4BE3.5 U3 C2 Obj1 Easy Medium Hard

WholesomeMaroon avatar
WholesomeMaroon
·
·
Download

Start Quiz

Study Flashcards

114 Questions

EASY What is the main purpose of the codes published by organizations such as CSA, ASME, and NFPA?

To ensure combustion safety

What type of burners are covered by the CSA B149.3 Code?

Natural gas and propane burners on non-certified appliances

Why does Figure 1 differ from other fuel trains shown in the PanGlobal Fourth Class text?

Because of different codes and regulations

What is the minimum input required for a boiler to be suitable for the fuel train configuration in Figure 1?

3.663 MW (12 500 000 Btuh input or 300 BoHP output)

Why is it reasonable for Fourth Class Power Engineers to be familiar with the fuel train in Figure 1?

Because Fourth Class Power Engineers can serve as Shift Engineers and Assistant Shift Engineers in Third and Second Class plants

What is the significance of the CSA B149.3 Code in Canada?

It takes precedence over international codes

What is the main difference between the fuel train in Figure 1 and other fuel trains in the PanGlobal Fourth Class text?

Code requirements

What is the purpose of the fuel train components?

To ensure combustion safety

What is the primary purpose of fuel piping in a gas supply system?

To deliver the correct amount of fuel to the burner without excessive pressure drop

What is the function of the fuel strainer in a gas supply system?

To catch debris introduced into fuel lines during installation

What is the purpose of the pressure relief valve in a gas supply system?

To relieve excessive fuel pressure and protect burner components

What is the purpose of the low gas pressure cut-off switch in a gas supply system?

To shut off the burner if the fuel pressure drops below 50% of the lowest normal operating pressure

What is the purpose of the main fuel safety shut-off valve in a gas supply system?

To prevent the accumulation of explosive fuel-air mixtures in furnaces when not in operation

What is the minimum input requirement for appliances to have a low gas pressure safety device?

120 kW (400 000 Btuh)

What is the maximum fuel pressure allowed inside buildings of various occupancies?

Defined by the CSA B41 and Propane Installation code

What is the purpose of the manual shut-off valve in a gas supply system?

To serve as isolation points for fuel train maintenance

What is the location of the low gas pressure cut-off switch in a gas supply system?

Downstream of the pressure regulator and pressure relief valve

What is the certification requirement for main fuel safety shut-off valves in a gas supply system?

CSA 6.5

What is the function of the Safety Vent Valve?

To bleed trapped fuel to the atmosphere

Under what conditions do Main SSOVs shut off the fuel flow to the main burner?

During normal operating limits or unsafe conditions

What prevents the boiler from proceeding with an ignition sequence if an SSOV does not fully close?

Proof-of-closure switches

What is the function of the Input Flow Control Valve?

To control fuel in accordance with the load demand

What is the purpose of the test firing valves?

To test the operation of the flame detection devices

What happens when the main SSOVs shut and the safety vent valve fails open?

Trapped fuel is bled to the atmosphere

Why is the firing rate control valve located downstream of the low gas pressure cut-off switch?

To prevent the LGPCO from actuating at low firing rates

What is the purpose of the pilot safety shut-off valves?

To shut off the fuel flow to the pilot burner

What is the function of the fuel pressure test ports?

To test, adjust, or monitor the fuel pressure

Why are proof-of-closure switches required on the main SSOVs?

To prevent fuel gas from leaking into the combustion chamber

What is the purpose of the quarter-turn isolation valve and pipe cap at each port?

To provide a connection point for pressure gauges or electronic instruments

What is the function of the pressure regulator in the fuel oil train?

To maintain fuel pressure at the nozzle

What is the purpose of the fuel filter in the fuel oil train?

To protect oil burner nozzles from suspended fuel contaminants

What is the function of the low oil temperature cut-off switch?

To stop the flow of fuel to the burner when the fuel oil temperature falls below the recommended range

What is the purpose of the low atomizing media cut-off switch?

To supervise the atomizing media pressure

What is the consequence of poor atomization in an oil burner?

