Questions and Answers
What is the primary purpose of detecting dissolved gases in transformer oil?
What is the primary purpose of detecting dissolved gases in transformer oil?
What kind of access do the protocol interfaces have to the MSENSE® DGA 2/3?
What kind of access do the protocol interfaces have to the MSENSE® DGA 2/3?
What is the primary role of the packaging during transport?
What is the primary role of the packaging during transport?
Which component of the packaging prevents the goods from moving excessively?
Which component of the packaging prevents the goods from moving excessively?
Signup and view all the answers
Which method is used to protect access to MESSKO® MSET parameterization software?
Which method is used to protect access to MESSKO® MSET parameterization software?
Signup and view all the answers
Which of the following standards is NOT associated with the Dissolved Gas Analysis (DGA) method?
Which of the following standards is NOT associated with the Dissolved Gas Analysis (DGA) method?
Signup and view all the answers
What should be avoided during the transportation of goods to prevent damage?
What should be avoided during the transportation of goods to prevent damage?
Signup and view all the answers
What do the markings on the packaging signify?
What do the markings on the packaging signify?
Signup and view all the answers
What types of fault events can be assessed through the composition of gases in transformer oil?
What types of fault events can be assessed through the composition of gases in transformer oil?
Signup and view all the answers
What is one of the main purposes of using a sturdy cardboard box for packaging?
What is one of the main purposes of using a sturdy cardboard box for packaging?
Signup and view all the answers
What must be ensured before opening the oil extraction connection?
What must be ensured before opening the oil extraction connection?
Signup and view all the answers
Which step follows the insertion of the oil extraction adapter into the device?
Which step follows the insertion of the oil extraction adapter into the device?
Signup and view all the answers
What precaution should be taken when inserting the measuring pipe into the ball valve?
What precaution should be taken when inserting the measuring pipe into the ball valve?
Signup and view all the answers
What specific action is required if the device is an offshore version before mounting it?
What specific action is required if the device is an offshore version before mounting it?
Signup and view all the answers
What risk is associated with improperly inserting the device measuring pipe?
What risk is associated with improperly inserting the device measuring pipe?
Signup and view all the answers
What should be done to ensure safety before connecting the device to an electrical circuit?
What should be done to ensure safety before connecting the device to an electrical circuit?
Signup and view all the answers
Which type of isolating device should be used when connecting the equipment?
Which type of isolating device should be used when connecting the equipment?
Signup and view all the answers
What is a necessary feature of the circuit used for the device connection?
What is a necessary feature of the circuit used for the device connection?
Signup and view all the answers
What action is required when selecting the circuit breaker type for the device?
What action is required when selecting the circuit breaker type for the device?
Signup and view all the answers
What should be done with the warning sign before operating the valve?
What should be done with the warning sign before operating the valve?
Signup and view all the answers
What is the first step to properly mount the ball valve?
What is the first step to properly mount the ball valve?
Signup and view all the answers
What precaution should be taken to avoid possible oil leakage during mounting?
What precaution should be taken to avoid possible oil leakage during mounting?
Signup and view all the answers
Which category of fastening materials should be used for mounting the ball valve?
Which category of fastening materials should be used for mounting the ball valve?
Signup and view all the answers
What is necessary in a flange version without a groove?
What is necessary in a flange version without a groove?
Signup and view all the answers
What should be done after lubricating the rear gaskets of the ball valve?
What should be done after lubricating the rear gaskets of the ball valve?
Signup and view all the answers
An electrically skilled person does not need to identify potential dangers independently.
An electrically skilled person does not need to identify potential dangers independently.
Signup and view all the answers
Regular inspection of safety equipment is unnecessary if the product appears to be in good condition.
Regular inspection of safety equipment is unnecessary if the product appears to be in good condition.
Signup and view all the answers
An electrically trained person can independently perform work on electrical systems without supervision.
An electrically trained person can independently perform work on electrical systems without supervision.
Signup and view all the answers
The responsibilities of personnel assembling and operating equipment include ensuring their qualifications.
The responsibilities of personnel assembling and operating equipment include ensuring their qualifications.
Signup and view all the answers
Compliance with statutory regulations for accident prevention is not necessary for an electrically skilled person.
Compliance with statutory regulations for accident prevention is not necessary for an electrically skilled person.
Signup and view all the answers
The MSENSE® DGA 3 device is used solely for measuring moisture content in transformer oil.
