Which type of LED luminaires must be identified as Type IC when installed in contact with thermal insulation?
Which type of LED luminaires must be identified as Type IC when installed in contact with thermal insulation?
- Type IB
- Type ID
- Type IA
- Type IC (correct)
What happens if a listed Type IC recessed luminaire is mislamped and overheats?
What happens if a listed Type IC recessed luminaire is mislamped and overheats?
- It emits a warning signal
- It automatically shuts off (correct)
- It causes a fire
- It continues to operate normally
In what type of construction can luminaires marked 'FOR USE IN NON-FIRE-RATED' be installed?
In what type of construction can luminaires marked 'FOR USE IN NON-FIRE-RATED' be installed?
- No specific type of construction
- Non-fire-rated construction (correct)
- Both fire-resistant and non-fire-rated construction
- Fire-resistant construction
According to the text, what is the minimum wire size for pendant conductors with intermediate or candelabra-base lampholders?
According to the text, what is the minimum wire size for pendant conductors with intermediate or candelabra-base lampholders?
According to the text, how long should pendant conductors be twisted together if they are not cabled in a listed assembly?
According to the text, how long should pendant conductors be twisted together if they are not cabled in a listed assembly?
According to the text, what type of cord is required for cord-connected showcases?
According to the text, what type of cord is required for cord-connected showcases?
According to the text, what is the minimum size of equipment grounding conductor required for cord-connected showcases?
According to the text, what is the minimum size of equipment grounding conductor required for cord-connected showcases?
According to the text, how should replacement luminaires be connected to an equipment grounding conductor?
According to the text, how should replacement luminaires be connected to an equipment grounding conductor?
According to the text, how should wiring on or within luminaires be arranged?
According to the text, how should wiring on or within luminaires be arranged?
According to the text, how should luminaires be wired in terms of polarization?
According to the text, how should luminaires be wired in terms of polarization?
Which type of incandescent lamp base is suitable for use if rated over 300 watts?
Which type of incandescent lamp base is suitable for use if rated over 300 watts?
What are the categories for fluorescent ballast enclosures according to UL?
What are the categories for fluorescent ballast enclosures according to UL?
Where are HID ballasts suitable for use?
Where are HID ballasts suitable for use?
What is the maximum temperature that adjacent combustible material should be subjected to in recessed luminaires?
What is the maximum temperature that adjacent combustible material should be subjected to in recessed luminaires?
Which of the following conditions must apply in order for a disconnecting means to not be required for every luminaire in a building area?
Which of the following conditions must apply in order for a disconnecting means to not be required for every luminaire in a building area?
When connected to multiwire branch circuits, what conductors should the disconnecting means simultaneously break?
When connected to multiwire branch circuits, what conductors should the disconnecting means simultaneously break?
Where should the disconnecting means be located for a luminaire?
Where should the disconnecting means be located for a luminaire?
What conductors should be disconnected by the disconnecting means for a luminaire?
What conductors should be disconnected by the disconnecting means for a luminaire?
According to the UL Luminaires Marking and Application Guide, 2016, how are luminaires listed for use as raceways marked?
According to the UL Luminaires Marking and Application Guide, 2016, how are luminaires listed for use as raceways marked?
According to 410.62(C)(1)(c), what is permitted to supply the luminaires in place of a grounding-type attachment plug?
According to 410.62(C)(1)(c), what is permitted to supply the luminaires in place of a grounding-type attachment plug?
According to 410.62(C)(1), where must the cord be located if a luminaire is cord connected?
According to 410.62(C)(1), where must the cord be located if a luminaire is cord connected?
According to 410.64, when can luminaires be used as a raceway for circuit conductors?
According to 410.64, when can luminaires be used as a raceway for circuit conductors?