Incomplete combustion and the creation of toxic and explosive carbon monoxide

What is the function of the safety shut-off valves in the fuel oil train?

To stop the flow of oil to the burner when operating limits are reached or under adverse combustion conditions

What is the purpose of the fuel pump in the fuel oil train?

To provide the necessary flow and pressure for proper atomization at the maximum firing rate

What is the code that covers all automatically fired heating and power boilers up to 3.663 MW input?

ASME CSD-1

What is the purpose of the pressure relief valve in the fuel oil train?

To divert excessive fuel pressure back to the oil tank or suction line

MEDIUM What is the function of the fuel filter in an oil burner?

To remove suspended fuel contaminants

What is the purpose of the low oil temperature cut-off switch in an oil burner?

To prevent the burner from starting if the fuel oil temperature falls below the recommended range

What is the consequence of poor atomization in an oil burner?

Incomplete combustion and creation of toxic and explosive carbon monoxide

What is the function of the safety shut-off valves in the fuel oil train?

To stop the flow of oil to the burner when operating limits are reached or under adverse combustion conditions

What is the purpose of the pressure relief valve in the fuel oil train?

To divert excessive fuel pressure back to the oil tank or suction line

What is the code that covers automatically fired heating and power boilers up to 3.663 MW input?

ASME CSD-1

What is the function of the fuel pump in the fuel oil train?

To provide the necessary flow and pressure for proper atomization at the maximum firing rate

What is the purpose of the low atomizing media cut-off switch?

To prevent the burner from starting if the atomizing media pressure falls below the recommended range

What is the function of the pressure gauge installed at the test port?

To monitor fuel pressure conditions

Why are fuel filters necessary in an oil burner?

To remove suspended fuel contaminants that can affect the spray pattern and quality of atomization

What is the primary function of the fuel strainer in a gas supply system?

To filter out debris from the fuel line

What is the purpose of the pressure relief valve in a gas supply system?

To prevent over-pressurization of the burner piping components

What is the primary function of the main manual shut-off valve in a gas supply system?

To shut off the fuel supply for maintenance

What is the requirement for appliances with inputs in excess of 120 kW (400 000 Btuh)?

A low gas pressure safety device must be installed

What is the certification requirement for main fuel safety shut-off valves in a gas supply system?

CSA 6.5

What is the purpose of the low gas pressure cut-off switch in a gas supply system?

To shut off the fuel supply in case of low pressure

What is the location of the high gas pressure cut-off switch in a gas supply system?

Upstream of the flow control valve

What is the purpose of the pressure gauge on the test port in a gas supply system?

To monitor fuel pressure

What is the primary function of the fuel pressure regulator in a gas supply system?

To regulate fuel pressure

What type of pipe is typically used for gas piping in a gas supply system?

Steel pipe

Which of the following codes is applicable to natural gas and propane burners installed on appliances for which no approval standard exists?

CSA B149.3

What is the main difference between the fuel train in Figure 1 and other fuel trains in the PanGlobal Fourth Class text?

Code requirements

What is the minimum input required for a boiler to be suitable for the fuel train configuration in Figure 1?

3.663 MW

Why is it important for Fourth Class Power Engineers to be familiar with the fuel train in Figure 1?

They will be serving as Shift Engineers and Assistant Shift Engineers in Third and Second Class plants

What is the significance of the CSA B149.3 Code in Canada?

It takes precedence over international codes

What is the main purpose of the codes published by organizations such as CSA, ASME, and NFPA?

To ensure combustion safety

Which of the following codes is similar to the CSA B149.3 Code?

ASME CSD-1

What is the main difference between the fuel train in Figure 1 and other fuel trains in terms of fuel pressure?

The fuel pressure is higher in Figure 1

What is the primary function of the Safety Vent Valve in a fuel train?

To bleed trapped fuel to the atmosphere when the main SSOVs shut

What is the purpose of the proof-of-closure switches on the main SSOVs?

To prevent the boiler from proceeding with an ignition sequence if an SSOV does not fully close

Why is the firing rate control valve located downstream of the low gas pressure cut-off switch?

