What is the maximum interval for testing a device inaccessible due to excessive height?
What is the maximum interval for testing a device inaccessible due to excessive height?
18 months
What is the acceptable maximum mounting height from the floor for a wall-mounted fire telephone appliance?
What is the acceptable maximum mounting height from the floor for a wall-mounted fire telephone appliance?
66 inches
Elevator lobby smoke detectors shall be mounted within a maximum distance of?
Elevator lobby smoke detectors shall be mounted within a maximum distance of?
21 feet
What is the minimum distance an aerial lift operator shall maintain from power lines with voltage of 600 volts and lower?
What is the minimum distance an aerial lift operator shall maintain from power lines with voltage of 600 volts and lower?
Signup and view all the answers
Under what condition shall the use of unprotected EMT be permitted?
Under what condition shall the use of unprotected EMT be permitted?
Signup and view all the answers
According to NFPA 70, what is the maximum unsupported length of 1/2-inch flexible metallic conduit?
According to NFPA 70, what is the maximum unsupported length of 1/2-inch flexible metallic conduit?
Signup and view all the answers
What is the maximum bend (in degrees) permitted in a conduit run between outlet boxes?
What is the maximum bend (in degrees) permitted in a conduit run between outlet boxes?
Signup and view all the answers
What is the minimum acceptable time for secondary power to operate the voice evacuation systems when the primary power is disconnected?
What is the minimum acceptable time for secondary power to operate the voice evacuation systems when the primary power is disconnected?
Signup and view all the answers
A riser room temperature switch should activate when the temperature falls below which level?
A riser room temperature switch should activate when the temperature falls below which level?
Signup and view all the answers
According to NFPA 72, what is the maximum sound pressure level permitted in a space with notification appliances?
According to NFPA 72, what is the maximum sound pressure level permitted in a space with notification appliances?
Signup and view all the answers
What is the minimum interval for testing a single-station smoke detector in multifamily units?
What is the minimum interval for testing a single-station smoke detector in multifamily units?
Signup and view all the answers
Where should a technician install a detector in relation to a beam that is less than 12 inches deep?
Where should a technician install a detector in relation to a beam that is less than 12 inches deep?
Signup and view all the answers
Where should an existing fire alarm cable in a drop ceiling be spliced to comply with NFPA 70?
Where should an existing fire alarm cable in a drop ceiling be spliced to comply with NFPA 70?
Signup and view all the answers
What function shall be tested for each newly installed smoke detector?
What function shall be tested for each newly installed smoke detector?
Signup and view all the answers
How many heat detectors are required in an 180-foot long corridor with a smooth 10-foot ceiling?
How many heat detectors are required in an 180-foot long corridor with a smooth 10-foot ceiling?
Signup and view all the answers
At what height must cables be physically protected when being installed within an exposed ceiling?
At what height must cables be physically protected when being installed within an exposed ceiling?
Signup and view all the answers
When shall smoke detectors be installed during the construction process?
When shall smoke detectors be installed during the construction process?
Signup and view all the answers
What is the maximum distance intermediate metal conduit shall be secured from an outlet box?
What is the maximum distance intermediate metal conduit shall be secured from an outlet box?
Signup and view all the answers
The requirement forbidding fire alarm circuits from being T-tapped is intended to prevent which type of malfunction?
The requirement forbidding fire alarm circuits from being T-tapped is intended to prevent which type of malfunction?
Signup and view all the answers
What is the maximum operating temperature of TW insulation?
What is the maximum operating temperature of TW insulation?
Signup and view all the answers
Which type of meter is used to measure the current draw of a strobe circuit?
Which type of meter is used to measure the current draw of a strobe circuit?
Signup and view all the answers
What is an acceptable document for finding information on spacing of video imaging smoke detection systems?
What is an acceptable document for finding information on spacing of video imaging smoke detection systems?
Signup and view all the answers
When pulling multiple cables through a junction box, what is the minimum length of wire an installer must leave for splicing?