According to the text, luminaires designed for end-to-end connection to form a continuous assembly, or luminaires connected together by recognized wiring methods, shall be permitted to contain the conductors of a 2-wire branch circuit, or one multiwire branch circuit, supplying the connected luminaires and shall not be required to be listed as a raceway. One additional 2-wire branch circuit separately supplying one or more of the connected luminaires shall also be permitted.
According to the text, luminaires designed for end-to-end connection to form a continuous assembly, or luminaires connected together by recognized wiring methods, shall be permitted to contain the conductors of a 2-wire branch circuit, or one multiwire branch circuit, supplying the connected luminaires and shall not be required to be listed as a raceway. One additional 2-wire branch circuit separately supplying one or more of the connected luminaires shall also be permitted.
According to the text, feeder and branch-circuit conductors within 75 mm (3 in.) of a ballast, LED driver, power supply, or transformer shall have an insulation temperature rating not lower than 90°C (194°F), unless supplying a luminaire marked as suitable for a different insulation temperature.
According to the text, feeder and branch-circuit conductors within 75 mm (3 in.) of a ballast, LED driver, power supply, or transformer shall have an insulation temperature rating not lower than 90°C (194°F), unless supplying a luminaire marked as suitable for a different insulation temperature.
According to the text, where control conductors are spliced, terminated, or connected in the same luminaire or enclosure as the branch-circuit conductors, the field-connected control conductor shall not be of a color reserved for the grounded branch-circuit conductor or the equipment grounding conductor.
According to the text, where control conductors are spliced, terminated, or connected in the same luminaire or enclosure as the branch-circuit conductors, the field-connected control conductor shall not be of a color reserved for the grounded branch-circuit conductor or the equipment grounding conductor.
According to the text, fluorescent or LED luminaires that utilize double-ended lamps and contain ballast(s) or LED driver(s) that can be serviced in place shall have a disconnecting means either internal or external to each luminaire.
According to the text, fluorescent or LED luminaires that utilize double-ended lamps and contain ballast(s) or LED driver(s) that can be serviced in place shall have a disconnecting means either internal or external to each luminaire.
According to the text, where should a germicidal irradiation system not be installed?
According to the text, where should a germicidal irradiation system not be installed?
According to the text, what is the scope of Article 411?
According to the text, what is the scope of Article 411?
According to the text, what should be provided by the system manufacturer or clearly specified in the installation instructions?
According to the text, what should be provided by the system manufacturer or clearly specified in the installation instructions?
According to the text, what type of luminaires are exempt from the thermal protection requirement?
According to the text, what type of luminaires are exempt from the thermal protection requirement?
According to the text, what type of ballast is not required to be thermally protected in a fluorescent luminaire with straight tubular lamps?
According to the text, what type of ballast is not required to be thermally protected in a fluorescent luminaire with straight tubular lamps?
According to the text, what is the maximum allowable wattage of lamps for incandescent lamp luminaires?
According to the text, what is the maximum allowable wattage of lamps for incandescent lamp luminaires?
According to the text, what type of transformers shall not be used in luminaires?
According to the text, what type of transformers shall not be used in luminaires?
According to the text, what is the maximum load that can be connected to a lighting track?
According to the text, what is the maximum load that can be connected to a lighting track?
According to the text, where is lighting track not permitted to be installed?
According to the text, where is lighting track not permitted to be installed?
According to the text, how should fittings be connected to lighting track?
According to the text, how should fittings be connected to lighting track?
According to the text, what is heavy-duty lighting track?
According to the text, what is heavy-duty lighting track?
According to the text, what is the maximum length of tap conductors running from the luminaire terminal connection to an outlet box?
According to the text, what is the maximum length of tap conductors running from the luminaire terminal connection to an outlet box?
According to the text, where should luminaires recessed in ceilings, floors, or walls not be used to access?
According to the text, where should luminaires recessed in ceilings, floors, or walls not be used to access?
According to the text, what is the minimum length of Type AC or MC cable that tap conductors running from the luminaire terminal connection to an outlet box should be?
