Podcast
Questions and Answers
What is the primary advantage of using proportional controllers in a system?
What is the primary advantage of using proportional controllers in a system?
- Increasing the maximum overshoot of the system.
- Reducing the steady-state error and increasing system stability. (correct)
- Ensuring rapid response to disturbances.
- Eliminating offsets completely.
Increasing the proportional band in a control system always reduces hunting and instability.
Increasing the proportional band in a control system always reduces hunting and instability.
False (B)
In the context of proportional control, what term describes the difference between the desired value and the actual steady state value of a process variable?
In the context of proportional control, what term describes the difference between the desired value and the actual steady state value of a process variable?
Offset
In a proportional controller, the controller output is directly proportional to the ______ signal.
In a proportional controller, the controller output is directly proportional to the ______ signal.
What is the recommended value for the proportional constant (Kp) in a proportional controller to effectively amplify the error signal?
What is the recommended value for the proportional constant (Kp) in a proportional controller to effectively amplify the error signal?
Integral controllers are effective at quickly responding to and correcting sudden errors or disturbances in a system.
Integral controllers are effective at quickly responding to and correcting sudden errors or disturbances in a system.
What is the primary function of an Integral controller, which leads to them often being referred to as 'reset controllers'?
What is the primary function of an Integral controller, which leads to them often being referred to as 'reset controllers'?
In integral control, a shorter reset time will result in a ______ integral action, which can lead to overshoot.
In integral control, a shorter reset time will result in a ______ integral action, which can lead to overshoot.
Which of the following is a disadvantage of using integral controllers in a control system?
Which of the following is a disadvantage of using integral controllers in a control system?
Derivative controllers are typically used alone to improve steady-state error in control systems.
Derivative controllers are typically used alone to improve steady-state error in control systems.
What characteristic of derivative control action allows it to anticipate the final value of a measured variable?
What characteristic of derivative control action allows it to anticipate the final value of a measured variable?
Derivative action helps to reduce the amount of measurement deviation and ______ by enabling the use of a narrower proportional band.
Derivative action helps to reduce the amount of measurement deviation and ______ by enabling the use of a narrower proportional band.
What is the primary advantage of using derivative controllers in a control system?
What is the primary advantage of using derivative controllers in a control system?
Match the following controller types with their respective actions:
Match the following controller types with their respective actions:
In the context of manual PID controller tuning, what is the first step?
In the context of manual PID controller tuning, what is the first step?
After increasing Kp, Ki should be increased until system instability occurs.
After increasing Kp, Ki should be increased until system instability occurs.
What is the purpose of using PID tuning and loop optimization software in modern control systems?
What is the purpose of using PID tuning and loop optimization software in modern control systems?
The most significant improvement to PID control involves incorporating ______ control, which uses knowledge about the system to anticipate and mitigate disturbances.
The most significant improvement to PID control involves incorporating ______ control, which uses knowledge about the system to anticipate and mitigate disturbances.
What is the purpose of a 'dead band' in split range control systems?
What is the purpose of a 'dead band' in split range control systems?
In split-range control, the control valves always operate over the same range of input signals.
In split-range control, the control valves always operate over the same range of input signals.
Define what a 'master flow' is in a ratio-control system.
Define what a 'master flow' is in a ratio-control system.
In digital systems, a transducer or sensor's analog signals are converted into ______ before being used by the controller.
In digital systems, a transducer or sensor's analog signals are converted into ______ before being used by the controller.
What is the output of an OR gate if one input is 'true' and the other is 'false'?
What is the output of an OR gate if one input is 'true' and the other is 'false'?
If 0 is called 'false' and 1 is called 'true', the AND gate outputs 'true' if either input is 'true.'
If 0 is called 'false' and 1 is called 'true', the AND gate outputs 'true' if either input is 'true.'
How does an XOR (exclusive-OR) gate behave, and how does it differ from a regular OR gate?
How does an XOR (exclusive-OR) gate behave, and how does it differ from a regular OR gate?
Flashcards
Proportional Controller
Proportional Controller
Controllers where the output is directly proportional to the error signal.
Offset
Offset
Difference between the new value and desired value in proportional control.