To prevent the LGPCO from acting at low firing rates

What is the purpose of the test firing valves in a fuel train?

To test the operation of the flame detection devices

What happens when the main SSOVs shut and the safety vent valve fails open?

The trapped fuel is bled to the atmosphere

Why are pilot SSOVs usually fast-acting automatic solenoid valves?

Because they are used to shut off the fuel flow to the pilot burner during unsafe conditions

What is the purpose of the fuel pressure test ports in a fuel train?

To connect instruments to check, adjust, or monitor the fuel pressure

Under what conditions do Main SSOVs shut off the fuel flow to the main burner?

When the fuel pressure is low or the water level is low

What is the function of the Input Flow Control Valve in a fuel train?

To control fuel flow to the main burner in accordance with the load demand

What is the purpose of the pilot safety shut-off valves in a fuel train?

To shut off the fuel flow to the pilot burner during unsafe conditions or normal pilot interruption

Which code would be used to design a fuel train for a boiler with an input of 12,000,000 Btu/h?

CSA B149.3

Why are certified burners upgraded or modified, according to CSA B149.3?

To comply with existing codes

What is the primary reason for the differences in fuel train configurations between Figure 1 and other fuel trains in the PanGlobal Fourth Class text?

Different codes and standards

Which organization publishes codes that take precedence over international codes in Canada?

CSA

What is the minimum input requirement for a boiler to be suitable for the fuel train configuration in Figure 1?

3.663 MW

Why is it essential for Fourth Class Power Engineers to be familiar with the fuel train in Figure 1?

They serve as Shift Engineers and Assistant Shift Engineers in Third and Second Class plants

Which code covers natural gas and propane burners installed on appliances for which no approval standard exists?

CSA B149.3

What is the primary purpose of the CSA B149.3 Code?

To cover natural gas and propane burners installed on appliances for which no approval standard exists

What is the purpose of the safety vent valve?

To bleed trapped fuel to the atmosphere when the main SSOVs shut

What is the purpose of the proof-of-closure switches on the main SSOVs?

To prevent the boiler from proceeding with an ignition sequence if an SSOV does not fully close

Why is the firing rate control valve located downstream of the low gas pressure cut-off switch?

To prevent the LGPCO from actuating at low firing rates

What is the purpose of the pilot safety shut-off valves?

To shut off the fuel flow to the pilot burner under unsafe conditions

What is the purpose of the fuel pressure test ports?

To check, adjust, or monitor the fuel pressure

What happens when the main SSOVs shut and the safety vent valve fails open?

Trapped fuel is bled to the atmosphere

Why are proof-of-closure switches required on the main SSOVs?

To prevent the boiler from proceeding with an ignition sequence if an SSOV does not fully close

What is the purpose of the input flow control valve?

To control fuel flow in accordance with the load demand

What is the function of the test firing valves?

To test the operation of the flame detection devices

What prevents the boiler from proceeding with an ignition sequence if an SSOV does not fully close?

The proof-of-closure switches

What is the primary purpose of the fuel filter in an oil burner?

To remove contaminants from the fuel

What is the function of the low oil temperature cut-off switch?

To prevent the burner from starting when the fuel oil temperature falls below the recommended range

What is the purpose of the pressure relief valve in the fuel oil train?

To divert excessive fuel pressure back to the oil tank or suction line

What is the consequence of poor atomization in an oil burner?

Creation of toxic and explosive carbon monoxide

What is the function of the safety shut-off valves in the fuel oil train?

To stop the flow of oil to the burner when operating limits are reached or under adverse combustion conditions

What is the purpose of the test ports in the fuel oil train?

To install pressure gauges or electronic instruments to monitor fuel pressure conditions

What is the function of the fuel pump in the fuel oil train?

To provide the necessary flow and pressure for proper atomization at the maximum firing rate

What is the purpose of the low atomizing media cut-off switch?

To prevent the burner from starting when the atomizing media pressure falls below the manufacturer's design pressure

What code covers all automatically fired heating and power boilers up to 3.663 MW input?

