Electrical Relay Safety and Specifications
160 Questions
0 Views

Electrical Relay Safety and Specifications

Created by
@BestSellingBeige

Podcast

Play an AI-generated podcast conversation about this lesson

Questions and Answers

Which component of the protective relay functions as a reset mechanism?

  • Potential tie-in
  • Pressure equalization element
  • OPERATION (reset) test button (correct)
  • Cable gland
  • What purpose does the DW 2000 pressure monitoring device serve?

  • It monitors temperature levels.
  • It enhances electrical voltage stability.
  • It protects the on-load tap-changer from impermissible pressure increases. (correct)
  • It insulates the protective relay.
  • What is indicated by the safety marking that says 'Warning of dangerous electrical voltage'?

  • The device is designed to handle low voltage.
  • Users should handle the device with care to avoid shocks. (correct)
  • The voltage range is safe for general public access.
  • Normal operation does not involve electrical currents.
  • Which part of the protective relay is used for conducting electrical potential?

    <p>Connection terminal</p> Signup and view all the answers

    What type of adapter is present in the protective relays RS 2003 and RS 2004?

    <p>1/2&quot;-14 NPT adapter</p> Signup and view all the answers

    Which component provides a means to assemble and secure the protective cover?

    <p>Slotted head screw for protective cover</p> Signup and view all the answers

    Where is the nameplate located on the protective relay?

    <p>On the back of the protective relay</p> Signup and view all the answers

    What is the function of the 'OFF (test tripping)' test button?

    <p>To conduct a test that deactivates the relay temporarily</p> Signup and view all the answers

    What precaution should be taken when transporting the crate?

    <p>Transport the crate only when it is closed</p> Signup and view all the answers

    What is a potential consequence of a crate tipping over during transport?

    <p>Damage must be expected regardless of the weight</p> Signup and view all the answers

    Which individuals are allowed to select the sling gear and secure the load?

    <p>Only trained and authorized persons</p> Signup and view all the answers

    What should be checked by the recipient before accepting the shipment?

    <p>Completeness based on the delivery slip and external damage</p> Signup and view all the answers

    What is the recommended action if visible transport damage is found upon receipt?

    <p>Record the damage and have it countersigned by the carrier</p> Signup and view all the answers

    How should the recipient inspect the shipment after unloading?

    <p>When the crate can be accessed from all sides</p> Signup and view all the answers

    What risks should be anticipated during transportation aside from oscillation stress?

    <p>Jolts and sudden impacts</p> Signup and view all the answers

    What is the role of the securing material in the crate during transport?

    <p>It must not be removed during transport</p> Signup and view all the answers

    What is the primary reason for not opening the sealed packaging until just before installation?

    <p>To avoid damage from tipping</p> Signup and view all the answers

    Which safety precaution should be taken during tap-change operations of the on-load tap-changer?

    <p>Maintain a distance of at least 1 m</p> Signup and view all the answers

    What must be checked after unpacking the packaged goods?

    <p>The completeness of the accessories kit</p> Signup and view all the answers

    Which issue can arise from ineffectively sealed packaging during transport?

    <p>Damage to packaged goods</p> Signup and view all the answers

    What component is necessary for fitting the on-load tap-changer head on the transformer cover?

    <p>Mounting flange</p> Signup and view all the answers

    What hazardous condition should be avoided when working on the tap-changer?

    <p>Moving components during operation</p> Signup and view all the answers

    What is the first step in preparing for the installation of the on-load tap-changer?

    <p>Fitting the mounting flange on the transformer cover</p> Signup and view all the answers

    Which of the following actions should NOT be performed during tap-change operations?

    <p>Reach into the selector area</p> Signup and view all the answers

    What should be done to prevent damage to the on-load tap-changer during assembly?

    <p>Carefully comply with the specified tightening torque.</p> Signup and view all the answers

    What is the consequence of removing the blocking strip from the selector coupling?

    <p>The selector coupling may no longer be turned.</p> Signup and view all the answers

    What is a critical safety measure when positioning the selector?

    <p>Secure the selector against tipping on a level surface.</p> Signup and view all the answers

    What action needs to be taken regarding the support and support ring of the change-over selector?

    <p>They must be removed before finalizing the assembly.</p> Signup and view all the answers

    How much does the selector weigh at maximum?

    <p>465 kg</p> Signup and view all the answers

    What packaging material should be removed from the selector before installation?

