What is the minimum capacity of the charger in a DC power plant system?

C/10 + load

What type of enclosure can be used for an AC Distribution Board?

Wall mounted metallic enclosure

What is the purpose of Integrated Surge & Transient Protection Devices in an AC Distribution Rack?

To protect sensitive Telecom Equipments from surges and transients

What is the requirement for terminating incoming AC Power Supply on an AC Distribution Board?

Through MCCBs & MCBs of adequate capacity

What is the purpose of having a spare capacity in an AC Distribution Board?

To accommodate anticipated future expansion

What is the requirement for new installations of AC Power Supply Distribution for Telecom Equipments?

Follow the guidelines stipulated in the manual

What is the function of an Automatic Changeover in an AC Power Supply Distribution?

To changeover from one incoming source to other

What is the requirement for the capacity of Battery Chargers in a DC Power Plant System?

Float cum boost charger of adequate capacity in N+1 or N+2

What is the recommended frequency for measuring the voltage and load current of a power supply system?

Weekly

What is the purpose of measuring the specific gravity of a battery?

To monitor the battery's state of charge

Who is responsible for cleaning and tightening the connections of a battery?

Telecom Technician

What is the frequency of checking the lubricant of a generator?

Fortnightly

What is the purpose of cleaning a solar panel?

To increase its efficiency

Who is responsible for measuring the terminal voltage of a solar panel?

Telecom Technician

What is the recommended frequency for tightening the connections of a battery charger?

Monthly

What is the purpose of measuring the cell voltage of a battery?

To monitor its state of charge

What should be used to connect positive and negative terminals of a battery?

Red and blue wire

What is essential to maintain in the battery room?

Good ventilation and cleanliness

What should be provided in the battery room to prevent corrosion?

Pure vaseline or petroleum jelly

How should connecting cables be maintained in a battery room?

By keeping them flexible and long

What should be used to lubricate electrical connections?

Pure vaseline

Why should nuts be used in battery connections?

To maintain firm connections

What should be used to top up the electrolyte level in LMLA Battery sets?

Distilled water

What should be maintained in power equipment?

Voltage and load current records

Which Telecommunication Equipment operates on 230 V AC Power Supply?

Public Address System

What type of power supply is required for Train Traffic Control Equipment?

12/24/48 V DC

Which of the following equipment operates on 48 V DC Power Supply?

Train Radio System

What is the recommendation for powering multiple systems in the same room or adjacent rooms of the same building?

Use a common power plant for all systems

Which of the following is NOT a characteristic of a reliable Power Supply for Telecom Equipments?

Low voltage

What is the typical voltage requirement for Datacom Equipment of PRS, FOIS, UTS etc?

230 V AC

Which of the following is a consideration for designing a Power Supply Room for Telecom Equipments?

All of the above

What is the importance of remote monitoring and control systems in Power Plant Systems for Telecom Installations?

To improve system reliability

Where should the incoming DC Power Supply be terminated?

In a DC Distribution Board

What is the purpose of the DC MCBs in the DC Distribution Board?

To terminate the outgoing DC Power Supply for individual Telecom Equipment

What is a desirable feature for the windows in the Power Supply Room?

Frosted or painted windows to prevent direct sun rays

What is a requirement for the Power Supply Room where secondary batteries are installed?

All of the above

What should be provided to remove fumes in all Power Supply Rooms where secondary batteries are installed?

Exhaust fans

Why should all cable entry points be rodent proof?

To prevent damage to the cables

What is a requirement for the DC Distribution Board?

It should have sufficient spare capacity to accommodate anticipated future expansion

Where should the stabilizers, chargers, distribution boards, and changeover switches be installed when VRLA batteries are used?

In the same room as the VRLA batteries

What should be provided in the battery room to prevent corrosion?

A ventilation system

How should connecting cables be maintained in a battery room?

By keeping them clean and dry

What is essential to maintain in the battery room?

A clean and dry environment

What should be used to lubricate electrical connections?

Grease

What should be maintained in power equipment?

Cleanliness

How often should the lubricant of a generator be checked?

Periodically as per manufacturer's recommendation

What should be done to the power equipment?

Cleaned with a blower

What should be maintained in the diesel generator set?

The no-load and on-load voltages of the alternator

When should electrolyte of proper specific gravity be added to cells?

In fully charged condition and after sufficient time has been allowed to cool down the cells to room temperature

What is the purpose of testing each cell as per maintenance schedule?

To check the voltage and specific gravity of the cell

What should be done to prevent corrosion in the battery room?

Provide a ventilation system

How should electrolyte be added to a cell?

Gradually in minimum quantity

What should be recorded in the battery history card?

Test results and maintenance schedule

What is the purpose of maintaining records of interruptions of main power supply and utilisation of the DG set?

