What is the purpose of a try lever test for pressure relief valves?

  • To check for leaks in the valve
  • To determine the pressure at which the valve opens
  • To determine if a pressure relief valve is operating freely (correct)
  • To assess the valve's compatibility with different types of boilers
  • How often should a try lever test be performed on power boilers operating below 2760 kPa?

  • Annually
  • Monthly
  • Every three months
  • Every six months (correct)
  • What is the minimum required pressure for performing a try lever test on a steam heating boiler?

  • 45 kPa
  • 35 kPa (correct)
  • 55 kPa
  • 25 kPa
  • When should try lever tests be conducted?

    <p>Before conducting pop tests and accumulation tests</p> Signup and view all the answers

    What is the minimum required pressure for performing a try lever test on a power boiler?

    <p>75% of the setting of the safety valve</p> Signup and view all the answers

    If a pressure relief valve simmers after a try lever test, what does it indicate?

    <p>The valve may have leaks</p> Signup and view all the answers

    What is the purpose of the pop test for a safety valve?

    <p>To measure the pressure at which the safety valve opens and closes</p> Signup and view all the answers

    When should a pop test be performed on a boiler?

    <p>Annually</p> Signup and view all the answers

    Who is qualified to adjust or repair pressure relief valves as per ASME BPVC?

    <p>Valve manufacturers or their authorized repair representative</p> Signup and view all the answers

    What should be done if a safety valve continues to simmer after operating the try lever?

    <p>It must be repaired or replaced</p> Signup and view all the answers

    Why is it important to perform a pop test before taking a boiler off-line for maintenance?

    <p>To identify any defective valves for replacement or repair</p> Signup and view all the answers

    What should be done after accurately recording the opening and reseating pressures in a pop test?

    <p>Compare the opening pressure and blowdown to established tolerances</p> Signup and view all the answers