    <p>Red-colored packaging material.</p> Signup and view all the answers

    What is the purpose of securing screw connections during assembly?

    <p>To enhance stability and prevent damage.</p> Signup and view all the answers

    Which action is NOT recommended during the assembly of the tap-selector?

    <p>Tighten screws without verifying the torque setting.</p> Signup and view all the answers

    What is the purpose of the tracing template when fitting stud bolts to the mounting flange?

    <p>To align the stud bolts correctly with markings</p> Signup and view all the answers

    What must be ensured when fitting the mounting flange on the transformer cover?

    <p>The sealing face must make complete contact and not be damaged</p> Signup and view all the answers

    Why is it important to place the oil compartment on a level surface during installation?

    <p>To prevent tipping that may lead to injuries or property damage</p> Signup and view all the answers

    What is the significance of cleaning sealing surfaces before installation?

    <p>To ensure proper adhesion and sealing of gaskets</p> Signup and view all the answers

    What should be done with the red-colored packaging material before installing the oil compartment?

    <p>It should be removed to prepare the compartment for use</p> Signup and view all the answers

    How can a tracing template be obtained for the initial installation of the on-load tap-changer?

    <p>It is available free of charge upon request</p> Signup and view all the answers

    What is one major risk of not securing the oil compartment properly during installation?

    <p>There is a risk of it tipping over causing injuries or damages</p> Signup and view all the answers

    What is the primary concern regarding the sealing face of the mounting flange?

    <p>It must make complete contact and remain undamaged</p> Signup and view all the answers

    Embedded warnings apply to individual information units rather than entire sections.

    <p>True</p> Signup and view all the answers

    The signal word 'NOTICE' indicates a hazardous situation that must be addressed immediately to prevent death.

    <p>False</p> Signup and view all the answers

    The term 'DANGER' signals a hazardous situation that can lead to minor injuries.

    <p>False</p> Signup and view all the answers

    Pictograms provide visual warnings of various dangers associated with the equipment.

    <p>True</p> Signup and view all the answers

    Caution indicates a situation that could result in damage to property.

    <p>False</p> Signup and view all the answers

    The instructional system in this technical file includes both single-step and multi-step instructions.

    <p>True</p> Signup and view all the answers

    Transporting the crate while it is open poses no risk of damage.

    <p>False</p> Signup and view all the answers

    The warning 'danger of tipping' is a correct interpretation of a pictogram used for warnings.

    <p>True</p> Signup and view all the answers

    Only trained and authorized individuals should secure the load during transportation.

    <p>True</p> Signup and view all the answers

    Warning of combustible substances is captured by the signal word 'WARNING'.

    <p>False</p> Signup and view all the answers

    Jolts and oscillation stress are not factors to consider during transportation.

    <p>False</p> Signup and view all the answers

    The recipient must check for completeness based on the delivery slip before signing for the shipment.

    <p>True</p> Signup and view all the answers

    Visible damage must be documented immediately after finding it upon receipt of the shipment.

    <p>True</p> Signup and view all the answers

    Securing materials inside the crate can be removed during transportation to save space.

    <p>False</p> Signup and view all the answers

    Damage is not expected if a crate falls from a certain height, regardless of its weight.

    <p>False</p> Signup and view all the answers

    The checks for external damage should take place after unloading the crate.

    <p>True</p> Signup and view all the answers

    Pipe connection S is used for connecting the on-load tap-changer oil conservator.

    <p>False</p> Signup and view all the answers

    The protective relay is activated when the flow speed from the on-load tap-changer head exceeds a specific limit due to a fault.

    <p>True</p> Signup and view all the answers

    Pipe connection E2 can be used to equalize pressure between the transformer tank and the oil compartment.

    <p>True</p> Signup and view all the answers

    The nameplate with the serial number is located on the body of the on-load tap-changer.

    <p>False</p> Signup and view all the answers

    Pipe connection R must be interchanged with pipe connection Q for proper functionality.

    <p>False</p> Signup and view all the answers

    The insulating fluid causes the flap valve in the protective relay to tip over into the OFF position when flow speed is exceeded.

    <p>True</p> Signup and view all the answers

    The protective relay's operation is not affected by the flow of insulating fluid.

    <p>False</p> Signup and view all the answers

    The protective relay does not have any protective devices integrated into its design.

    <p>False</p> Signup and view all the answers

    Immediately notify the manufacturer and the relevant insurance company if there is severe damage or total loss.