To analyze the monthly report and take follow-up action

What should be done to maintain the connecting cables in a battery room?

Clean and tighten the connections regularly

Who is responsible for analyzing the monthly report and taking follow-up action?

Sr.DSTE/Dy.CSTE(Tele)

What should be provided in the battery room to prevent corrosion?

Pure Vaseline or Petroleum Jelly

What should be maintained in the battery room?

Cleanliness and Ventilation

How should connecting cables be maintained in a battery room?

They should be flexible and sufficiently long

What should be used to top up the electrolyte level in LMLA Battery sets?

Distilled Water

What should be used to connect positive and negative terminals of a battery?

Red and Blue wires

What should be maintained in power equipment?

Voltage and Load Current

Why should nuts be used in battery connections?

To maintain firm connections

What is essential to maintain in the battery room?

Cleanliness and Ventilation

What is the recommended frequency for measuring the voltage and load current of a power supply system?

Weekly

Who is responsible for cleaning and tightening the connections of a battery?

Telecom Technician

What should be maintained in the battery room to prevent corrosion?

Cleanliness and dryness

What should be used to lubricate electrical connections?

Silicone-based lubricant

Why should nuts be used in battery connections?

To prevent corrosion

What should be used to top up the electrolyte level in LMLA Battery sets?

Distilled water

What should be maintained in power equipment?

All of the above

How should connecting cables be maintained in a battery room?

They should be kept clean and dry

What is the recommended frequency for checking the lubricant of a generator?

Before every engine start

What should be used to connect positive and negative terminals of a battery?

Insulated connectors

What is essential to maintain in the battery room?

Cleanliness and dryness

What should be used to top up the electrolyte level in LMLA Battery sets?

Distilled water

What should be maintained in power equipment?

Desired lubricant levels

Why should all cable entry points be rodent proof?

To prevent rodent damage

What should be provided to remove fumes in all Power Supply Rooms where secondary batteries are installed?

Ventilation system

What is a desirable feature for the windows in the Power Supply Room?

Small size to prevent heat gain

Study Notes

AC Power Supply Distribution Arrangements

  • Existing installations will continue with existing arrangements of AC Power Supply Distribution for Telecom Equipments.
  • New installations shall follow the guidelines stipulated in the manual.
  • Incoming AC Power Supply from various sources (AT Transformer, Local Power Supply, Diesel Generator Power Supply, Solar Panel Power Supply) shall be terminated in an AC Distribution Board.
  • The AC Distribution Board shall have a facility of changeover from one incoming source to another.
  • Incoming AC Power Supply on the AC Distribution Board shall be terminated through MCCBs & MCBs of adequate capacity.
  • Outgoing Single Phase AC Power Supply for individual Telecom Equipment from the AC Distribution Board shall be through MCBs of adequate capacity.
  • Integrated Surge & Transient Protection Devices shall be provided in the AC Distribution Rack for sensitive Telecom Equipments.
  • AC Distribution Board shall have sufficient spare capacity to accommodate anticipated future expansion.

DC Power Plant System

  • Battery Chargers and Voltage Stabilizers shall be provided in all Telecom installations.
  • Charger capacity should be minimum C/10 + load, where C is the AH of the battery.
  • DC Distribution Board can be “wall mounted metallic enclosure” or “floor mounted cubicle”.
  • Incoming DC Power Supply shall be terminated in the DC Distribution Board.
  • Incoming DC Power Supply on the DC Distribution Board shall be terminated through DC MCB of adequate capacity.
  • Outgoing DC Power Supply for individual Telecom Equipment from the DC Distribution Board shall be through DC MCBs of adequate capacity.
  • DC Distribution Board shall have sufficient spare capacity to accommodate anticipated future expansion.

Requirement of Power Supply Room(s)

  • Power Supply Room(s) shall be dry, cool, well lighted, and well ventilated.
  • Exhaust fans shall be provided to remove fumes in all Power Supply Rooms where secondary batteries are installed.
  • It is desirable that window glasses shall be frosted or painted wherever necessary to prevent direct sun rays falling on the cells.
  • Power Supply Room(s) shall have a water sink and universal (5A & 15A) electric power plug for connection to the hand lamp.
  • The Power Supply Room(s) where secondary batteries are installed shall be provided with acid-resistant tiles on the floor and the walls up to 1.5 M.
  • A thermometer to measure the room temperature should also be kept in the battery room.
  • All cable entry points should be rodent-proof.