Integral Controllers
Integral Controllers
Controllers where the output is proportional to the integral of the error signal over time.
Advantage of Integral Controllers
Advantage of Integral Controllers
Signup and view all the flashcards
Reset Time
Reset Time
Signup and view all the flashcards
Derivative Controllers
Derivative Controllers
Signup and view all the flashcards
Advantage of Derivative Controllers
Advantage of Derivative Controllers
Signup and view all the flashcards
PID Controller
PID Controller
Signup and view all the flashcards
Split Range Control
Split Range Control
Signup and view all the flashcards
Dead Band
Dead Band
Signup and view all the flashcards
Ratio Control
Ratio Control
Signup and view all the flashcards
Cascade Control
Cascade Control
Signup and view all the flashcards
Two Element Control
Two Element Control
Signup and view all the flashcards
Process Control
Process Control
Signup and view all the flashcards
Feedback Loop
Feedback Loop
Signup and view all the flashcards
Controlled/Measured Variable
Controlled/Measured Variable
Signup and view all the flashcards
Manipulated Variable
Manipulated Variable
Signup and view all the flashcards
Set Point
Set Point
Signup and view all the flashcards
Sensor
Sensor
Signup and view all the flashcards
Transducer
Transducer
Signup and view all the flashcards
Controllers
Controllers
Signup and view all the flashcards
Error Signal
Error Signal
Signup and view all the flashcards
Correction Signal
Correction Signal
Signup and view all the flashcards
Transmitters
Transmitters
Signup and view all the flashcards
Integrated Circuit
Integrated Circuit
Signup and view all the flashcards
Study Notes
PID Controllers
- Proportional controllers operate correctly when deviations are not too large or sudden.
- The output is directly proportional to the error signal.
- A(t) ∝ e(t) represents the proportional controller output being directly proportional to the error signal.
- A(t) = Kp * e(t) is the equation when removing the sign of proportionality, where Kp is the proportional constant/controller gain.
- Kp should be greater than unity to amplify the error signal for easy detection.
- Proportional controllers reduce steady-state error and stabilize the system.
- Proportional controllers introduce offsets and increase the maximum overshoot.
- Proportional control action arrests changes and holds them steady, but at a different point from the desired value, with the difference being the "offset".
- Offset can be reduced by increasing system sensitivity via a narrower proportional band.
- Pneumatic proportional controllers use bellows to establish a set value and feed in the measured value.
- Differences in pressure cause movement, altering airflow and output pressure to the controlled valve.
- Moving the nozzle relative to the flapper increases sensitivity and gain, narrowing proportional bandwidth.
- The top end of the flapper moves oppositely to the lower end, reducing sensitivity and widening the proportional band.
- Objectives when adjusting a controller to a plant are minimum offset and stability.
- Proportional control provides throttling action to balance process input with demand.
- A set point is where it's desired to maintain the measured variable
- Offset is the deviation between the set point and the control point.
- Measurements stabilize within the proportional band, but narrowing it too much causes on-off controller cycling.
Integral Controllers
- Output is directly proportional to the integral of the error signal; also known as the actuating signal
- A(t) ∝ ∫e(t)dt is the equation for this relationship
- A(t) = Ki * ∫e(t)dt is the equation after removing the sign of proportionality, where Ki is the integral constant/controller gain.
- Integral controllers can be referred to as reset controllers.
- Reset controllers can return the controlled variable to the set point after a disturbance.
- A disadvantage is that it can make the system unstable by responding slowly to error.
- Proportional and integral action (P+I) can arrest change and reset to the desired value, load independent.
- Integral action happens continuously while deviation exists.
- Controllers have reset time adjustments, shorter times mean greater integral action, but too much integral effect causes overshoot.
Integral Corrective Action
- If an offset is acceptable, using a simple proportional controller may be best.
- Controllers can be adjusted to vary the integral action time or 'reset time'.
- Integral action is directly related to proportional control action.
- Integral action time is the time it takes for integral action to alter the controller output by an amount equal to the proportional action.
- As processes become harder to control, the proportional band must be increased to eliminate cycling.
- To maintain measurement, a control function can be introduced to maintain the measurement near a precise point, insteading of within the band
Derivative Controllers
- These are never used alone, but in combinations with other modes of controllers
- Derivative controllers cannot improve steady-state error, produce saturation effects, and amplify noise signals.