The MSENSE® DGA 3 device is used solely for measuring moisture content in transformer oil.
Signup and view all the answers
The MSENSE® DGA instruments are available in multiple housing colors, including RAL 7033 and RAL 7038.
The MSENSE® DGA instruments are available in multiple housing colors, including RAL 7033 and RAL 7038.
Signup and view all the answers
The delivery of the MSENSE® DGA 2 or 3 includes a USB connection cable.
The delivery of the MSENSE® DGA 2 or 3 includes a USB connection cable.
Signup and view all the answers
All MSENSE® DGA models utilize the same communication protocols without any variations.
All MSENSE® DGA models utilize the same communication protocols without any variations.
Signup and view all the answers
The MSENSE® DGA 2/3 allows changing parameters through its protocol interfaces.
The MSENSE® DGA 2/3 allows changing parameters through its protocol interfaces.
Signup and view all the answers
Dissolved Gas Analysis (DGA) in transformer oil is a method that requires disconnecting the transformer.
Dissolved Gas Analysis (DGA) in transformer oil is a method that requires disconnecting the transformer.
Signup and view all the answers
The MSENSE® DGA measuring head is meant to be installed outside the transformer.
The MSENSE® DGA measuring head is meant to be installed outside the transformer.
Signup and view all the answers
Operational safety of the MSENSE® DGA 2/3 can be improved by ensuring it is operated by trained personnel familiar with IT security.
Operational safety of the MSENSE® DGA 2/3 can be improved by ensuring it is operated by trained personnel familiar with IT security.
Signup and view all the answers
The composition of gases in transformer oil provides no important information regarding fault events.
The composition of gases in transformer oil provides no important information regarding fault events.
Signup and view all the answers
Passwords for accessing the MESSKO® MSET parameterization software should be changed regularly.
Passwords for accessing the MESSKO® MSET parameterization software should be changed regularly.
Signup and view all the answers
The maximum Modbus baud rate setting is 19200 Bd.
The maximum Modbus baud rate setting is 19200 Bd.
Signup and view all the answers
Modbus addresses can be set between 1 and 247.
Modbus addresses can be set between 1 and 247.
Signup and view all the answers
A minimum pause of 200 ms between two Modbus requests is required.
A minimum pause of 200 ms between two Modbus requests is required.
Signup and view all the answers
Even parity is a fixed specification for Modbus data transmission.
Even parity is a fixed specification for Modbus data transmission.
Signup and view all the answers
Issuing the same network address for Modbus will not cause any issues.
Issuing the same network address for Modbus will not cause any issues.
Signup and view all the answers
The gaskets at the rear of the ball valve should be lubricated after the front gaskets have been lubricated.
The gaskets at the rear of the ball valve should be lubricated after the front gaskets have been lubricated.
Signup and view all the answers
A flat gasket is always included in the delivery for flange versions without a groove.
A flat gasket is always included in the delivery for flange versions without a groove.
Signup and view all the answers
Using fastening materials made of stainless steel A4 is recommended for mounting the closed ball valve.
Using fastening materials made of stainless steel A4 is recommended for mounting the closed ball valve.
Signup and view all the answers
Mounting errors can lead to tight seals and controlled oil leakage.
Mounting errors can lead to tight seals and controlled oil leakage.
Signup and view all the answers
The locking lever of the ball valve should be positioned at the bottom during installation.
The locking lever of the ball valve should be positioned at the bottom during installation.
Signup and view all the answers
Study Notes
Training and Access Control
- Device operation is restricted to trained personnel well-versed in IT security.
- Protocol interfaces (Modbus RTU, Modbus TCP, DNP3 TCP, IEC 61850-8-1 MMS) provide only read-access to MSENSE® DGA 2/3, preventing data alteration.
- Password protection is essential for accessing MESSKO® MSET parameterization software; regular password changes are recommended.
Product Overview and Importance
- DGA (Dissolved Gas Analysis) detects dissolved gases in transformer oil, signaling potential faults.
- International standards (IEEE Std C57.104™-2008, IEC 60422, IEC 60567, IEC 60599) underscore the method's significance.
- Gas composition analysis assists in identifying issues like partial discharges, overheating, and overloads, facilitating timely risk assessment.
Packaging and Transportation Guidelines
- Packaging must withstand transport stresses (vibrations, moisture) and prevent item movement.
