What is the first step in the typical sequence of operation for most programming controllers mentioned in the text?

  • Pre-ignition Interlocks (correct)
  • Start draft fan
  • Start purge
  • High airflow
  • When does the BMS start the draft fan according to the sequence of operation outlined in the text?

  • After Ignite pilot
  • Before Pre-ignition Interlocks
  • After Pre-ignition Interlocks and High airflow (correct)
  • After Start purge
  • What initiates the increase in fan speed or combustion air damper position to high-fire position as per the text?

  • Low airflow
  • Start purge
  • High airflow (correct)
  • Ignite pilot
  • What marks the completion of the purge process as per the typical sequence of operation discussed in the text?

    <p>Low airflow</p> Signup and view all the answers

    When does the BMS ignite the pilot flame based on the sequence of operation detailed in the text?

    <p>After Low airflow</p> Signup and view all the answers

    What is the purpose of waiting up to 10 seconds after starting the igniter according to the text?

    <p>To stabilize the pilot flame</p> Signup and view all the answers

    What happens when the steam pressure or hot water temperature rises above the set point of the operating control?

    <p>The programming controller de-energizes the SSOVs</p> Signup and view all the answers

    What occurs during the programming controller's post-purge phase?

    <p>The flame is extinguished</p> Signup and view all the answers

    What does the programming controller do during standby mode?

    <p>Allows time for SSOV proof-of-closure switches to close</p> Signup and view all the answers

    If the SSOV proof-of-closure switches do not close during standby, what does the programming controller do?

    <p>Remains in standby mode until corrected</p> Signup and view all the answers

    When a call for heat is received and all permissives are satisfied, what does the programming controller do?

    <p>Repeats the startup sequence</p> Signup and view all the answers

    What will the BMS do if the pilot is too small to reliably light off the main burner?

    <p>Shut the pilot SSOV and lockout the burner system</p> Signup and view all the answers

    During the main flame trial for ignition period, what happens if the main flame is not established within 10 seconds?

    <p>A safety shutdown and lockout occurs</p> Signup and view all the answers

    What initiates the Safe Start stage in the operating sequence chart?

    <p>Power quality evaluation</p> Signup and view all the answers

    What happens if a flame is detected during the safe start check according to the text?

    <p>Controller returns to standby mode</p> Signup and view all the answers

    During the Pilot Trial for Ignition period, what is expected if the pilot flame is not proven within 10 seconds?

    <p>Safety shutdown will occur</p> Signup and view all the answers

    What does the BMS do if a permissive switch opens during the run period?

    <p>Shuts off SSOVs and conducts a post-purge of the furnace</p> Signup and view all the answers

    What happens if a flame is not detected during safe start check?

    <p>The controller begins the purge.</p> Signup and view all the answers

    Which component must be at the proper pressure to satisfy the low atomizing medium cut-off switch for an oil-fired boiler?

    <p>Atomizing medium</p> Signup and view all the answers

    What must be running to satisfy the low fuel pressure cut-off switch for an oil-fired boiler?

    <p>Oil pumps</p> Signup and view all the answers

    In a dual fuel boiler, what must be placed on either oil or gas depending on the fuel used?

    <p>Fuel selector switch</p> Signup and view all the answers

    What is required to initiate the boiler ignition sequence according to the text?

    <p>Closing the main electrical disconnect switch</p> Signup and view all the answers

    What does closing the on-off switch during initial startup lead to?

    <p>Initiating the firing sequence</p> Signup and view all the answers

    What is needed for the programming controller to move from standby mode to safe start check mode?

    <p>'On-off' and 'operating control' switches closed</p> Signup and view all the answers

    What happens if the pilot fails to light within 15 to 90 seconds?

    <p>The primary controller will go into safety shutdown and lockout.</p> Signup and view all the answers

    If the main flame goes out during the run period, what action does the burner take?

    <p>Goes into safety shutdown and lockout.</p> Signup and view all the answers

    What does the primary controller do in case of a second failed attempt to establish a pilot?

    <p>Goes into safety shutdown and lockout.</p> Signup and view all the answers

    What action is taken if the number of main flame failures in a call for heat cycle reaches 5?

    <p>A 5-minute natural draft purge is performed before attempting to establish a pilot.</p> Signup and view all the answers

    What must the operator do if there is an ignition failure during boiler startup?

    <p>Correct the problem and reset the control.</p> Signup and view all the answers

    What are the conditions that must be satisfied before a boiler can be started by its programming controller?

    <p>The pressure should be above the cut-in setting.</p> Signup and view all the answers

    What does the programming controller do if permissives and pre-ignition interlocks are not satisfied?

    <p>Purges the furnace first.</p> Signup and view all the answers

    What happens if there is a main burner failure during operation?

    <p>The programming control will lock out.</p> Signup and view all the answers

    What happens if there is an ignition failure during boiler startup?

    <p>The operator must manually ignite the burner.</p> Signup and view all the answers

    What happens in case of a main flame failure during operation?

    <p>The operator must correct the issue and reset the control.</p> Signup and view all the answers

    What happens when a safety shutdown and lockout occurs during the PILOT TRIAL-FOR-IGNITION PERIOD (PTFI)?

    <p>There is no pilot flame present at the end of the PTFI period</p> Signup and view all the answers

    When does the burner restart automatically in an automatically fired boiler?

    <p>When the operating control closes</p> Signup and view all the answers

    Which component of a natural draft gas-fired boiler is energized to light the pilot flame?

    <p>Ignition transformer and pilot SSOV</p> Signup and view all the answers

    What is a requirement for all fuel-fired boilers?

    <p>Built-in self-diagnostics</p> Signup and view all the answers

    What is indicated directly on the controller during a safety shutdown and lockout?

    <p>An ALARM light</p> Signup and view all the answers

    What happens during a safety shutdown if an SSOV proof-of-closure switch opens during the RUN period?

    <p>There is no flame present</p> Signup and view all the answers

    Which condition is likely to trigger a safety shutdown and lockout during the INITIATE period?

    <p>AC line power error occurred</p> Signup and view all the answers

    What occurs when an operating control opens in an automatically fired boiler?

    <p>'Call for heat' condition initiates</p> Signup and view all the answers

    'Shutdown without Lockout' occurs in an automatically fired boiler when:

    <p>'Call for heat' condition is initiated by pressuretrol</p> Signup and view all the answers

    'Safety Shutdown and Lockout' closes all SSOVs and locks itself out when:

    <p>'Pilot is intermittent, pilot SSOV is NOT energized'</p> Signup and view all the answers

    More Like This

    Boiler Inspection and Compliance Quiz
    30 questions
    Ohio Boiler Test Flashcards
    100 questions

    Ohio Boiler Test Flashcards

    WellRegardedObsidian1129 avatar
    WellRegardedObsidian1129
    Use Quizgecko on...
    Browser
    Browser