MSENSE® DGA 9 Installation Guidelines
50 Questions
0 Views

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to lesson

Podcast

Play an AI-generated podcast conversation about this lesson

Questions and Answers

What is the primary purpose of the technical document for the MSENSE® DGA 9?

  • To detail the installation, connection, commissioning, and monitoring (correct)
  • To outline marketing strategies and pricing
  • To provide guidelines for storage and distribution
  • To promote the product to potential customers
  • Who is responsible for customer inquiries about the MSENSE® DGA 9?

  • EMH Energie-Messtechnik GmbH
  • MTE Meter Test Equipment AG
  • MR Service & Complaint at Maschinenfabrik Reinhausen GmbH (correct)
  • Landis + Gyr-Strasse 1
  • Which company manufactures the MSENSE® DGA 9?

  • EMH Energie-Messtechnik GmbH
  • Landis + Gyr-Strasse 1
  • Maschinenfabrik Reinhausen GmbH (correct)
  • MTE Meter Test Equipment AG
  • What should accompany the technical document to ensure completeness?

    <p>Other applicable documents</p> Signup and view all the answers

    What is reflected in a new edition of the technical file?

    <p>Significant changes to the technical specifications</p> Signup and view all the answers

    What is the required thread depth for the threaded flange used in the installation of the MSENSE® DGA 9?

    <p>At least 25 mm</p> Signup and view all the answers

    What is the recommended method of connection for the MSENSE® DGA 9 to ensure no turning of the device during installation?

    <p>Threaded joint</p> Signup and view all the answers

    What type of valve is suitable for the installation of the MSENSE® DGA 9?

    <p>Gate valve or ball valve</p> Signup and view all the answers

    How much free space is required around the center of the connecting flange for the flange connection of the MSENSE® DGA 9?

    <p>430 mm in diameter</p> Signup and view all the answers

    What should be specified when ordering the MSENSE® DGA 9?

    <p>The voltage version</p> Signup and view all the answers

    What should you do immediately after noticing no more air bubbles escaping from the sample hose?

    <p>Close the vent screw.</p> Signup and view all the answers

    What should be used to seal the threaded joint during indirect mounting of the MSENSE® DGA 9?

    <p>Flat gasket.</p> Signup and view all the answers

    What is the correct procedure to clean the external thread of the connecting unit?

    <p>Use a brass brush.</p> Signup and view all the answers

    Before installing the MSENSE® DGA 9, what should you ensure about the protective cap?

    <p>It should not be removed until ready for installation.</p> Signup and view all the answers

    How should the MSENSE® DGA 9 be positioned on the threaded joint during installation?

    <p>Horizontally without twisting.</p> Signup and view all the answers

    What should be done before installing or removing the MSENSE® DGA 9?

    <p>Open the aeration screw</p> Signup and view all the answers

    Which of the following practices is recommended when mounting the MSENSE® DGA 9?

    <p>Wear safety gloves</p> Signup and view all the answers

    What can lead to the expiry of the warranty claim for the MSENSE® DGA 9?

    <p>Improper handling of the connection unit</p> Signup and view all the answers

    What type of tools should not be used for handling the MSENSE® DGA 9?

    <p>Multiple slip-joint pliers</p> Signup and view all the answers

    What is required if the MSENSE® DGA 9 is to be installed over 1 m high?

    <p>Specially trained personnel and lifting equipment</p> Signup and view all the answers

    What does the filling level L1 indicate?

    <p>Sufficient filling has been achieved</p> Signup and view all the answers

    Which component is monitored for the filling time?

    <p>Flow measurement</p> Signup and view all the answers

    What occurs during the degassing process?

    <p>Gases dissolved in oil are released into the air</p> Signup and view all the answers

    Which error is detectable by the filling sensors?

    <p>Filling level L2 reached</p> Signup and view all the answers

    What happens if the filling level drops according to fault detection?

    <p>Filling sensors report a low condition</p> Signup and view all the answers

    The device is designed to detect very fast developing faults and protect itself from them.

