SOP S1-6230
13 Questions
0 Views

SOP S1-6230

Created by
@ImpeccableCarnelian4634

Questions and Answers

What are abnormal conditions?

  • Controllable conditions that have reached an emergency level
  • Controllable conditions that could cause a safety issue but have not reached an emergency level (correct)
  • Uncontrollable conditions that could cause a safety issue
  • Uncontrollable conditions that have reached an emergency level
  • What is required when taking an LNG storage tank out of service for maintenance or repair?

  • A written detailed procedure (correct)
  • No procedure is required
  • A verbal request
  • A simple written request
  • When is warming and cooldown procedure necessary for an LNG storage tank?

  • When it has a leak
  • When it is full
  • When it is in service
  • When it has been out of service for maintenance or repair (correct)
  • Do FNG LNG storage tanks operate year-round?

    <p>Yes</p> Signup and view all the answers

    What is required when warming or depressurizing an FNG LNG storage tank?

    <p>A written detailed procedure</p> Signup and view all the answers

    What is the Maximum Allowable Operating Pressure (MAOP) for Distribution Pressure?

    <p>60 psi</p> Signup and view all the answers

    What is the typical operating pressure for Distribution Pressure at Site #1?

    <p>45-50 psi</p> Signup and view all the answers

    What gas detection procedures are in place?

    <p>Procedures are in place for levels between 25% and 50% LEL and levels over 50% LEL</p> Signup and view all the answers

    What happens when gas detectors reach 50% LEL?

    <p>The ESD system automatically shuts down all valves tied to the ESD system</p> Signup and view all the answers

    What is the SOP for flame detectors activation due to fire?

    <p>SOP 1112 - Fire Protection Plan</p> Signup and view all the answers

    What are the specific steps outlined in the procedure for false detections caused by low temperature, glaring sun, or other causes?

    <p>The operator should verify the detection and follow the procedure</p> Signup and view all the answers

    What is the proper PPE and ventilation in case of accidental release of polypropylene glycol?

    <p>Specialized PPE and ventilation is required</p> Signup and view all the answers

    What is the recommended time to change the filter element in Master Meter Dry Gas Filters?

    <p>At half of its collapsible differential pressure of 12.5 PSIG</p> Signup and view all the answers

    Study Notes

    Procedures for Abnormal Operating Conditions in LNG Storage and Distribution

    • Abnormal conditions are controllable conditions that could cause a safety issue but have not reached an emergency level.
    • Taking an LNG storage tank out of service for maintenance or repair requires a written detailed procedure.
    • Warming and cooldown procedures are necessary when an LNG storage tank requires maintenance or repair and has been out of service, respectively.
    • FNG LNG storage tanks are operational year-round, and warming or depressurizing them requires a detailed written procedure.
    • Abnormal operating conditions may exist if Distribution Pressure exceeds its Maximum Allowable Operating Pressure (60 psi).
    • Distribution Pressure at Site #1 is typically operated at 45-50 psi, well below the MAOP of 60 psi.
    • Gas detection procedures are in place for levels between 25% and 50% LEL and levels over 50% LEL.
    • The ESD system automatically shuts down all valves tied to the ESD system when gas detectors reach 50% LEL.
    • Flame detectors activation due to fire requires following SOP 1112 - Fire Protection Plan.
    • False detections caused by low temperature, glaring sun, or other causes require specific steps outlined in the procedure.
    • Polypropylene glycol is used in the system and requires proper PPE and ventilation in case of accidental release.
    • Good engineering practice suggests changing the filter element in Master Meter Dry Gas Filters at half of its collapsible differential pressure of 12.5 PSIG.

    Studying That Suits You

    Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

    Quiz Team

    Description

    Test your knowledge on Procedures for Abnormal Operating Conditions in LNG Storage and Distribution with this informative quiz. From understanding warming and cooldown procedures to gas detection protocols, this quiz will cover all the essential aspects of ensuring safety in LNG storage and distribution. Learn about written detailed procedures and good engineering practices that are necessary to prevent safety issues and handle any abnormal operating conditions that may arise. Don't miss out on this opportunity to enhance your understanding of LNG storage and distribution procedures and take this quiz now!

    More Quizzes Like This

    SOP Test
    10 questions

    SOP Test

    LuxuryCoral avatar
    LuxuryCoral
    SOP 72
    45 questions

    SOP 72

    ResourcefulPointillism avatar
    ResourcefulPointillism
    SOP 73
    67 questions

    SOP 73

    ResourcefulPointillism avatar
    ResourcefulPointillism
    SOP 34-35
    41 questions

    SOP 34-35

    ResourcefulPointillism avatar
    ResourcefulPointillism
    Use Quizgecko on...
    Browser
    Browser