ASME CSD-1

What is the purpose of the pressure gauge installed at the test port?

To monitor the fuel pressure conditions

What is the primary reason for the installation of a low gas pressure safety device in a gas supply system?

To shut off the supply of gas if the pressure at the point of connection drops below 50% of the lowest normal operating pressure

What is the purpose of the pressure gauge installed at the test port of a gas pressure cut-off switch?

To monitor the pressure while the burner is in operation

What is the consequence of a failure of the pressure regulator to reduce the fuel pressure in a gas supply system?

The burner piping components may over-pressurize and fail

What is the purpose of the main manual shut-off valve in a gas supply system?

To serve as an isolation point for fuel train maintenance

What is the requirement for the certification of main fuel safety shut-off valves in a gas supply system?

CSA 6.5-2015 Automatic Valves for Gas Appliances

What is the purpose of the fuel strainer in a gas supply system?

To catch debris before it can affect the operation of fuel pressure regulators and control valves

What is the consequence of excessive fuel pressure in a gas supply system?

Over-firing and flame instability

What is the location of the high gas pressure cut-off switch in a gas supply system?

Downstream of the pressure regulator and upstream of the flow control valve

What is the purpose of the pressure relief valve in a gas supply system?

To protect the pilot and main burner controls from excessive fuel pressure

What is the requirement for the installation of a high gas pressure safety device in a gas supply system?

Where the failure of the pressure regulator results in unsafe operation

Study Notes

Burner Systems and Components

  • Burner systems comprise various components that work together to ensure combustion safety, with each component serving a critical safety role.
  • The CSA B149.3 code serves as a guideline for the layout of combustion safety components, especially those found on boilers.

Gas Supply and Piping

  • Burners require fuel at the correct pressure, and fuel piping must be properly sized to deliver the required amount of fuel without excessive pressure drop.
  • Gas piping is typically constructed of steel pipe, with smaller diameters using threaded connections and larger diameters using welded connections.

Fuel Train Components

  • Main and Pilot Manual Shut-Off Valves (A and K): serve as isolation points for fuel train maintenance and can be used to test the operation of the low gas pressure cut-off switch.
  • Fuel Strainer (B): catches debris introduced during fuel line modifications to prevent negative effects on fuel pressure regulators and control valves.
  • Fuel Pressure Regulators (C): ensure proper fuel pressure at each burner, as excessive pressure can lead to overfiring and inadequate pressure can lead to flame instability.
  • Pressure Relief Valves (D): protect burner piping components from excessive fuel pressure.
  • Low (PSLL) and High (PSHH) Gas Pressure Cut-off Switches (E and H): shut down the burner if fuel pressure rises above or drops below the required level.

Main Fuel Safety Shut-Off Valves (F)

  • SSOVs prevent the accumulation of explosive fuel-air mixtures in furnaces when not in operation.
  • These valves must be certified to CSA 6.5 and can be slow-opening diaphragm, solenoid, or Hydramotor valves.

Safety Vent Valve (G)

  • Located between main fuel SSOVs, safety vent valves are typically fast-acting, normally-open solenoid valves.
  • They bleed trapped fuel to the atmosphere when the main SSOVs shut, reducing fuel pressure to atmospheric.

Input Flow Control Valve (I)

  • Fully modulating burners require fuel control to match load demand.
  • The input flow control valve is placed downstream of the low gas pressure cut-off switch to permit correct operation of other safety controls.

Main Test Firing and Pilot Test Firing Valves (J and M)

  • Used to test the operation of flame detection devices and high fuel pressure cut-off.
  • The main test firing valve is often used as a fuel train isolation point.

Pilot Safety Shut-Off Valves (L)

  • Shut off fuel flow to the pilot burner under certain circumstances, such as flame failure or normal pilot interruption.

Fuel Pressure Test Ports (N)

  • Located at various points on the fuel train, these ports allow instruments to be connected to check, adjust, or monitor fuel pressure.