    <p>True</p> Signup and view all the answers

    It is acceptable to modify the condition of the shipment after identifying any damage.

    <p>False</p> Signup and view all the answers

    Photographing damaged packaging and goods is unnecessary for any claim for damages.

    <p>False</p> Signup and view all the answers

    Hidden damage can be claimed by notifying the responsible party as soon as the damage is discovered.

    <p>True</p> Signup and view all the answers

    It is sufficient to check sealed packaging immediately after delivery only if the product appears to be intact.

    <p>False</p> Signup and view all the answers

    Insurance claims for hidden damage can only succeed if relevant provisions are included in the insurance terms.

    <p>True</p> Signup and view all the answers

    Retaining packaging material is important until an inspection decision has been made by the concerned parties.

    <p>True</p> Signup and view all the answers

    The party responsible for damages should not be contacted until a damage report is prepared.

    <p>False</p> Signup and view all the answers

    A mounting flange for the on-load tap-changer is always provided by the manufacturer.

    <p>False</p> Signup and view all the answers

    It is safe to reach into the selector during a tap-change operation as long as you are careful.

    <p>False</p> Signup and view all the answers

    The packaged goods should be unpacked immediately upon arrival to check their condition.

    <p>False</p> Signup and view all the answers

    During tap-change operations, the change-over selector is completely accessible for repairs.

    <p>False</p> Signup and view all the answers

    It is necessary to perform checks on the completeness of the accessories kit using the delivery slip after unpacking.

    <p>True</p> Signup and view all the answers

    The potential connection unit poses a minimal risk during installation.

    <p>False</p> Signup and view all the answers

    Serious injuries can occur if the packaged goods are not placed upright during transport.

    <p>True</p> Signup and view all the answers

    Transport damage can occur even with effectively sealed packaging.

    <p>False</p> Signup and view all the answers

    What must be ensured about personnel responsible for assembly and maintenance?

    <p>They possess the required technical qualifications and are familiar with applicable standards.</p> Signup and view all the answers

    What type of modifications are recommended for the product according to the guidelines?

    <p>Modifications made after consultation with the manufacturer.</p> Signup and view all the answers

    What could unauthorized spare parts lead to in the context of the product?

    <p>Physical injury and product malfunctions.</p> Signup and view all the answers

    What distinguishes an electrically skilled person from an electrically trained person?

    <p>An electrically skilled person has a broader technical qualification and independent decision-making capabilities.</p> Signup and view all the answers

    What is the status of lubricants and auxiliary materials not approved by the manufacturer?

    <p>They may cause operational faults and should not be used.</p> Signup and view all the answers

    What role does an electrically trained person have in relation to the work environment?

    <p>They receive instructions and handle tasks under guidance for safety.</p> Signup and view all the answers

    What is a potential risk of modifying a product without consulting the manufacturer?

    <p>It could lead to personal injury and material damage.</p> Signup and view all the answers

    What qualifications must an electrically skilled person meet?

    <p>They must satisfy all statutory regulations for accident prevention.</p> Signup and view all the answers

    What should be done if the serial numbers of the on-load tap-changer and its accessories do not match?

    <p>Return the items and request a replacement.</p> Signup and view all the answers

    Under which electrical conditions can the on-load tap-changer operate safely?

    <p>With sinusoidal 50/60 Hz alternating current.</p> Signup and view all the answers

    What is a permissible short-term variation for the rated step voltage Uir?

    <p>Up to 10% increase.</p> Signup and view all the answers

    Who is authorized to perform necessary work on the on-load tap-changer?

    <p>Trained and qualified personnel only.</p> Signup and view all the answers

    What is critical to check regarding the coupling components during assembly?

    <p>The compatibility of the coupling components.</p> Signup and view all the answers

    What tool usage is discouraged with the tap-changer equipment?

    <p>Using equipment outside the scope of delivery.</p> Signup and view all the answers

    What must be ensured about the technical specifications during operation?

    <p>They should be strictly followed.</p> Signup and view all the answers

    What should be done if an unapproved electrical component is discovered in the on-load tap-changer setup?

    <p>Remove it immediately and follow correct procedures.</p> Signup and view all the answers

    What mechanism allows on-load tap-changers to adjust the transmission ratio without interrupting load flow?

    <p>Motor-drive unit</p> Signup and view all the answers

    Which personal protective equipment is specifically designed to protect the eyes from flying parts and splashing liquids?

