All facilities greater than ____ or more than two stories in height must have at least one means of all-weather ground access to allow emergency vehicles unimpeded access to the Facility.
All facilities greater than ____ or more than two stories in height must have at least one means of all-weather ground access to allow emergency vehicles unimpeded access to the Facility.
5,000 ft2
All facilities more than ____ stories in height must have a means of all-weather ground access to allow emergency vehicles unimpeded access to the Facility.
All facilities more than ____ stories in height must have a means of all-weather ground access to allow emergency vehicles unimpeded access to the Facility.
2
All facilities greater than two stories in height must have at least ____ means of all-weather ground access to allow emergency vehicles unimpeded access to the Facility.
All facilities greater than two stories in height must have at least ____ means of all-weather ground access to allow emergency vehicles unimpeded access to the Facility.
1
All-weather ground access must be paved, start from the road, and terminate no farther than ____ feet from an exterior door accessible for fire department ingress.
All-weather ground access must be paved, start from the road, and terminate no farther than ____ feet from an exterior door accessible for fire department ingress.
Signup and view all the answers
New facilities _____ stories or more in height and all new warehouses must be provided with suitable all-weather ground access for aerial apparatus.
New facilities _____ stories or more in height and all new warehouses must be provided with suitable all-weather ground access for aerial apparatus.
Signup and view all the answers
New facilities and all new warehouses must be provided with suitable all-weather ground access for aerial apparatus on a minimum of _____ sides of the perimeter of the structure.
New facilities and all new warehouses must be provided with suitable all-weather ground access for aerial apparatus on a minimum of _____ sides of the perimeter of the structure.
Signup and view all the answers
Facilities with fire department connections for fire suppression systems must be provided with suitable all-weather ground access surface for any apparatus within ____ feet.
Facilities with fire department connections for fire suppression systems must be provided with suitable all-weather ground access surface for any apparatus within ____ feet.
Signup and view all the answers
Fire flow for sprinklered facilities must be a minimum of ____ gpm at 20 psi.
Fire flow for sprinklered facilities must be a minimum of ____ gpm at 20 psi.
Signup and view all the answers
Fire flow for sprinklered facilities must be a minimum of ____ psi.
Fire flow for sprinklered facilities must be a minimum of ____ psi.
Signup and view all the answers
The fire flow for non-sprinklered, one story family housing must be ____ GPM.
The fire flow for non-sprinklered, one story family housing must be ____ GPM.
Signup and view all the answers
The fire flow for non-sprinklered, two story family housing must be ____ GPM.
The fire flow for non-sprinklered, two story family housing must be ____ GPM.
Signup and view all the answers
The fire flow for non-sprinklered, three story and above family housing must be ____ GPM.
The fire flow for non-sprinklered, three story and above family housing must be ____ GPM.
Signup and view all the answers
The fire flow for non-sprinklered, one story family housing must be capable of operating for a minimum of ____ minutes.
The fire flow for non-sprinklered, one story family housing must be capable of operating for a minimum of ____ minutes.
Signup and view all the answers
A minimum fire flow of ____ gpm is to be provided for aircraft parking and refueling facilities.
A minimum fire flow of ____ gpm is to be provided for aircraft parking and refueling facilities.
Signup and view all the answers
A minimum fire flow for aircraft parking and refueling facilities is to be provided for at least a ____ duration.
A minimum fire flow for aircraft parking and refueling facilities is to be provided for at least a ____ duration.
Signup and view all the answers
A minimum fire flow of ____ gpm must be provided for vehicle parking areas.
A minimum fire flow of ____ gpm must be provided for vehicle parking areas.
Signup and view all the answers
A minimum fire flow must be provided for vehicle parking areas for a ____ duration.
A minimum fire flow must be provided for vehicle parking areas for a ____ duration.
Signup and view all the answers
Service mains must be looped to provide at least ___ percent of the required fire flow in case of a single break.
Service mains must be looped to provide at least ___ percent of the required fire flow in case of a single break.
Signup and view all the answers
Service mains must be sized so that the minimum residual pressure is not less than ____ psi.
Service mains must be sized so that the minimum residual pressure is not less than ____ psi.
Signup and view all the answers
Not more than ____ fire hydrants can be located on a service lateral.
Not more than ____ fire hydrants can be located on a service lateral.
Signup and view all the answers
Minimum size service lateral for fire sprinkler systems must be not less than ____ in diameter.
Minimum size service lateral for fire sprinkler systems must be not less than ____ in diameter.
Signup and view all the answers
Minimum size service lateral for NFPA 13R fire sprinkler systems must be not less than ____ in diameter.
Minimum size service lateral for NFPA 13R fire sprinkler systems must be not less than ____ in diameter.
Signup and view all the answers
The minimum _____ pressure in a service lateral must not be less than 20 psi.