- The output is proportional to the derivative of the error signal.
- A(t) ∝ de(t)/dt is the equation for this relationship.
- A(t) = Kd * de(t)/dt is the equation after removing the sign of proportionality, where Kd is the proportional constant/controller gain.
- A derivative controller can be referred to as a rate controller.
- Derivative controllers improve the transient response of the system.
- The longer the derivative action time (adjustable), the greater the derivative action.
- Integral action is needed to eliminate offset with minimal overshoot.
- A third-term derivative control action can be a damping action to reduce overshoot.
- Derivative control action is anticipatory and deviations in the rate of change can estimate the final value of a measured variable
- A control signal based on the rate of change of a deviation can over-correct the controlled condition, reducing deviations.
- Rapid changes cause large overshoots, slow changes give small overshoots.
- Derivative control sets up a correction signal proportional to the variable's velocity when the variable is moving.
- Proportional mode produces a response proportional to deviation from the set point.
- Integral response is proportional to the time the measurement is away from the set point.
- Derivative response is proportional to the rate at which the measurement departs.
- A derivative control mode, when added to proportional-plus-integral-plus-derivative control, allows for a narrower proportional band reducing measurement deviation and overshoot.
- Pneumatic proportional-plus-integral-plus-derivative controllers differ from proportional-plus-integral ones with an adjustable derivative resistance (restrictor) in the feedback circuit.
- When the measurement is at the set point, the pressures in the proportional and integral bellows are equal to the output pressure of the controller.
- If the measurement increases uniformly, the derivative restrictor delays the output pressure from reaching the bellows, delaying the effect of reducing output, maintaining constant differential pressure.
PID Control Summary
- (P) indicates a Single term controller
- (P+I) or (P+D) indicates a Two term controller
- (P+I+D) indicates a Three term controller
PID Controller Tuning
- When manually setting a PID controller, first set the Ki (integral) and Kd (derivative) values to zero.
- Increase Kp (proportional) until the output of the loop oscillates, then set Kp to about half.
- Increase Ki until the offset is corrected in a timeframe, but be aware that too much Ki will cause instability.
- Increase Kd until the response is quick enough after a load change, but again be aware that too much results in excessive response and overshoot.
- Fast-acting PID loops usually overshoot to reach the setpoint quicker. But some systems cannot accept overshoot, where an over-damped closed loop system is needed.
- The Kp setting will need to be significantly less than half the initial value that was causing the oscillation.
- Manual calculation has been replaced with PID tuning and loop optimization software to ensure consistent results. The software will then gather data, develop process models and suggest optimal tuning.
- Some digital loop controllers feature a self-tuning process using small set point changes for optimal tuning values.
Limitations of PID Controllers
- PID controllers can perform poorly in some applications without optimal control.
- The fundamental issue is that it is a feedback control system, with constant parameters, where there is no knowledge of the process.
- For this reason performance is reactive and is a compromise
- PID control is the most effective when there is an observer capacity without a process model.
- Better performance can be attained by overtly modeling the process
PID Improvements
- A significant improvement is incorporating feed-forward control using knowledge about the system
- PID controllers can be changed using gain scheduling, adaptive modifications, improved measurement or cascading multiple PID controllers.
- Control system performance can be improved with feed-forward (open-loop) control, combined with feedback (closed-loop) PID control.
- Feed-forward values can provide most of the controller output.
- The PID controller has to compensate for any difference or error remains between the set point and system response to the open loop control.
- Since its unaffected by the process feedback, it can never cause the control system to oscillate, improving system response and stability.
- Feed-forward can be based on the set point and any extra measured disturbances.
Control System Loops: Split Range Control
-
Split-range control uses one controller to manage two final-control elements
-
Typically found in temperature control applications but extends far beyond this.
-
In temperature control applications, the process could need heating or cooling dependent on product temperate
-
The controller output range (0% – 100%) is split between two valves.
-
If the controller output:
- is between 0%–50%, then the cooling valve operates, fully open at 0% and fully closed at 50%
- is between 50%–100%, then the heating valve operates, starts to open at 50% and is fully open at 100%
-
In split-range control, there are different ways to connect the valves so they operate on two different ranges.
