Electrical Installation Testing Regulations
10 Questions
0 Views

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to lesson

Podcast

Play an AI-generated podcast conversation about this lesson

Questions and Answers

Where electricity at voltage exceeding 650 V is supplied, converted, transformed or used, the owner shall maintain safety clearances for electrical apparatus as per relevant ______ specification

standards

In case of ______, the safety clearances for electrical apparatus to be as per relevant mining regulations

mines

The live parts of all apparatus within the reach from any position in which a person may require to be, are suitably protected to prevent ______

danger

Where the transformer is used, suitable provision shall be made, either by connecting with ______, a point of the circuit at the lower voltage or otherwise, to guard against danger

<p>earth</p> Signup and view all the answers

A substation or a switching station with apparatus having more than 2000 litre of ______ in the basement where proper oil draining arrangement cannot be provided shall not be installed

<p>oil</p> Signup and view all the answers

In a substation or a switching station with oil-filled apparatus, a separation ______ or fire barrier walls of thickness and dimensions as specified in the relevant standards shall be provided

<p>wall</p> Signup and view all the answers

Spare ______ shall not be stored in the vicinity of any oil filled equipment in any such substation or switching station

<p>oil</p> Signup and view all the answers

Every transformer of 10 MVA or reactor of 10 MVAR and above rating shall be provided with automatic ______ fighting system as per relevant standards

<p>fire</p> Signup and view all the answers

Cable trenches inside the substations and switching stations containing cables are filled with sand, pebbles or similar non-______ materials or completely covered with non-inflammable slabs

<p>inflammable</p> Signup and view all the answers

Unless the conditions are such that all the conductors and apparatus may be made ______ at the same time for the purpose of cleaning or for other work

<p>dead</p> Signup and view all the answers

Study Notes

Owner's Responsibilities

  • Before applying for approval, the owner must test every circuit, except overhead lines, to ensure they can withstand the testing voltage set out in regulation 48 and record the results.
  • The owner must not connect new apparatus or electric supply lines to the supply without approval from the Electrical Inspector.

Electrical Safety Officer

  • The owner of an electrical installation with a connected load above 250 kW (or 2000 kW in mines and oil-fields) must designate an Electrical Safety Officer.
  • The Electrical Safety Officer must:
    • Have the required qualification and experience
    • Carry out recommended periodic tests as per relevant standards
    • Inspect installations at intervals not exceeding one year
    • Keep records of tests, recommendations, and compliances made

Chartered Electrical Safety Engineer

  • The Appropriate Government may authorise Chartered Electrical Safety Engineers to assist with self-certification under regulations 32 and 45.
  • Chartered Electrical Safety Engineers must have the required qualification and experience.

Safety Measures for Installations above 650 V

  • The owner must:
    • Maintain safety clearances for electrical apparatus as per relevant standards
    • Not allow encroachment below the installation
    • Ensure minimum safety working clearances for outdoor substations
    • Protect live parts of apparatus from danger
    • Ensure suitable provision to prevent danger from leakage or contact with higher voltage circuits
    • Take measures for substations or switching stations with oil-filled apparatus, including:
      • Providing separation walls or fire barriers
      • Making provisions for oil soakpits and fire protection
      • Storing spare oil away from the vicinity
      • Maintaining equipment as per relevant standards
    • Implement fire detection and protection arrangements
    • Ensure automatic fire fighting systems for transformers of 10 MVA or reactors of 10 MVAR and above rating

Studying That Suits You

Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

Quiz Team

Related Documents

Description

Quiz on regulations for testing electrical installations, including voltage testing and reporting requirements.

More Like This

Electrical Installation Quiz
5 questions

Electrical Installation Quiz

UnequivocalLapisLazuli avatar
UnequivocalLapisLazuli
Pemasangan dan Penyeliaan Elektrik
24 questions
Electrical Installation Standards
21 questions
Use Quizgecko on...
Browser
Browser