    <p>Safety glasses</p> Signup and view all the answers

    What is the primary purpose of a hard hat in personal protective equipment?

    <p>To protect against falling and flying objects</p> Signup and view all the answers

    What aspect of on-load tap-changers allows them to compensate for fluctuations in the power transmission grid?

    <p>Continuous adjustment capability</p> Signup and view all the answers

    Which type of safety equipment is essential for protecting against thermal hazards?

    <p>Protective gloves</p> Signup and view all the answers

    What control element changes the on-load tap-changer’s operating position in response to the voltage regulator?

    <p>Motor-drive unit</p> Signup and view all the answers

    Which protective equipment is necessary to prevent hearing damage?

    <p>Hearing protection</p> Signup and view all the answers

    What must be done to ensure the oil compartment is securely fitted during installation of the on-load tap-changer?

    <p>Ensure it is on a level surface</p> Signup and view all the answers

    What is the primary function of the on-load tap-changer in a transformer system?

    <p>To adjust the voltage levels without interrupting the power supply</p> Signup and view all the answers

    Which component is responsible for selecting specific taps of the transformer?

    <p>Tap selector</p> Signup and view all the answers

    Which of the following is NOT a part of the on-load tap-changer head assembly?

    <p>Thermal expansion valve</p> Signup and view all the answers

    What is the purpose of the oil compartment in the on-load tap-changer assembly?

    <p>To act as a cooling medium and insulator</p> Signup and view all the answers

    Which function does the change-over selector perform in the on-load tap-changer system?

    <p>It selects between different transformer taps</p> Signup and view all the answers

    During the assembly of the tap-selector, which action is most critical for ensuring its functionality?

    <p>Securing the screw connections properly</p> Signup and view all the answers

    What is indicated by the presence of four pipe connections on the on-load tap-changer head?

    <p>Multiple functionality for cooling and oil circulation</p> Signup and view all the answers

    Which component is primarily responsible for converting mechanical movements to electrical signaling in the on-load tap-changer?

    <p>Motor-drive unit</p> Signup and view all the answers

    What is the consequence of operating the motor-drive unit electrically before disconnecting the transformer?

    <p>Danger of explosion</p> Signup and view all the answers

    What action should be taken if the hand crank becomes difficult to move during operation?

    <p>Stop using the hand crank immediately</p> Signup and view all the answers

    What must be ensured regarding the oil compartment during commissioning of the transformer?

    <p>It should be completely filled with insulation fluid</p> Signup and view all the answers

    What is a safe practice regarding tap-change operations after inrush current impulses?

    <p>Wait until inrush current impulses have subsided</p> Signup and view all the answers

    During commissioning, how should the signaling contact for the oil conservator be configured?

    <p>Looped into the tripping circuit of the transformer</p> Signup and view all the answers

    What precaution should be followed when performing a tap-change operation under load conditions?

    <p>Make sure inrush current is adequately managed</p> Signup and view all the answers

    What risk is associated with leaving the stop-cocks between the on-load tap-changer and oil conservator closed?

    <p>Insufficient oil supply during operation</p> Signup and view all the answers

    Why should tap-change operations not be interrupted after initiating electrically?

    <p>To prevent failure of the tap-changer mechanism</p> Signup and view all the answers

    The technical file is intended for general use by anyone.

    <p>False</p> Signup and view all the answers

    Warning relating to sections applies only to specific paragraphs within the technical file.

    <p>False</p> Signup and view all the answers

    The supporting documents include connection diagrams and routine test reports.

    <p>True</p> Signup and view all the answers

    The notation conventions indicate that embedded warnings are applicable to an entire section.

    <p>False</p> Signup and view all the answers

    One of the supporting documents required for completeness is the order confirmation.

    <p>True</p> Signup and view all the answers

    Warnings are displayed in a specific format that includes a type of danger, source of danger, and action steps.

    <p>True</p> Signup and view all the answers

    It is recommended to keep the technical file and supporting documents easily accessible at all times.

    <p>True</p> Signup and view all the answers

    Maschinenfabrik Reinhausen GmbH is the manufacturer identified in the technical file.

    <p>True</p> Signup and view all the answers

    The flap valve must be in the STANDBY position for the protective relay to function correctly.

    <p>False</p> Signup and view all the answers

    The transformer's circuit breaker can remain closed during testing of the pressure monitoring device.

