Testing and Repair of Pressure Relief Valves
12 Questions
1 Views

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to lesson

Podcast

Play an AI-generated podcast conversation about this lesson

Questions and Answers

What is the purpose of the 'pop test' for safety valves?

  • To check the full operation of the safety valve, including the exact pressures at which it opens and closes (correct)
  • To determine whether the valve is operating properly or if it requires repair or replacement
  • To increase boiler steam pressure to the safety valve set point
  • To perform maintenance on the safety valve
  • When should the pop test be performed?

  • Annually (correct)
  • Bi-annually
  • Quarterly
  • Semi-annually
  • Who is qualified to adjust or repair pressure relief valves according to ASME BPVC sections?

  • Valve manufacturer or its authorized repair representative (correct)
  • Boiler maintenance personnel
  • Local boiler operators
  • Valve users
  • What should be done if the safety valve continues to simmer after operating the try lever?

    <p>It should be repaired or replaced</p> Signup and view all the answers

    What should be compared during the pop test to determine if the valve is operating properly?

    <p>Opening pressure and blowdown</p> Signup and view all the answers

    What should be done before taking a boiler off-line for maintenance, according to the text?

    <p>Perform a pop test on all safety valves</p> Signup and view all the answers

    What is the purpose of a try lever test for pressure relief valves?

    <p>To determine if the valve is operating freely</p> Signup and view all the answers

    How often should try lever tests be performed for power boilers operating below 2760 kPa?

    <p>Every six months</p> Signup and view all the answers

    What is the minimum required pressure for performing a try lever test on a steam heating boiler?

    <p>35 kPa</p> Signup and view all the answers

    When should try lever tests be performed?

    <p>Before pop tests and accumulation tests</p> Signup and view all the answers

    Where can detailed descriptions of pressure relief valve test procedures be found?

    <p>Part B, Unit 4, Chapter 4 Operational Checks</p> Signup and view all the answers

    What is the primary purpose of keeping pressure relief valves in good working condition?

    <p>To ensure safe operation of the equipment</p> Signup and view all the answers