The minimum _____ pressure in a service lateral must not be less than 20 psi.
Signup and view all the answers
A sufficient number of sectional valves must be provided on the service main, so that not more than a combined total of ____ are out of service due to a single break.
A sufficient number of sectional valves must be provided on the service main, so that not more than a combined total of ____ are out of service due to a single break.
Signup and view all the answers
A sufficient number of sectional valves must be provided on the service main, so that not more than a combined total of _____ separate buildings are out of service due to a single break.
A sufficient number of sectional valves must be provided on the service main, so that not more than a combined total of _____ separate buildings are out of service due to a single break.
Signup and view all the answers
In the absence of an installation established color code standard use ____ for non-potable water.
In the absence of an installation established color code standard use ____ for non-potable water.
Signup and view all the answers
In the absence of an installation established color code standard use ____ for potable water.
In the absence of an installation established color code standard use ____ for potable water.
Signup and view all the answers
In the absence of an installation established color code standard use ____ for reclaimed/reuse water.
In the absence of an installation established color code standard use ____ for reclaimed/reuse water.
Signup and view all the answers
Hydrant barrels must be long enough to permit an ____ clearance between the center of the 4 1/2-in outlet and grade.
Hydrant barrels must be long enough to permit an ____ clearance between the center of the 4 1/2-in outlet and grade.
Signup and view all the answers
Landscaping, fencing, bollards, and similar must be located a minimum of _____ from a hydrant.
Landscaping, fencing, bollards, and similar must be located a minimum of _____ from a hydrant.
Signup and view all the answers
All parts of the facility exterior must be within ____ feet of a hydrant.
All parts of the facility exterior must be within ____ feet of a hydrant.
Signup and view all the answers
Hydrants must be spaced so at least ____ hydrant be located within ____ feet of an FDC.
Hydrants must be spaced so at least ____ hydrant be located within ____ feet of an FDC.
Signup and view all the answers
Hydrants protecting warehouses must be spaced at ______ feet.
Hydrants protecting warehouses must be spaced at ______ feet.
Signup and view all the answers
Hydrant spacing must be spaced at ____ feet for non-sprinklered family housing.
Hydrant spacing must be spaced at ____ feet for non-sprinklered family housing.
Signup and view all the answers
____ and military/tactical equipment/vehicle parking shall be spaced at 300 feet.
____ and military/tactical equipment/vehicle parking shall be spaced at 300 feet.
Signup and view all the answers
Hydrant spacing must not exceed 1,000 feet with sprinklered ____.
Hydrant spacing must not exceed 1,000 feet with sprinklered ____.
Signup and view all the answers
Facility on-site water storage must be capable of being self-replenished to its required volume within ____ hours.
Facility on-site water storage must be capable of being self-replenished to its required volume within ____ hours.
Signup and view all the answers
A clear width of ____ feet must be provided from the room entry and in front of all equipment to the fire pump assembly and controller and ____-in behind the equipment.
A clear width of ____ feet must be provided from the room entry and in front of all equipment to the fire pump assembly and controller and ____-in behind the equipment.
Signup and view all the answers
Drainage piping of less than ____ inches may discharge to a floor drain.
Drainage piping of less than ____ inches may discharge to a floor drain.
Signup and view all the answers
Fire pumps must be arranged to automatically shut down after reaching the ____ psi stop pressure.
Fire pumps must be arranged to automatically shut down after reaching the ____ psi stop pressure.
Signup and view all the answers
Fire pumps must be arranged to automatically shut down after reaching the 5 psi stop pressure and the expiration of a minimum ____ minute run timer.
Fire pumps must be arranged to automatically shut down after reaching the 5 psi stop pressure and the expiration of a minimum ____ minute run timer.
Signup and view all the answers
When ____ or less sprinklers are modified, or relocated, shop drawings, hydraulic calculations, and material submittals are not required to be submitted.
When ____ or less sprinklers are modified, or relocated, shop drawings, hydraulic calculations, and material submittals are not required to be submitted.
Signup and view all the answers
Install ____ backflow preventers so that the bottom of the assembly is no greater than 24-in above the finished floor/grade.
Install ____ backflow preventers so that the bottom of the assembly is no greater than 24-in above the finished floor/grade.
Signup and view all the answers
Install ____ backflow preventers so that the upper operating handwheel is no more than 6 feet above the finished floor/grade.
Install ____ backflow preventers so that the upper operating handwheel is no more than 6 feet above the finished floor/grade.
Signup and view all the answers
Test valves must be 2.5-inch male angle or globe valves and provide _____ gpm.
Test valves must be 2.5-inch male angle or globe valves and provide _____ gpm.
Signup and view all the answers
Any drains, test connection pipe, etc., that penetrate the exterior wall must do so no greater than ____ feet (610 mm) above finished grade.