Fuel Oil Trains

  • Function similarly to natural gas fuel trains, with components including pressure regulators, pressure relief valves, and low fuel pressure cut-off switches.
  • Unique components include fuel filters, fuel pumps, low oil temperature cut-off switches, and low atomizing media cut-off switches.

Fuel Filter

  • Essential for oil burners to protect against contaminants that can affect atomization and lead to poor combustion and toxic emissions.

Fuel Pump

  • Required to provide necessary flow and pressure for proper atomization at the maximum firing rate.

Low Oil Temperature Cut-off Switch

  • Stops fuel flow to a burner that fires oil requiring preheating, as poor atomization can lead to incomplete combustion and toxic emissions.

Low Atomizing Media Cut-Off Switch

  • Supervises atomizing media pressure for burners designed to use atomizing air or steam, causing safety shutdown and lockout if pressure falls below the manufacturer's design pressure.

Burner Systems and Components

  • Burner systems comprise various components that work together to ensure combustion safety, with each component serving a critical safety role.
  • The CSA B149.3 code serves as a guideline for the layout of combustion safety components, especially those found on boilers.

Gas Supply and Piping

  • Burners require fuel at the correct pressure, and fuel piping must be properly sized to deliver the required amount of fuel without excessive pressure drop.
  • Gas piping is typically constructed of steel pipe, with smaller diameters using threaded connections and larger diameters using welded connections.

Fuel Train Components

  • Main and Pilot Manual Shut-Off Valves (A and K): serve as isolation points for fuel train maintenance and can be used to test the operation of the low gas pressure cut-off switch.
  • Fuel Strainer (B): catches debris introduced during fuel line modifications to prevent negative effects on fuel pressure regulators and control valves.
  • Fuel Pressure Regulators (C): ensure proper fuel pressure at each burner, as excessive pressure can lead to overfiring and inadequate pressure can lead to flame instability.
  • Pressure Relief Valves (D): protect burner piping components from excessive fuel pressure.
  • Low (PSLL) and High (PSHH) Gas Pressure Cut-off Switches (E and H): shut down the burner if fuel pressure rises above or drops below the required level.

Main Fuel Safety Shut-Off Valves (F)

  • SSOVs prevent the accumulation of explosive fuel-air mixtures in furnaces when not in operation.
  • These valves must be certified to CSA 6.5 and can be slow-opening diaphragm, solenoid, or Hydramotor valves.

Safety Vent Valve (G)

  • Located between main fuel SSOVs, safety vent valves are typically fast-acting, normally-open solenoid valves.
  • They bleed trapped fuel to the atmosphere when the main SSOVs shut, reducing fuel pressure to atmospheric.

Input Flow Control Valve (I)

  • Fully modulating burners require fuel control to match load demand.
  • The input flow control valve is placed downstream of the low gas pressure cut-off switch to permit correct operation of other safety controls.

Main Test Firing and Pilot Test Firing Valves (J and M)

  • Used to test the operation of flame detection devices and high fuel pressure cut-off.
  • The main test firing valve is often used as a fuel train isolation point.

Pilot Safety Shut-Off Valves (L)

  • Shut off fuel flow to the pilot burner under certain circumstances, such as flame failure or normal pilot interruption.

Fuel Pressure Test Ports (N)

  • Located at various points on the fuel train, these ports allow instruments to be connected to check, adjust, or monitor fuel pressure.

Fuel Oil Trains

  • Function similarly to natural gas fuel trains, with components including pressure regulators, pressure relief valves, and low fuel pressure cut-off switches.
  • Unique components include fuel filters, fuel pumps, low oil temperature cut-off switches, and low atomizing media cut-off switches.

Fuel Filter

  • Essential for oil burners to protect against contaminants that can affect atomization and lead to poor combustion and toxic emissions.

Fuel Pump

  • Required to provide necessary flow and pressure for proper atomization at the maximum firing rate.

Low Oil Temperature Cut-off Switch

  • Stops fuel flow to a burner that fires oil requiring preheating, as poor atomization can lead to incomplete combustion and toxic emissions.