-
Current-to-pressure converters split controller output; one responding to 4mA to 12mA, the other to 12mA to 20mA.
-
Split-range can happen with pneumatic signals; the two valves are mechanically designed differently, using spring/diaphragm actuators.
-
Cooling valve opens/closes from 3psi–8psi; the heating valve closes/opens from 8psi–13psi.
Dead Band for Split Range Control
- Continuous switching between cooling and heating near 50% output may arise
- A dead band avoids oscillation. Set the cooling valve range from 0%–49% and the heating valve range from 51%–100%.
- In engine thermal load, the slave controller detects lube oil temperature changes from the cooler, compares it to the set value and adjust is seawater flow through the cooler.
- With constant seawater temperature and an engine thermal-load drop, the master controller sense is a piston cooling oil temperature drop, and adjust is the seawater flow through the cooler.
- If the engine thermal load is low or zero, steam diaphragm valve (1) receives signal from slave controller, which supplies steam to the lube oil heater.
- Means that the slave control is split between valve positioners (1) and (2), which is called "split range control" or "split level control".
- The slave controller output range is between 1.2 and 2.0 bar. - Valve positioner (1) works on the range 1.2 to 1.4 bar. - Valve positioner (2) works on the range 1.4 to 2.0 bar.
- The range is split in the ratio 1:3.
Control System Loops - Ratio Control
- Ratio control maintains set ratios between two or more flow rates
- In a ratio-control scenario, one flow, "master flow", aligns with production rate.
- The ratio controller regulates another flow to maintain the desired ratio between the two flows, which is called the "controlled flow".
- In treating water with chlorine, water is the master flow while chlorine is the controlled flow.
- Ratio control should calculate a flow set point, not a division of flow rates.
Control System Loops - Cascade Control
- A product temperature regulated via heated oil jacket utilizes cascade control.
- The maximum input (400°C) restricts jacket temperature.
- At start-up, the master compares the product temperature (ambient) to its setpoint (300°C) to give maximum output.
- This sets the slave’s maximum setpoint (400°C); the slave compares it to the jacket temperature (ambient) giving maximum heater output.
- As the jacket temperature rises towards setpoint, the slave’s heater output decreases.
- The master's PID output decreases, reducing the ‘jacket’ setpoint on the slave, when product temperature rises.
- Balanced occurs when continuing this process
- Quicker, smoother control results while coping with load changes by keeping the jacket temperature within acceptable tolerances.
Control System Loops - Two Element Control
- Steam flow and water level measurements define two-element control.
- Sends out a pneumatic proportional to changes in its measured variable.
- The steam flow signal goes to a relay. This relay transmits signal to the valve positioner, via hand auto unit, which alters the valve position an amount proportional to the steam flow.
- Characteristics in the valve positioner are adjusted to match changes with feed
- The water level signal goes to a P+I controller whose set value adjusts to keep the boiler water at a desired level is set.
- Any deviation of the water level and the desired values results in a change in output signal from the controller to the relay.
- This signal is added to the steam flow signal to correct the deviation in level which could occur due to unbalance of boiler feed and steam flow.
Process Control
- A basic control example is keeping water temperature constant at cleaning stations despite demand.
- Manual control uses a thermometer and operator adjustment to maintain the temperature.
- Automated control senses the water temperature, sends an electrical signal to a controller, which sends a correcting signal to an actuator; the actuator adjusts steam flow to maintain the temperature.
- Process control automatically manages output by comparing a measured output to the desired "set value," adjusting an input variable based on the error signal.
Additional Process Control Info
-
A process manipulates inputs to create a new output, and controlled inputs and measured output parameters make up variables.
-
Rather than being limited to one variable, a controller can measure and control many variables, for example, as an engine processor does.
-
Functions performed by an engine processor, typically over six to eight devices depending on the number of cylinders, have to be within approximately 5 milliseconds.