Any drains, test connection pipe, etc., that penetrate the exterior wall must do so no greater than ____ feet (610 mm) above finished grade.
Signup and view all the answers
Provide listed or approved sprinkler guards for sprinklers that are less than _____ above finished floor.
Provide listed or approved sprinkler guards for sprinklers that are less than _____ above finished floor.
Signup and view all the answers
Foam concentrate pumps must be used where the distance from the tank to the proportioner exceeds ____ feet.
Foam concentrate pumps must be used where the distance from the tank to the proportioner exceeds ____ feet.
Signup and view all the answers
Spill control must consist of a minimum ____ high concrete berm or similar and sized for the full volume of the tank.
Spill control must consist of a minimum ____ high concrete berm or similar and sized for the full volume of the tank.
Signup and view all the answers
For facilities less than four stories in height, ____ systems must be provided when the distance from any exterior door to any portion of the building (on any floor) exceeds 450 feet.
For facilities less than four stories in height, ____ systems must be provided when the distance from any exterior door to any portion of the building (on any floor) exceeds 450 feet.
Signup and view all the answers
Clean agent fire extinguishing systems must comply with NFPA ____.
Clean agent fire extinguishing systems must comply with NFPA ____.
Signup and view all the answers
Water mist fire protection systems must comply with NFPA ____.
Water mist fire protection systems must comply with NFPA ____.
Signup and view all the answers
Carbon dioxide systems must comply with NFPA ____.
Carbon dioxide systems must comply with NFPA ____.
Signup and view all the answers
When are general purpose portable fire extinguishers not required?
When are general purpose portable fire extinguishers not required?
Signup and view all the answers
Fire alarm systems (detection and notification) must comply with the applicable provisions of NFPA ____.
Fire alarm systems (detection and notification) must comply with the applicable provisions of NFPA ____.
Signup and view all the answers
The fire alarm control panel must be capable of storing at least ____ events in the history log.
The fire alarm control panel must be capable of storing at least ____ events in the history log.
Signup and view all the answers
Provide rechargeable batteries per NFPA 72 to operate the fire alarm system under supervisory conditions for ____ hours and all alarm devices for an additional ____ minutes.
Provide rechargeable batteries per NFPA 72 to operate the fire alarm system under supervisory conditions for ____ hours and all alarm devices for an additional ____ minutes.
Signup and view all the answers
Study Notes
Fire Protection Systems Overview
- Facilities greater than 5,000 ft² or more than two stories must have all-weather ground access for emergency vehicle access.
- Facilities above two stories need at least one means of all-weather ground access.
- All-weather ground access must be paved and terminate within 33 feet of an exterior door for fire department access.
Fire Flow Requirements
- Fire Flow minimum for sprinklered facilities is 1,000 gpm at 20 psi.
- Non-sprinklered, one-story family housing requires a Fire Flow of 500 gpm, while two-story needs 750 gpm, and three stories or above requires 1,000 gpm.
- Aircraft parking refueling facilities require a Fire Flow of 1,000 gpm for at least a 2-hour duration.
- Vehicle parking areas also need a Fire Flow of 500 gpm for 2 hours.
Water Service Specifications
- Service mains must be looped to provide 50% of required Fire Flow in case of a break.
- Minimum residual pressure in service mains should not be less than 20 psi.
- Hydrants must not exceed two on a Service Lateral, which should be at least 6 inches in diameter for fire sprinkler systems.
Hydrant and Maintenance Standards
- A sufficient number of sectional valves should allow no more than five hydrants or three buildings to be out of service due to a single break.
- Fire hydrants must be spaced at a maximum of 600 feet for non-sprinklered family housing and 1,000 feet with sprinkler systems.
- Facility on-site water storage must self-replenish within 48 hours.
Equipment and Alarm Systems
- Clearance of 3 feet must be maintained for fire pump assembly access.
- Drainage piping less than 3/4 inches may discharge to a floor drain.
- Fire pumps should shut down after reaching a set pressure of 5 psi and a minimum run timer of 10 minutes.
Backflow Preventers and Extinguishing Systems
- Horizontal backflow preventers should be installed no higher than 24 inches above the floor/grade.
- Vertical backflow preventers should have an upper hand wheel maximum height of 6 feet.
- Clean agent fire extinguishing systems must comply with NFPA 2001, while water mist systems must comply with NFPA 750.
Battery and Alarm Compliance
- Fire alarm systems must adhere to the guidelines of NFPA 72, which includes the capacity to store at least 400 events in the history log.
- Rechargeable batteries must support the fire alarm system for 48 hours under supervisory conditions and provide 15 minutes of operation for alarm devices.
Key Color Codes for Water Systems
- Non-potable water is indicated by red, while potable water is indicated by yellow. Reclaimed/reuse water is designated purple.