    <p>False</p> Signup and view all the answers

    The sensor on the snap-action switch is activated only when the transformer is in operation.

    <p>False</p> Signup and view all the answers

    Grounding the transformer must be performed on the high-voltage side only during the pressure monitoring device check.

    <p>False</p> Signup and view all the answers

    The protective tests require leaving the transformer's danger zone during each step.

    <p>True</p> Signup and view all the answers

    Resetting the pressure monitoring device involves activating the snap-action switch to its OFF position.

    <p>False</p> Signup and view all the answers

    The circuit breaker will not close if the sensor is activated for a passive protection test.

    <p>True</p> Signup and view all the answers

    Once the cover cap is secured, the transformer can immediately be powered on.

    <p>False</p> Signup and view all the answers

    The pipe connection Q can only be interchanged with pipe connection R.

    <p>False</p> Signup and view all the answers

    Pipe connection S is solely used for venting purposes and cannot be connected to a drain valve.

    <p>False</p> Signup and view all the answers

    The pipe connection E2 is intended for direct attachment to the oil conservator of the tap-changer.

    <p>False</p> Signup and view all the answers

    Each pipe connection is permanently fixed and cannot be swiveled after installation.

    <p>False</p> Signup and view all the answers

    Pipe connection R includes installation for both the protective relay and the oil conservator.

    <p>True</p> Signup and view all the answers

    The connection cables for the tap-change supervisory device are routed through pipe connection S.

    <p>False</p> Signup and view all the answers

    Pipe connection Q is covered with a blank cover to prevent any connections.

    <p>True</p> Signup and view all the answers

    If the on-load tap-changer is fitted with an oil suction pipe, it cannot be emptied via pipe connection S.

    <p>False</p> Signup and view all the answers

    The pressure monitoring device activates a sensor on the snap-action switch to trigger the circuit breaker when static and dynamic pressures exceed a certain threshold.

    <p>True</p> Signup and view all the answers

    Low-energy interference will cause the pressure monitoring device to trip because it is sensitive to all changes in pressure.

    <p>False</p> Signup and view all the answers

    The tripping pressure set in the pressure monitoring device can be adjusted by the user to customize its sensitivity.

    <p>False</p> Signup and view all the answers

    The pressure monitoring device uses a spring and a corrugated tube mechanism to measure both static and dynamic pressures in the oil compartment.

    <p>True</p> Signup and view all the answers

    After the pressure monitoring device is tripped, resetting the sensor on the snap-action switch must be done automatically.

    <p>False</p> Signup and view all the answers

    The protective relay is designed to respond to large pressure increases more swiftly than the pressure monitoring device.

    <p>False</p> Signup and view all the answers

    The markings on the product include instructions to read the documentation for safety compliance.

    <p>True</p> Signup and view all the answers

    The warning of dangerous electrical voltage is one of the safety markings associated with the product.

    <p>True</p> Signup and view all the answers

    The motor-drive unit can still be electrically actuated after the tap-change supervisory device is activated.

    <p>False</p> Signup and view all the answers

    Tripping of the pressure relief device does not require checking the on-load tap-changer.

    <p>False</p> Signup and view all the answers

    One must take measurements on the transformer after tripping of the pressure monitoring device.

    <p>True</p> Signup and view all the answers

    It is permissible to manually operate the motor-drive unit via the hand crank when the transformer is switched on.

    <p>False</p> Signup and view all the answers

    The activation of tap-change supervisory device indicates that the transformer must be taken out of service.

    <p>True</p> Signup and view all the answers

    Contacting MR is necessary only when checking the pressure monitoring device, not for the tap-changer.

    <p>False</p> Signup and view all the answers

    Tripping the protective relay requires the transformer to be re-commissioned after diagnosis.

    <p>True</p> Signup and view all the answers

    The pressure relief device does not have any connection to the transformer checks.

    <p>False</p> Signup and view all the answers

    Study Notes

    Product Overview

    • VACUTAP® VR I HD is a type of on-load tap-changer designed for transformer applications.
    • The protective relay RS 2001 features multiple components including a gasket, terminal box cover, operation/reset test buttons, and a pressure equalization element.
    • Variants RS 2003 and RS 2004 come equipped with a 1/2"-14NPT adapter instead of a cable gland.