When pulling multiple cables through a junction box, what is the minimum length of wire an installer must leave for splicing?
Signup and view all the answers
Which three of the following conditions are symptoms of a heart attack? (Select all that apply)
Which three of the following conditions are symptoms of a heart attack? (Select all that apply)
Signup and view all the answers
To what water temperature should sprinkler water storage containers be supervised to indicate?
To what water temperature should sprinkler water storage containers be supervised to indicate?
Signup and view all the answers
According to NFPA 72, what is the minimum separation between outgoing and returning conductors for a Class A loop that is horizontally placed down an 8-foot-wide corridor?
According to NFPA 72, what is the minimum separation between outgoing and returning conductors for a Class A loop that is horizontally placed down an 8-foot-wide corridor?
Signup and view all the answers
According to NFPA 72, what is the minimum time period that a public emergency alarm reporting system shall operate its emergency power source?
According to NFPA 72, what is the minimum time period that a public emergency alarm reporting system shall operate its emergency power source?
Signup and view all the answers
Where shall employers post a safety data sheet?
Where shall employers post a safety data sheet?
Signup and view all the answers
During an acceptance test, what method can be utilized for testing a sprinkler waterflow switch?
During an acceptance test, what method can be utilized for testing a sprinkler waterflow switch?
Signup and view all the answers
When technicians are working in a plant, where should they learn about the plant's safety regulations?
When technicians are working in a plant, where should they learn about the plant's safety regulations?
Signup and view all the answers
Where is at least one telephone or jack required to be installed in a fire communication system?
Where is at least one telephone or jack required to be installed in a fire communication system?
Signup and view all the answers
Who is responsible for fire alarm system testing and maintenance?
Who is responsible for fire alarm system testing and maintenance?
Signup and view all the answers
In a protected premises with a 40-foot long by 15-foot wide room having a smooth ceiling, what is the minimum quantity of smoke detectors that shall be required?
In a protected premises with a 40-foot long by 15-foot wide room having a smooth ceiling, what is the minimum quantity of smoke detectors that shall be required?
Signup and view all the answers
What is the correct way to connect a meter to measure a horn strobe circuit current draw?
What is the correct way to connect a meter to measure a horn strobe circuit current draw?
Signup and view all the answers
Which plans include fire detection system details?
Which plans include fire detection system details?
Signup and view all the answers
How many inches below the finished ceiling should wall-mounted audible signal appliances be mounted?
How many inches below the finished ceiling should wall-mounted audible signal appliances be mounted?
Signup and view all the answers
What is the recommended first step in treating a suspected leg fracture?
What is the recommended first step in treating a suspected leg fracture?
Signup and view all the answers
How often shall alarm notification appliances be tested?
How often shall alarm notification appliances be tested?
Signup and view all the answers
When the outgoing and return conductors enter or exit notification circuits, how far can the conductors run in the same cable assembly?
When the outgoing and return conductors enter or exit notification circuits, how far can the conductors run in the same cable assembly?
Signup and view all the answers
Which part requires special handling or disposal?
Which part requires special handling or disposal?
Signup and view all the answers
What is the minimum acceptable size of conductors for multi-conductor cables?
What is the minimum acceptable size of conductors for multi-conductor cables?
Signup and view all the answers
Which type of detector is recommended for protecting atriums and similar open spaces?
Which type of detector is recommended for protecting atriums and similar open spaces?
Signup and view all the answers
Which type of fire alarm key blank must be used for a run installed in a plenum space?
Which type of fire alarm key blank must be used for a run installed in a plenum space?
Signup and view all the answers
What are the current courses of action if a technician notices that a step is missing from a ladder?
What are the current courses of action if a technician notices that a step is missing from a ladder?
Signup and view all the answers
What is the minimum size for EMT?
What is the minimum size for EMT?
Signup and view all the answers
What is the maximum size for EMT?
What is the maximum size for EMT?
Signup and view all the answers
How often must EMT be securely fastened in place?