According to the text, what is the minimum length of Type AC or MC cable that tap conductors running from the luminaire terminal connection to an outlet box should be?
According to Article 547 of the NEC, what are the requirements for agricultural buildings?
According to Article 547 of the NEC, what are the requirements for agricultural buildings?
What is the purpose of horticultural lighting equipment?
What is the purpose of horticultural lighting equipment?
According to 410.178, when is flexible cord permitted for horticultural lighting equipment?
According to 410.178, when is flexible cord permitted for horticultural lighting equipment?
What are the requirements for luminaires intended to emit germicidal irradiation?
What are the requirements for luminaires intended to emit germicidal irradiation?
Which type of ballast is more energy efficient than single- or three-lamp ballasts?
Which type of ballast is more energy efficient than single- or three-lamp ballasts?
What is the maximum voltage that the secondary circuit of a transformer can have under any load condition?
What is the maximum voltage that the secondary circuit of a transformer can have under any load condition?
Where should transformers be located to prevent adjacent combustible materials from being subjected to excessive temperatures?
Where should transformers be located to prevent adjacent combustible materials from being subjected to excessive temperatures?
What is the minimum insulation temperature rating required for feeder and branch-circuit conductors within 75 mm (3 in.) of a ballast, LED driver, power supply, or transformer?
What is the minimum insulation temperature rating required for feeder and branch-circuit conductors within 75 mm (3 in.) of a ballast, LED driver, power supply, or transformer?
According to the text, what type of lamps are suitable for use in open luminaires?
According to the text, what type of lamps are suitable for use in open luminaires?
According to the text, what is the maximum open-circuit voltage allowed for equipment installed in dwelling occupancies?
According to the text, what is the maximum open-circuit voltage allowed for equipment installed in dwelling occupancies?
According to the text, what is considered as combustible low-density cellulose fiberboard?
According to the text, what is considered as combustible low-density cellulose fiberboard?
According to the text, what type of luminaires require auxiliary equipment to be enclosed in accessible, permanently installed metal cabinets?
According to the text, what type of luminaires require auxiliary equipment to be enclosed in accessible, permanently installed metal cabinets?
According to the text, what is the maximum allowable wattage of lamps for incandescent lamp luminaires?
According to the text, what is the maximum allowable wattage of lamps for incandescent lamp luminaires?
According to the text, what is the maximum open-circuit voltage allowed for equipment installed in dwelling occupancies?
According to the text, what is the maximum open-circuit voltage allowed for equipment installed in dwelling occupancies?
According to the text, where should transformers be located to prevent adjacent combustible materials from being subjected to excessive temperatures?
According to the text, where should transformers be located to prevent adjacent combustible materials from being subjected to excessive temperatures?
According to Article 411, what is the maximum operating voltage allowed for low-voltage lighting systems and their associated components?
According to Article 411, what is the maximum operating voltage allowed for low-voltage lighting systems and their associated components?
According to Article 411, what are the components that can be assembled to create a low-voltage lighting system?
According to Article 411, what are the components that can be assembled to create a low-voltage lighting system?
According to Article 411, what is the scope of this article?
According to Article 411, what is the scope of this article?
According to the text, where should the GFCI be located for vending machines?
According to the text, where should the GFCI be located for vending machines?
According to the text, what is the minimum branch-circuit rating for a continuous load appliance?
According to the text, what is the minimum branch-circuit rating for a continuous load appliance?
According to the text, what is the minimum ampacity of branch-circuit conductors for motor-operated appliances without a marked rating?
According to the text, what is the minimum ampacity of branch-circuit conductors for motor-operated appliances without a marked rating?
According to the text, what is the maximum demand for overcurrent protection for household-type appliances with surface heating elements?
According to the text, what is the maximum demand for overcurrent protection for household-type appliances with surface heating elements?
Which type of heating appliances shall have the heating elements subdivided?
Which type of heating appliances shall have the heating elements subdivided?