    Nameplate and Safety Markings

    • The nameplate is located on the back of the protective relay, providing essential information about the device.
    • Safety markings include:
      • Protective conductor connection
      • Warning of dangerous electrical voltage
      • Instruction to read provided documentation.

    Pressure Monitoring Device

    • The DW 2000 pressure monitoring device ensures safety by protecting the on-load tap-changer from excessive pressure.

    Handling and Transportation

    • Strict precautions are necessary during transportation to prevent tipping and falling loads:
      • Keep crates closed during transport.
      • Ensure loads are secured and handled by qualified personnel.
    • Recipients must check shipments for completeness and external damage upon delivery.
    • Any visible transport damage must be documented immediately and countersigned by the carrier.

    Unpacking Procedures

    • Packages should be transported to the installation site without opening them until needed, avoiding risk to the contents.
    • Unpack goods carefully while ensuring they remain stable to prevent accidents.

    Mounting and Installation

    • Safety measures are critical during installation to avoid injuries from moving components during tap-change operations.
    • A mounting flange must be fitted on the transformer cover to secure the on-load tap-changer.
    • Customer-produced mounting flanges must comply with specific installation drawings for proper fit.
    • Proper sealing and alignment of components is necessary to ensure a secure installation.

    Connection and Fastening

    • The oil compartment must be placed securely to prevent tipping during installation.
    • It is crucial to follow specified tightening torque and secure screw connections to avoid damage to the on-load tap-changer.
    • Removal of packaging materials and ensuring proper positioning of components is essential before installation.

    Selector and Fastening Procedures

    • The selector, which weighs up to 465 kg, needs to be positioned on a level surface and secured against tipping.
    • The blocking strip should be removed cautiously from the selector coupling as it prevents accidental movement of the selector.

    Embedded Warnings and Signal Words

    • Embedded warnings provide specific alerts within sections, focusing on smaller information units.
    • Warning format includes "DANGER!", giving instructions to avoid potentially life-threatening situations.
    • Signal words with definitions:
      • DANGER: Imminent risk of death or serious injury.
      • WARNING: Significant risk of death or serious injury.
      • CAUTION: Risk of minor or moderate injury.
      • NOTICE: Preventative measures to protect property.

    Pictograms and Their Meanings

    • Pictograms are visual symbols warning of hazards:
      • Indicates danger points.
      • Warns about dangerous electrical voltages.
      • Alerts to combustible substances.
      • Signifies risk of tipping.
      • Represents danger of crushing.

    Information and Instruction Systems

    • Information systems are designed to enhance understanding of procedures, detail important points.
    • Instruction systems provide single-step and multi-step processes for equipment usage.
    • Pipe connections (S, R, E2) facilitate functions such as oil suction, protective relay attachment, and pressure equalization in transformers.

    Protective Devices and Functions

    • The on-load tap-changer includes protective relays integrated into the circuit breaker tripping circuit.
    • Relays activate if flow speed exceeds limits, triggering circuit breaker trips to de-energize the transformer.

    Transportation and Handling Precautions

    • Strict instructions to prevent hazards during transport:
      • Secure crate before transport; do not open or modify packaging.
      • Only authorized personnel should handle and secure loads.
      • Inspect shipments for completeness and damage upon receipt.
      • Report visible transport damage immediately with proper documentation.
      • Address hidden damage proactively with responsible parties to ensure claims.

    Unpacking and Installation Guidelines

    • Maintain packaging until immediate installation; do not open prematurely.
    • Ensure safety during unpacking to prevent tipping and injury.
    • Check all components against the delivery slip for completeness.
    • Clear warning against reaching into machinery during operation to avoid crushing injuries.

    Product Lifecycle and Usage Guidelines

    • Applies from delivery to disposal of the product.
    • Must use specified transformer/motor-drive unit as ordered.
    • Serial numbers of on-load tap-changer and accessories must match if supplied together.
    • Check nameplate for applicable standards and year of issue.
    • Operate per technical file, delivery conditions, and technical data.
    • Only qualified personnel should perform necessary work.
    • Use only specified equipment and tools for intended purposes.
    • Not compatible with an oil filter unit.

    Operating Conditions and Safety

    • Designed for sinusoidal 50/60 Hz AC; can switch 2 times rated through-current at rated step voltage.
    • Temporary 10% overstep of rated voltage Uir is acceptable without exceeding rated step capacity PStN.
    • Use only manufacturer-approved lubricants and materials; consult manufacturer for modifications.
    • Unauthorized changes may lead to personal injury and operational issues.