How often must EMT be securely fastened in place?
Signup and view all the answers
What is the definition of a continuous load?
What is the definition of a continuous load?
Signup and view all the answers
What is ampacity?
What is ampacity?
Signup and view all the answers
What device provides protection from the effects of arc faults?
What device provides protection from the effects of arc faults?
Signup and view all the answers
What are the circuit conductors between the final overcurrent device protecting the circuit and the outlet(s)?
What are the circuit conductors between the final overcurrent device protecting the circuit and the outlet(s)?
Signup and view all the answers
What is overcurrent?
What is overcurrent?
Signup and view all the answers
What is the maximum height for initiating a pull box?
What is the maximum height for initiating a pull box?
Signup and view all the answers
How long shall a secondary power supply's capacitance last when primary power is off?
How long shall a secondary power supply's capacitance last when primary power is off?
Signup and view all the answers
What is the duration for a secondary power supply for in-building mass notification system (MNS)?
What is the duration for a secondary power supply for in-building mass notification system (MNS)?
Signup and view all the answers
What is the duration for a secondary power supply for in-building fire emergency voice/alarm communications?
What is the duration for a secondary power supply for in-building fire emergency voice/alarm communications?
Signup and view all the answers
Within what time frame shall trouble signals and their restoration to normal be indicated?
Within what time frame shall trouble signals and their restoration to normal be indicated?
Signup and view all the answers
Which circuit class is a fail-safe circuit?
Which circuit class is a fail-safe circuit?
Signup and view all the answers
Which circuit class is not monitored for integrity?
Which circuit class is not monitored for integrity?
Signup and view all the answers
How is a Class B circuit different from a Class A circuit?
How is a Class B circuit different from a Class A circuit?
Signup and view all the answers
Monitoring for integrity shall not be required for the interconnection between enclosures containing control equipment located within?
Monitoring for integrity shall not be required for the interconnection between enclosures containing control equipment located within?
Signup and view all the answers
What is the formula for calculating current (I) in terms of voltage (E) and resistance (R)?
What is the formula for calculating current (I) in terms of voltage (E) and resistance (R)?
Signup and view all the answers
What is the formula for calculating resistance (R) in terms of voltage (E) and current (I)?
What is the formula for calculating resistance (R) in terms of voltage (E) and current (I)?
Signup and view all the answers
What is the formula for calculating voltage (E) in terms of current (I) and resistance (R)?
What is the formula for calculating voltage (E) in terms of current (I) and resistance (R)?
Signup and view all the answers
What is K for copper at 167 degrees F?
What is K for copper at 167 degrees F?
Signup and view all the answers
What is K for aluminum at 167 degrees F?
What is K for aluminum at 167 degrees F?
Signup and view all the answers
What is the voltage drop formula for single-phase circuits?
What is the voltage drop formula for single-phase circuits?
Signup and view all the answers
What is the voltage drop formula for three-phase circuits?
What is the voltage drop formula for three-phase circuits?
Signup and view all the answers
What is the total current for a series circuit?
What is the total current for a series circuit?
Signup and view all the answers
What is the total voltage for a series circuit?
What is the total voltage for a series circuit?
Signup and view all the answers
What is the total resistance for a series circuit?
What is the total resistance for a series circuit?
Signup and view all the answers
What is the total current for a parallel circuit?
What is the total current for a parallel circuit?
Signup and view all the answers
What is the total voltage for a parallel circuit?
What is the total voltage for a parallel circuit?
Signup and view all the answers
What is the total resistance for parallel circuits?
What is the total resistance for parallel circuits?
Signup and view all the answers
What is the total resistance when current and voltage are unknown?
What is the total resistance when current and voltage are unknown?
Signup and view all the answers
What is the formula for total resistance of only 2 resistors in parallel?
What is the formula for total resistance of only 2 resistors in parallel?
Signup and view all the answers
What is the definition of a detector?
What is the definition of a detector?
Signup and view all the answers
What is beam construction?
