Where electricity at voltage exceeding 650 V is supplied, converted, transformed or used, the owner shall maintain safety clearances for electrical apparatus as per relevant ______ specification
Where electricity at voltage exceeding 650 V is supplied, converted, transformed or used, the owner shall maintain safety clearances for electrical apparatus as per relevant ______ specification
standards
In case of ______, the safety clearances for electrical apparatus to be as per relevant mining regulations
In case of ______, the safety clearances for electrical apparatus to be as per relevant mining regulations
mines
The live parts of all apparatus within the reach from any position in which a person may require to be, are suitably protected to prevent ______
The live parts of all apparatus within the reach from any position in which a person may require to be, are suitably protected to prevent ______
danger
Where the transformer is used, suitable provision shall be made, either by connecting with ______, a point of the circuit at the lower voltage or otherwise, to guard against danger
Where the transformer is used, suitable provision shall be made, either by connecting with ______, a point of the circuit at the lower voltage or otherwise, to guard against danger
Signup and view all the answers
A substation or a switching station with apparatus having more than 2000 litre of ______ in the basement where proper oil draining arrangement cannot be provided shall not be installed
A substation or a switching station with apparatus having more than 2000 litre of ______ in the basement where proper oil draining arrangement cannot be provided shall not be installed
Signup and view all the answers
In a substation or a switching station with oil-filled apparatus, a separation ______ or fire barrier walls of thickness and dimensions as specified in the relevant standards shall be provided
In a substation or a switching station with oil-filled apparatus, a separation ______ or fire barrier walls of thickness and dimensions as specified in the relevant standards shall be provided
Signup and view all the answers
Spare ______ shall not be stored in the vicinity of any oil filled equipment in any such substation or switching station
Spare ______ shall not be stored in the vicinity of any oil filled equipment in any such substation or switching station
Signup and view all the answers
Every transformer of 10 MVA or reactor of 10 MVAR and above rating shall be provided with automatic ______ fighting system as per relevant standards
Every transformer of 10 MVA or reactor of 10 MVAR and above rating shall be provided with automatic ______ fighting system as per relevant standards
Signup and view all the answers
Cable trenches inside the substations and switching stations containing cables are filled with sand, pebbles or similar non-______ materials or completely covered with non-inflammable slabs
Cable trenches inside the substations and switching stations containing cables are filled with sand, pebbles or similar non-______ materials or completely covered with non-inflammable slabs
Signup and view all the answers
Unless the conditions are such that all the conductors and apparatus may be made ______ at the same time for the purpose of cleaning or for other work
Unless the conditions are such that all the conductors and apparatus may be made ______ at the same time for the purpose of cleaning or for other work
Signup and view all the answers
Study Notes
Owner's Responsibilities
- Before applying for approval, the owner must test every circuit, except overhead lines, to ensure they can withstand the testing voltage set out in regulation 48 and record the results.
- The owner must not connect new apparatus or electric supply lines to the supply without approval from the Electrical Inspector.
Electrical Safety Officer
- The owner of an electrical installation with a connected load above 250 kW (or 2000 kW in mines and oil-fields) must designate an Electrical Safety Officer.
- The Electrical Safety Officer must:
- Have the required qualification and experience
- Carry out recommended periodic tests as per relevant standards
- Inspect installations at intervals not exceeding one year
- Keep records of tests, recommendations, and compliances made
Chartered Electrical Safety Engineer
- The Appropriate Government may authorise Chartered Electrical Safety Engineers to assist with self-certification under regulations 32 and 45.
- Chartered Electrical Safety Engineers must have the required qualification and experience.
Safety Measures for Installations above 650 V
- The owner must:
- Maintain safety clearances for electrical apparatus as per relevant standards
- Not allow encroachment below the installation
- Ensure minimum safety working clearances for outdoor substations
- Protect live parts of apparatus from danger
- Ensure suitable provision to prevent danger from leakage or contact with higher voltage circuits
- Take measures for substations or switching stations with oil-filled apparatus, including:
- Providing separation walls or fire barriers
- Making provisions for oil soakpits and fire protection
- Storing spare oil away from the vicinity
- Maintaining equipment as per relevant standards
- Implement fire detection and protection arrangements
- Ensure automatic fire fighting systems for transformers of 10 MVA or reactors of 10 MVAR and above rating