Low Atomizing Media Cut-Off Switch

  • Supervises atomizing media pressure for burners designed to use atomizing air or steam, causing safety shutdown and lockout if pressure falls below the manufacturer's design pressure.

Burner Systems and Components

  • Burner systems comprise various components that work together to ensure combustion safety, with each component serving a critical safety role.
  • The CSA B149.3 code serves as a guideline for the layout of combustion safety components, especially those found on boilers.

Gas Supply and Piping

  • Burners require fuel at the correct pressure, and fuel piping must be properly sized to deliver the required amount of fuel without excessive pressure drop.
  • Gas piping is typically constructed of steel pipe, with smaller diameters using threaded connections and larger diameters using welded connections.

Fuel Train Components

  • Main and Pilot Manual Shut-Off Valves (A and K): serve as isolation points for fuel train maintenance and can be used to test the operation of the low gas pressure cut-off switch.
  • Fuel Strainer (B): catches debris introduced during fuel line modifications to prevent negative effects on fuel pressure regulators and control valves.
  • Fuel Pressure Regulators (C): ensure proper fuel pressure at each burner, as excessive pressure can lead to overfiring and inadequate pressure can lead to flame instability.
  • Pressure Relief Valves (D): protect burner piping components from excessive fuel pressure.
  • Low (PSLL) and High (PSHH) Gas Pressure Cut-off Switches (E and H): shut down the burner if fuel pressure rises above or drops below the required level.

Main Fuel Safety Shut-Off Valves (F)

  • SSOVs prevent the accumulation of explosive fuel-air mixtures in furnaces when not in operation.
  • These valves must be certified to CSA 6.5 and can be slow-opening diaphragm, solenoid, or Hydramotor valves.

Safety Vent Valve (G)

  • Located between main fuel SSOVs, safety vent valves are typically fast-acting, normally-open solenoid valves.
  • They bleed trapped fuel to the atmosphere when the main SSOVs shut, reducing fuel pressure to atmospheric.

Input Flow Control Valve (I)

  • Fully modulating burners require fuel control to match load demand.
  • The input flow control valve is placed downstream of the low gas pressure cut-off switch to permit correct operation of other safety controls.

Main Test Firing and Pilot Test Firing Valves (J and M)

  • Used to test the operation of flame detection devices and high fuel pressure cut-off.
  • The main test firing valve is often used as a fuel train isolation point.

Pilot Safety Shut-Off Valves (L)

  • Shut off fuel flow to the pilot burner under certain circumstances, such as flame failure or normal pilot interruption.

Fuel Pressure Test Ports (N)

  • Located at various points on the fuel train, these ports allow instruments to be connected to check, adjust, or monitor fuel pressure.

Fuel Oil Trains

  • Function similarly to natural gas fuel trains, with components including pressure regulators, pressure relief valves, and low fuel pressure cut-off switches.
  • Unique components include fuel filters, fuel pumps, low oil temperature cut-off switches, and low atomizing media cut-off switches.

Fuel Filter

  • Essential for oil burners to protect against contaminants that can affect atomization and lead to poor combustion and toxic emissions.

Fuel Pump

  • Required to provide necessary flow and pressure for proper atomization at the maximum firing rate.

Low Oil Temperature Cut-off Switch

  • Stops fuel flow to a burner that fires oil requiring preheating, as poor atomization can lead to incomplete combustion and toxic emissions.

Low Atomizing Media Cut-Off Switch

  • Supervises atomizing media pressure for burners designed to use atomizing air or steam, causing safety shutdown and lockout if pressure falls below the manufacturer's design pressure.

Understanding the components of burner systems and their role in ensuring combustion safety, as well as the importance of proper gas supply and piping.

Make Your Own Quizzes and Flashcards

Convert your notes into interactive study material.

Get started for free

More Quizzes Like This

Quiz da Revolução Industrial
3 questions
Industrial Automation Commands
29 questions

Industrial Automation Commands

NoteworthyGadolinium2944 avatar
NoteworthyGadolinium2944
4BE3.5 U3 C2 Obj 4 Easy Medium Hard
78 questions
Use Quizgecko on...
Browser
Browser