    Personnel Qualifications

    • Assembly and maintenance must be conducted by qualified personnel.
    • An electrically skilled person has the requisite technical knowledge and experience.
    • Recognizes potential dangers and avoids them, able to work with electrical systems, familiar with safety regulations.
    • An electrically trained person receives guidance from a skilled person, focusing on safety and task understanding.

    Personal Protective Equipment (PPE)

    • Safety shoes prevent slipping and injuries from falling objects.
    • Safety glasses protect against flying parts and splashes.
    • Visors guard the face from hazardous substances.
    • Hard hats shield against falling materials.
    • Hearing protection avoids noise-induced damage.
    • Protective gloves defend against mechanical, thermal, and electrical hazards.

    On-load Tap-changer Function and Components

    • Used to adjust transformer transmission ratios without disrupting load flow; compensates for voltage fluctuations.
    • Connected to transformer’s active part; motor-drive unit receives control signals for operation adjustment.
    • Key components include transformer tank, motor-drive unit, drive shafts, protective relays, and oil conservators.

    On-load Tap-changer Setup

    • Features pipe connections for various functions.
    • Commissioning requires monitoring oil fill levels and ensuring protective devices are operational.
    • Ensure stop-cocks are open between on-load tap-changer and oil conservator before powering on.

    Operational Warnings

    • Inrush currents can exceed rated transformer currents; wait for currents to stabilize before making tap changes.
    • Never use the hand crank on the motor-drive unit if transformer may contain faults; de-energize first.
    • Do not complete electric tap-change operations with a hand crank if not properly concluded.

    Additional Considerations

    • Maintenance and inspection must follow all manufacturer recommendations to ensure safety and functionality.
    • Spare parts must be approved by Maschinenfabrik Reinhausen GmbH to prevent malfunctions or injuries.

    Manufacturer Information

    • Maschinenfabrik Reinhausen GmbH located at Falkensteinstraße 8, Regensburg, Germany.
    • Contact through phone: (+49) 9 41/40 90-0 or email: [email protected].
    • Availability of additional product information and technical files upon request.

    Technical File Overview

    • Designed for specially trained and authorized personnel.
    • Contains safety instructions, general product information, and installation guidance.
    • Incomplete without accompanying supporting documents such as unpacking instructions, routine test reports, and order confirmations.

    Safekeeping Instructions

    • Technical files and supporting documents must be readily accessible for future reference.

    Safety Notation Conventions

    • Warnings indicate dangers and necessary actions, organized by section.
    • Embedded warnings address specific parts within sections.

    Product Description

    • Features pipe connections (R, Q, S, E2) with specific functions such as venting and drainage.
    • Connection Q: Blank cover; can be swapped with connection R for supervisory device cables.
    • Connection S: Includes a vent screw, allows for complete draining when connected to a drain valve.
    • Connection R: Links to the protective relay and on-load tap-changer oil conservator.
    • Connection E2: Sealed with a blank cover; can connect to Buchholz relay if needed.

    Safety Markings

    • Product includes markings indicating:
      • Protective conductor connection.
      • Warning of dangerous electrical voltage.
      • Instruction to read relevant documentation.

    Pressure Monitoring Device (DW)

    • Protects the on-load tap-changer from unauthorized pressure increases.
    • Comprised of a corrugated tube and spring mechanism linked to a sensor for tripping.
    • The sensor activates, de-energizing the transformer if high pressure is detected.
    • Resetting the sensor requires manual intervention after tripping.
    • The device remains impervious to low-energy interference.

    Checking Procedures

    • Before commissioning, ensure protective relay and pressure monitoring device functions.
    • Includes grounding the transformer, ensuring de-energized status, and valve positioning.
    • Tests confirm that circuit breakers remain open, ensuring active and passive protection.

    Fault Elimination

    • Procedures established for tripping of protective and pressure relief devices.
    • Recommendations to check on-load tap-changer and transformer for faults as needed.
    • Manual operation of the motor-drive unit is prohibited during supervisory device activation.

    Studying That Suits You

    Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

    Quiz Team

    Description

    Test your knowledge on the VACUTAP® VR I HD and its associated protective relay RS 2001. This quiz covers essential safety markings, handling precautions, and specifications related to transformer applications. Ideal for electrical engineers and technicians.

    More Like This

    Use Quizgecko on...
    Browser
    Browser