-
Examples of measured and controlled variables in the Automotive Engine:
- Measured Variables: Manifold Air Pressure, Manifold Air Flow, Oxygen in Exhaust
- Controlled Variables: Ignition Timing, Injector Timing, Fuel Flow
-
The measuring element comprises a sensor, transducer, and transmitter plus regulated power, while the control element comprises actuator, power control circuit and power. The controller comprises a processor with a memory and summing circuit to compare set point with sensed signal. The processor uses the error to generate a correction signal to control the actuator and the input variable.
Process Control Terminology
- Feedback loop: the signal path from output to input that corrects variations between output and setpoint where the output of a process is being continually monitored. The error is determined, and a correction signal is sent back to inputs.
- Controlled/measured variable: the monitored process output value.
- Manipulated variable: the input that a control signal varies via an actuator.
- Set point: the desired output value monitored by a sensor, where any deviation creates an error signal.
- Instrument: any device indicating/measuring physical quantities/conditions.
- Sensors: detect physical variables; examples include thermometers (temperature), or diaphragm pressure sensors with strain transducers.
- Transducers: change energy form (resistance thermometer converting temp to resistance).
- Converters: change signal format (voltage-to-current).
- Actuators: control an input variable in response to controller signals with a typical example being a flow-control valve.
- Controllers: Monitor signals from transducers to keep the process within limits.
- Programmable Logic Controllers (PLCs): Microprocessor-based systems used in process control. They use analog/digital I/O, communicate globally, are easily programmed, and supply extensive data.
- Ladder networks are typically used to program these controllers
- Error signal: the difference between the "set point" and the amplitude of the measured variable.
- Correction signal: controls actuator power to set the input level.
- Transmitters: amplify/format signals for long-distance transmission of data, or digital signals that can be transmitted without information loss.
Integrated Circuits
-
Integrated circuit is a set of electronic circuits on a silicon piece, and can be called an IC, chip, or microchip
-
Integrated circuits can be:
- analog
- digital
- mixed signal with both analog and digital
-
Digital integrated circuits squares millimeters and can contain billions of logic gates, multiplexers, flip-flops, etc.
-
These digital integrated circuits require little, low power and speed to operate, used in microprocessors and microcontrollers to process ‘“one” and “zero” signals with Boolean algebra.
-
Microprocessors, which control computers and cellular phones, are among the most advanced integrated circuits.
-
Digital memory chips and application-specific integrated circuits (ASICs) are used in modern applications.
-
Programmable logic devices came about in the 1980s
-
Logical function and connectivity is able to be programmed by the user, rather than the manufacture, so a chip can implement different functions such as logic gates, adders, and registers.
-
Analog ICs (sensors, power management, operational amplifiers), work in continuous signals.
-
Mixed chips combine analog and digital circuits for A/D and D/A converters, while requiring concern for signal interference.
-
Mono-crystalline silicon is the main substance used, with gallium arsenide for LEDs, lasers etc.
-
A random-access memory (RAM) is a typical IC, and material layers are fabricated like a photographic.
Logic Gates
- Combining Gates enables complex operations, limited in practice
- Arrays of Logic Gates are found in Digital Integrated Circuits (ICs).
- Digital Devices of the same size shrink as logic gate volume gets smaller and become more capable.
The AND Gate
- Act in the same way as the logical and operator
- the output is true when both inputs are true other wise it is false
The OR Gate
- Its output is true of either or both inputs are true otherwise it is false
Derived and Inverter Gates (XOR)
- The XOR (exclusive OR) Gate acts in the same way as the logical other/or.
- Output is true if either, but not both, inputs are true
- Output is false if both inputs are true or both imputs arwe false
- In other words, the output is 1 if the inputs are different otherwise they are the same
Inverter
- Only has one input and is somtimes called a nor gate
- Reverses logic gate
- The NAND Gate a negation and and gate
- it acts as the AND logical gate with the negation process the output is false if both imputs are true otherwise the output is true.
- There is no fimited ofr inouts that cab be used in a NAND function nor a funktional amount of inputs that can be used to NAND
- The NOR gate is a combination OR that is followed by an invertor if both inputis are false output is true if not output if false
- The XNOR (exclusive NOR) gate is a combination XOR gate followed by an invertor. Unlike OR/NOR adn AND/NAND Functions XOR always has 2 imputs
Studying That Suits You
Use AI to generate personalized quizzes and flashcards to suit your learning preferences.