What is the maximum load that each subdivided load in heating appliances shall not exceed?
What is the maximum load that each subdivided load in heating appliances shall not exceed?
What is the maximum protection for each subdivided load in heating appliances?
What is the maximum protection for each subdivided load in heating appliances?
What are the requirements for commercial kitchen and cooking appliances using sheathed-type heating elements?
What are the requirements for commercial kitchen and cooking appliances using sheathed-type heating elements?
Which of the following is true about low-voltage lighting systems according to Article 411?
Which of the following is true about low-voltage lighting systems according to Article 411?
In wet locations where contact with the lighting system might occur, what is the maximum voltage limit according to the text?
In wet locations where contact with the lighting system might occur, what is the maximum voltage limit according to the text?
According to Article 411, how should exposed bare conductors and current-carrying parts be installed?
According to Article 411, how should exposed bare conductors and current-carrying parts be installed?
According to the text, what distinguishes Article 411 from Article 410?
According to the text, what distinguishes Article 411 from Article 410?
According to the text, what is the minimum length of the cord for an electrically operated in-sink waste disposer?
According to the text, what is the minimum length of the cord for an electrically operated in-sink waste disposer?
According to the text, where should the receptacle for a trash compactor be located?
According to the text, where should the receptacle for a trash compactor be located?
According to the text, what is the maximum length of the cord for a built-in dishwasher?
According to the text, what is the maximum length of the cord for a built-in dishwasher?
According to the text, where should the receptacle for a built-in dishwasher be located?
According to the text, where should the receptacle for a built-in dishwasher be located?
According to 422.17, which one of the following conditions must be met in order for range hoods and over-the-range microwave ovens to be permitted to be cord-and-plug-connected?
According to 422.17, which one of the following conditions must be met in order for range hoods and over-the-range microwave ovens to be permitted to be cord-and-plug-connected?
According to 422.18, which one of the following is a method for supporting ceiling-suspended (paddle) fans?
According to 422.18, which one of the following is a method for supporting ceiling-suspended (paddle) fans?
According to 422.19, what is the purpose of providing sufficient space in the combined volume of the canopy of ceiling-suspended (paddle) fans and outlet box?
According to 422.19, what is the purpose of providing sufficient space in the combined volume of the canopy of ceiling-suspended (paddle) fans and outlet box?
According to 422.30, what is the requirement for the disconnecting means of each appliance supplied by more than one branch circuit or feeder?
According to 422.30, what is the requirement for the disconnecting means of each appliance supplied by more than one branch circuit or feeder?
Which of the following is NOT considered fixed electric space-heating equipment according to the text?
Which of the following is NOT considered fixed electric space-heating equipment according to the text?
What is the maximum amperage rating for branch circuits supplying two or more outlets for fixed electric space-heating equipment in a dwelling unit?
What is the maximum amperage rating for branch circuits supplying two or more outlets for fixed electric space-heating equipment in a dwelling unit?
What is the minimum ampacity of the branch-circuit conductor(s) for fixed electric space-heating equipment and any associated motor(s)?
What is the minimum ampacity of the branch-circuit conductor(s) for fixed electric space-heating equipment and any associated motor(s)?
What type of heating equipment must be listed and labeled according to the text?
What type of heating equipment must be listed and labeled according to the text?
According to the text, what is the minimum ampacity of field-wired conductors between the heater and the supplementary overcurrent protective devices for heaters rated less than 50 kW?
According to the text, what is the minimum ampacity of field-wired conductors between the heater and the supplementary overcurrent protective devices for heaters rated less than 50 kW?
According to the text, what is the maximum ampacity of field-wired conductors between the heater and the supplementary overcurrent protective devices for heaters rated 50 kW or more?
According to the text, what is the maximum ampacity of field-wired conductors between the heater and the supplementary overcurrent protective devices for heaters rated 50 kW or more?
According to the text, what is the requirement for the ampacity of field-wired conductors between the heater and the supplementary overcurrent protective devices for heaters rated 50 kW or more?