- Sturdy cardboard boxes secure goods during transport while ensuring no contact with loading surfaces or the ground.
- Shipping markings include instructions for safe transport and handling, with mandatory adherence to symbols like "Fragile" and "Protect against moisture."
Handling and Safety Precautions
- Careful handling is necessary to avoid damage from vibrations or falls during transportation.
- Tipping or dropping the packaging can result in damage regardless of product weight.
Mounting Instructions
- Gaskets at the front and rear of the ball valve require lubrication before installation.
- Avoid mounting errors that could result in leakage; ensure proper placement of the flange gasket.
- Use stainless steel A4 fastening materials for securing the closed ball valve to the transformer.
Installation Process
- Proper oil extraction adapter for device compatibility must be verified to avoid damage.
- Open the oil extractor valve during assembly to allow for air dissipation.
- Ensure the measuring pipe is inserted straight into the ball valve with even pressure to avoid tilting.
Electrical Connection Safety
- Always de-energize the device and related systems before making electrical connections.
- Employ circuits with external overcurrent protection and an all-pole isolating device for safety.
- Circuit breakers should meet IEC 60947-1 and IEC 60947-3 standards, considering circuit voltage and maximum currents for appropriate selection.
Operational Safety and Personnel Qualifications
- Only operate equipment in sound operational condition to avoid danger to health and safety.
- Regular checks on the reliability of safety equipment are essential.
- Personnel must be sufficiently qualified for assembly, commissioning, operation, maintenance, and inspection.
Electrically Skilled Personnel
- Electrically skilled individuals possess technical qualifications, knowledge of standards, and experience in electrical work.
- They can independently identify potential dangers, perform electrical tasks, and comply with safety regulations.
Electrically Trained Persons
- Electrically trained personnel work under the guidance of electrically skilled individuals and are informed about potential risks and safeguards.
- Only trained personnel familiar with IT security should operate devices.
Communication and Security Protocols
- Protocol interfaces (Modbus RTU, Modbus TCP, DNP3 TCP, IEC 61850-8-1 MMS) have read-only access to MSENSE® DGA 2/3.
- Changing parameters via protocol interfaces is prohibited to maintain security.
- MESSKO® MSET software access can be password-protected, with regular password updates recommended.
Product Overview
- Dissolved gas analysis (DGA) in transformer oil indicates emerging faults, critical for regulatory compliance.
- Key international standards include IEEE Std C57.104™-2008, IEC 60422, IEC 60567, and IEC 60599.
- DGA method is cost-effective, fast, and does not require transformer disconnection for analysis.
Gas Detection and Measuring Capabilities
- MSENSE® DGA 3 detects dissolved fault gases (H2, CO), moisture content, and oil temperature.
- Available features include:
- 2-line display and 3 operating keys
- Various housing colors (RAL 7033, RAL 7038)
- Multiple mounting flanges (DN50, DN80)
- Communication protocols with optional MESSKO® protocol converter and offshore version available.
Delivery Components
- Upon delivery, the package includes:
- MSENSE® DGA 2 or 3 unit
- Operating instructions and certification
- Installation components (valves, connectors, extraction adapters)
- USB medium containing MESSKO® MSET software.
Functionality and Usage
- The MSENSE® DGA 2/3 measuring head is installed directly in the transformer oil.
Mounting Instructions
- Proper lubrication of gaskets at the ball valve is crucial to prevent oil leakage.
- Attention to mounting errors is necessary to ensure tight seals and functionality.
Modbus Configuration
- Modbus baud rate options range from 4800 to 115200, with a standard value of 19200 baud.
- Minimum pause of 500 milliseconds between two requests is required for successful communication.
- Modbus address settings can range from 1 to 247, and duplicate addresses may cause malfunctions.
- Parity for data transmission is fixed at even.
Device Operation
- Be aware of functional differences between MSENSE® DGA 2 and MSENSE® DGA 3 device versions; descriptions generally refer to DGA 3 unless noted otherwise.
Studying That Suits You
Use AI to generate personalized quizzes and flashcards to suit your learning preferences.
Related Documents
Description
This quiz focuses on the essential practices for operating devices securely, particularly emphasizing the importance of training personnel and ensuring correct access control. It covers protocols like Modbus RTU and IEC standards to enhance understanding of data access and security measures involved.