 51 mm and larger
Hangers and Anchorage
- Sufficient strength is required, and piping must be adequately anchored or supported.
Trenching, Excavation, and Backfill (Section 316)
- Tunnels must have a clear height of 0.60 meters above the pipe, minimum length should be 1/2 the depth of the trench, and maximum length not exceeding 2.4 meters
- Driven pipes must be at least one pipe size larger
- Open trenches should be backfilled in layers of 0.30 meters above the top of the pipe
Studying That Suits You
Use AI to generate personalized quizzes and flashcards to suit your learning preferences.