    <p>False</p> Signup and view all the answers

    Using personal protective equipment is essential to minimize risks during installation and operation of the product.

    <p>True</p> Signup and view all the answers

    The intended use of the device includes operating it without adhering to the technical specifications provided.

    <p>False</p> Signup and view all the answers

    Wearing loose clothing and jewelry is recommended when working near rotating parts of the device.

    <p>False</p> Signup and view all the answers

    All necessary work on the device should be performed by untrained personnel to ensure effective operation.

    <p>False</p> Signup and view all the answers

    The MSENSE® DGA 9 is manufactured by Maschinenfabrik Reinhausen GmbH exclusively.

    <p>False</p> Signup and view all the answers

    Legal provisions regarding the MSENSE® DGA 9 are mentioned in the document.

    <p>True</p> Signup and view all the answers

    MTE Meter Test Equipment AG holds all copyright rights for the MSENSE® DGA 9 documentation.

    <p>True</p> Signup and view all the answers

    The installation and operating instructions for the MSENSE® DGA 9 may be modified without prior notice.

    <p>True</p> Signup and view all the answers

    The contact information provided includes physical addresses located in France and Spain.

    <p>False</p> Signup and view all the answers

    The connection terminals X403 are used for relay outputs 1... 4.

    <p>False</p> Signup and view all the answers

    Relay outputs 5 and 6 are connected through terminals X302.

    <p>True</p> Signup and view all the answers

    The RS485 interface is exclusively used for analogue outputs.

    <p>False</p> Signup and view all the answers

    Analogue outputs can range from 0 to 20 mA DC as stated in the terminal specifications.

    <p>True</p> Signup and view all the answers

    Relay outputs 7 through 10 are accessible via connection terminals X401.

    <p>False</p> Signup and view all the answers

    The MSENSE® DGA 9 can safely be installed on a knee pipe or pipe bend.

    <p>False</p> Signup and view all the answers

    It is permissible to clean the MSENSE® DGA 9 with a solvent.

    <p>False</p> Signup and view all the answers

    The protective cap should be used after dismantling the device to prevent damage.

    <p>True</p> Signup and view all the answers

    External cables can be laid above the heating units without concern.

    <p>False</p> Signup and view all the answers

    The MSENSE® DGA 9 must be removed before every gas release or filling of the transformer.

    <p>True</p> Signup and view all the answers

    The MSENSE® DGA 9 uses a 64-bit processor with a frequency of 240 MHz.

    <p>False</p> Signup and view all the answers

    The flash memory of the MSENSE® DGA 9 has a capacity of 128 Mbyte.

    <p>True</p> Signup and view all the answers

    Each alarm status change in the MSENSE® DGA 9 requires 20 bytes of storage space.

    <p>False</p> Signup and view all the answers

    When using additional sensors, the storage capacity of the MSENSE® DGA 9 is determined by the number of sensors and the chosen storage interval.

    <p>True</p> Signup and view all the answers

    The relative moisture of the oil is displayed continuously on the main screen of the MSENSE® DGA 9.

    <p>False</p> Signup and view all the answers

    Study Notes

    Introduction

    • Technical file provides guidance for the installation, connection, commissioning, and monitoring of MSENSE® DGA 9.
    • Intended for specially trained and authorized personnel.

    Contact Information

    • Contact for inquiries: MR Service & Complaint at Maschinenfabrik Reinhausen GmbH, Regensburg, Germany.
    • Email: [email protected], [email protected].
    • Notable manufacturers: EMH Energie-Messtechnik GmbH (Germany) and MTE Meter Test Equipment AG (Switzerland).

    Safety and Handling

    • Open aeration screw before installation or removal to avoid accidents.
    • Avoid mounting on galvanized connections to prevent erroneous readings.
    • Do not use high-pressure cleaners for maintenance to avert damage.
    • Recommended tools include an M55 open-ended spanner or a 1½" adjustable spanner.
    • Incorrect handling, such as the use of solvents or improper tools, voids the warranty.