Maintenance of Secondary Cells

  • Cable to connect battery terminals and load should use proper color code of wires.
  • The battery room shall be kept well ventilated, free from water, oil, and dust.
  • Surroundings of batteries shall be kept clean.
  • Acid-proof reusable hand gloves and Hydrometer to be provided.
  • Hydrometer should be kept on a Wall Mounted Stand in the Battery Room.
  • Connecting cables shall be flexible and sufficiently long to prevent strain on the battery terminals.
  • Connecting lugs shall be fitted to battery posts/terminals by using suitable nuts/bolts & tightened by using flat and spring/serrated washers.
  • Lugs at the end of conductors, utilized for making connections, shall be crimped and/or brazed.
  • The electrical connections shall always be kept tight.
  • Check nuts should also be used to maintain firm connections.
  • The terminals and connections of battery cells shall be coated with pure vaseline or petroleum jelly to prevent corrosion.

Power Supply Systems for Telecom Installations

  • This chapter discusses the power supply requirements for various Telecommunication Equipments.
  • All Telecom Equipments shall be provided with a reliable Power Supply.
  • Telecom System/Equipments like Public Address System, Passenger Information Display System, Wifi equipment, Video Surveillance System (Close Circuit TeleVision), Centralised Clock System, Voice Logging Equipments, Railnet, Video conference equipment, Datacom Equipment of PRS, FOIS, UTS, etc. operates on 230 V AC Power Supply.
  • Telecom System/Equipments like Train Radio System, Optic Fibre Equipment, Multiplexing Equipments, Telephone Exchanges, etc. operates on 48 V DC Power Supply.
  • Train Traffic Control Equipment operates on 12/24/48 V DC. VOIP based TTC may work on standard AC power supply (230 V AC) too. Datacom Equipment of SCADA operates on 48/110 V DC or 230V AC.

Diesel Generator Set Maintenance

  • Lubricating oil shall be changed periodically as per the manufacturer's data for engine hour run.
  • Diesel generator sets shall be overhauled in accordance with the manufacturer's recommendation.
  • Checking and cleaning of parts shall be done once in every three months or as the situation warrants.
  • It is preferable to have them overhauled by the manufacturer or their authorized representative.
  • Automatic Starting Device shall be tested periodically for effective starting during power failures and low voltage conditions.
  • The no-load and on-load voltages of the alternator shall be maintained within limits and the Governor adjusted during periodic maintenance to the RPM specified and a steady output of 50Hz.
  • The DG set shall run for 5-10 minutes on load to verify its proper working during periodic maintenance check.
  • A log book shall be maintained at every location, which shall bear the history of performance and maintenance of Diesel Generator Set together with the signatures of the maintainers and SSE(Telecom).

Maintenance of Power Supply System

  • The working of battery charger shall be checked for proper working of switches, fuses, etc.
  • Power equipment shall be cleaned by a blower or any other device to remove dust.
  • Battery Measurement & Maintenance:
    • Cell Number
    • Date
    • Parameter (Cell Voltage, Specific Gravity)
    • Work done & remarks
    • Signature & Designation

Maintenance Schedule for Power Supply System

  • Battery:
    • Cleaning of all connections: Fortnightly
    • Tightening of all connections: Monthly
    • Checking of working: Weekly
    • Measurement of voltages & load current: Weekly
  • Chargers:
    • Cleaning of all connections: Fortnightly
    • Tightening of all connections: Monthly
    • Checking of working: Weekly
    • Measurement of voltages & load current: Weekly

Maintenance of Solar Panel

  • Cleaning of Solar panel: Fortnightly
  • Measurement of terminal voltage of solar panel: Fortnightly
  • Measurement of current of solar panel: Fortnightly

Electrolyte Maintenance

  • Electrolyte loss due to spillage shall be replenished with proper amount of electrolyte of the same specific gravity as that of remaining electrolyte in the cell.
  • Electrolyte shall not be added under any other circumstances.
  • Each cell shall be tested as per maintenance schedule so that its voltage and specific gravity are within specified limits.

Records and Reports

  • The inspector in-charge of Telecom Installation and remote control centre shall arrange to maintain:
    • Record of interruptions of main power supply and utilisation of the DG set with details of each duration.
    • Record of supply and utilisation of diesel fuel.
    • Prepare monthly interruption reports of mains supply/upkeep/utilisation of DG set and send to Sr.DSTE/Dy.CSTE(Tele).
  • Sr.DSTE/Dy.CSTE(Tele) shall analyse the monthly report and take follow-up action with concerned divisional officers as to minimise the interruption of the main power supply.

Remote Monitoring and Control System

  • The arrangement shall be approved by PCSTE of the Railway.
  • It shall have the following features:
    • Facility of remote monitoring and control of the power plant systems.
    • Provide vital alarms to the remote monitoring system through NMS / Data Logger/ Mobile app/software using mobile communication facilities etc.
    • The control system shall be capable of accepting and reacting to following vital commands from the remote monitoring centre.