According to the text, what is the requirement for the ampacity of field-wired conductors between the heater and the supplementary overcurrent protective devices for heaters rated 50 kW or more?
Which of the following is true about disconnecting means for motor-operated appliances rated over 1/8 horsepower?
Which of the following is true about disconnecting means for motor-operated appliances rated over 1/8 horsepower?
According to the text, which of the following is a requirement for cord-and-plug-connected or attachment fitting-connected appliances?
According to the text, which of the following is a requirement for cord-and-plug-connected or attachment fitting-connected appliances?
According to the text, where can a cord-and-plug connection be made for a household electric range?
According to the text, where can a cord-and-plug connection be made for a household electric range?
According to the text, what is the purpose of an approved stand for smoothing irons and other cord-and-plug-connected electrically heated appliances?
According to the text, what is the purpose of an approved stand for smoothing irons and other cord-and-plug-connected electrically heated appliances?
According to 422.47, what is the requirement for storage or instantaneous-type water heaters?
According to 422.47, what is the requirement for storage or instantaneous-type water heaters?
According to 422.48, what type of lampholders are permitted for infrared heating lamps rated at 300 watts or less?
According to 422.48, what type of lampholders are permitted for infrared heating lamps rated at 300 watts or less?
According to the text, what are infrared lamps designed to do?
According to the text, what are infrared lamps designed to do?
According to 422.34, where should the other disconnecting means be located in a multifamily dwelling?
According to 422.34, where should the other disconnecting means be located in a multifamily dwelling?
According to 422.40, what type of appliances are required to have a signal or an integral temperature-limiting device in other than dwelling-type occupancies?
According to 422.40, what type of appliances are required to have a signal or an integral temperature-limiting device in other than dwelling-type occupancies?
According to the text, which of the following devices de-energize the supply to the appliance when leakage current exceeds a predetermined value?
According to the text, which of the following devices de-energize the supply to the appliance when leakage current exceeds a predetermined value?
According to 422.44, how should electric heaters of the cord-and-plug-connected immersion type be constructed and installed?
According to 422.44, how should electric heaters of the cord-and-plug-connected immersion type be constructed and installed?
According to the text, what is the ampere rating required for the disconnecting means specified in 424.19(A) and (B) for heating equipment supplied by more than one source?
According to the text, what is the ampere rating required for the disconnecting means specified in 424.19(A) and (B) for heating equipment supplied by more than one source?
According to the text, what is the purpose of grouping and identifying the disconnecting means for heating equipment supplied by more than one source?
According to the text, what is the purpose of grouping and identifying the disconnecting means for heating equipment supplied by more than one source?
According to the text, what is the maximum open-circuit voltage allowed for equipment installed in dwelling occupancies?
According to the text, what is the maximum open-circuit voltage allowed for equipment installed in dwelling occupancies?
According to the text, where should the disconnecting means be located for fixed electric space-heating equipment with supplementary overcurrent protection?
According to the text, where should the disconnecting means be located for fixed electric space-heating equipment with supplementary overcurrent protection?
According to the text, what are the conditions for thermostatically controlled switching devices and combination thermostats to serve as both controllers and disconnecting means?
According to the text, what are the conditions for thermostatically controlled switching devices and combination thermostats to serve as both controllers and disconnecting means?
According to the text, what are the requirements for switches and circuit breakers used as disconnecting means?
According to the text, what are the requirements for switches and circuit breakers used as disconnecting means?
According to the text, what is the maximum protection for resistance-type heating elements in electric space-heating equipment?
According to the text, what is the maximum protection for resistance-type heating elements in electric space-heating equipment?
According to the text, what are the conditions for supplementary overcurrent protective devices for the subdivided loads specified in 424.22(B)?
According to the text, what are the conditions for supplementary overcurrent protective devices for the subdivided loads specified in 424.22(B)?