    Installation Guidelines

    • Visual inspections of the MSENSE® DGA 9 required prior to installation.
    • Connection options include G 1½" ISO DIN 228-1 or 1½" NPT ANSI B 1.20.1.
    • Device should be installed on a gate valve with full passage or a ball valve on the transformer.
    • Ensure ample space (430 mm diameter) is available for direct flange connections.

    Connection Types

    • Flange Connection: Directly screws to the threaded flange; requires at least 25 mm thread depth.
    • Threaded Joint: Uses a union nut and flat sealing for easier installation without twisting the device.

    Voltage and Sample Hose Connection

    • MSENSE® DGA 9 is available in 4 voltage configurations.
    • Sample hose must be secured to eliminate air bubbles and oil residues must be cleaned with a dry cloth.

    Indirect Mounting

    • Involves fixing the device with a union nut on a threaded joint; requires a gasket as a seal.
    • Protective cap should remain in place until installation.

    Device Alignment

    • Align the device with vent screw at the 12 o'clock position after installation.
    • Ensure gasket is in place between the MSENSE® DGA 9 and the screw connection.

    Monitoring and Safety Functions

    • Monitored components include filling sensors and pressure sensors.
    • Detects errors with filling levels, flow measurement, and operational timing.

    Degasification Process

    • Releases dissolved gases from oil through circulation into the air, achieving a balance in gas proportions between oil and air.

    Contact Information

    • For inquiries about the MSENSE® DGA 9, contact MR Service & Complaint at Maschinenfabrik Reinhausen GmbH in Regensburg, Germany.
    • Additional manufacturer details: EMH Energie-Messtechnik GmbH (Germany) and MTE Meter Test Equipment AG (Switzerland).
    • Emails for service and complaints: [email protected], [email protected].

    Product Overview

    • MSENSE® DGA 9 is designed for detecting gas-in-oil through microprocessor control.
    • Utilizes a 32-bit “Cold-fire” processor operating at 240 MHz.
    • Capable of storing measured data for approximately 10 years in a 128 Mbyte flash memory.

    Safety Guidelines

    • Not designed to detect fast-developing faults; requires additional safety devices for such protection.
    • Installation must ensure compliance with operating conditions to minimize risks to personnel, property, and the environment.
    • Personal protective equipment (PPE) is crucial; avoid damaged gear and loose clothing near moving parts.
    • Avoid contact with hydrocarbon compounds and do not use solvents for cleaning; only dry cloth recommended.
    • Ensure proper ventilation and avoid exposing the device to a vacuum.

    Installation Requirements

    • Position MSENSE® DGA 9 at least 100 cm below the oil filling level.
    • Avoid installation near pipes or bends to prevent turbulence-related issues.
    • Always switch off power supply before servicing and ensure the device is removed from the transformer valve before gas release or filling.

    Connection Details

    • Features multiple relay output terminals (X402, X403) for connecting to relay systems.
    • Analogue outputs (X301, X302, X303) available for data monitoring, each supporting 0/4 - 20 mA DC.
    • RS485 interface (X304) for digital communication intended for service purposes.

    Memory and Data Management

    • Memory calculations account for the number of sensors and storage intervals; additional sensors decrease memory availability.
    • Each alarm status change consumes 12 bytes of memory, affecting overall storage capacity.
    • Regular data reading using MR MSET DGA software is recommended to avoid data loss.

    Main Screen Functionality

    • Displays relative and absolute oil moisture alternately with a 3-second change interval, providing crucial real-time data for users.

    Studying That Suits You

    Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

    Quiz Team

    Description

    This quiz covers the installation, connection, and commissioning of the MSENSE® DGA 9 device. It includes essential safety precautions, recommended tools, and handling instructions to ensure proper setup and maintenance. Designed for specially trained personnel, it emphasizes the importance of correct procedures to avoid warranty voiding issues.