What is beam construction?
Signup and view all the answers
How soon shall actuation of alarm notification appliances occur?
How soon shall actuation of alarm notification appliances occur?
Signup and view all the answers
How soon shall indication and restoring of self-restoring supervisory devices occur?
How soon shall indication and restoring of self-restoring supervisory devices occur?
Signup and view all the answers
What is the maximum air sample transport time from the farthest sampling port to the detector?
What is the maximum air sample transport time from the farthest sampling port to the detector?
Signup and view all the answers
What is the minimum distance between raceway entries inside the box?
What is the minimum distance between raceway entries inside the box?
Signup and view all the answers
What is the maximum distance vertical runs of a metal wireway shall be securely supported?
What is the maximum distance vertical runs of a metal wireway shall be securely supported?
Signup and view all the answers
What is the maximum distance a metal wireway shall be supported horizontally?
What is the maximum distance a metal wireway shall be supported horizontally?
Signup and view all the answers
What are Class 1 location hazards?
What are Class 1 location hazards?
Signup and view all the answers
What are Class 2 location hazards?
What are Class 2 location hazards?
Signup and view all the answers
What are Class 3 location hazards?
What are Class 3 location hazards?
Signup and view all the answers
What defines Class 1 Division 1?
What defines Class 1 Division 1?
Signup and view all the answers
What defines Class 1 Division 2?
What defines Class 1 Division 2?
Signup and view all the answers
What defines Class 2 Division 1?
What defines Class 2 Division 1?
Signup and view all the answers
What defines Class 2 Division 2?
What defines Class 2 Division 2?
Signup and view all the answers
What defines Class 3 Division 1?
What defines Class 3 Division 1?
Signup and view all the answers
What defines Class 3 Division 2?
What defines Class 3 Division 2?
Signup and view all the answers
What is Group A?
What is Group A?
Signup and view all the answers
What is Group B?
What is Group B?
Signup and view all the answers
What is Group C?
What is Group C?
Signup and view all the answers
What is Group D?
What is Group D?
Signup and view all the answers
What is Group F?
What is Group F?
Signup and view all the answers
What is Group G?
What is Group G?
Signup and view all the answers
Study Notes
Fire Alarm System Standards and Testing
- Devices must be tested at least every 18 months if inaccessible due to height.
- Wall-mounted fire telephone appliances should be mounted no higher than 66 inches.
- Elevator lobby smoke detectors must be placed within 21 feet of the door's center-line.
- Aerial lift operators need to keep a 10-foot distance from 600-volt power lines.
- Unprotected EMT is allowed only when in direct contact with the earth.
Conduit and Cable Regulations
- The maximum unsupported length of 1/2-inch flexible metallic conduit is 4 1/2 feet.
- A maximum bend of 360 degrees is permitted in conduit runs between boxes.
- Smoke detectors in multifamily units must be tested annually.
- Detectors in beam constructions (less than 12 inches deep) should be installed at the beam's bottom.
Electrical Connections and Safety
- Riser room temperature switches activate below 40°F.
- Notification appliances' maximum sound pressure level is limited to 110 dBA per NFPA 72.
- Installers must ensure at least 6 inches of wire for splicing when pulling multiple cables through junction boxes.
- After construction, smoke detectors should be installed following final clean-up.
Fire Detection and Emergency Power
- Secondary power must sustain voice evacuation systems for a minimum of 15 minutes during alarm conditions.
- Fire alarm circuits cannot be T-tapped unless specified by the manufacturer to maintain monitoring integrity.
- Sprinkler storage must be supervised to indicate water temperature drops below 40°F.
- Public emergency alarm systems require a minimum operational time of 10 minutes on emergency power.
Fire Alarm Components and Requirements
- Smoke detectors should be placed strategically to protect spaces adequately, with the minimum number specified depending on room size.
- A multimeter is utilized to measure current draw of strobe circuits.
- Fire alarm system maintenance and testing is the responsibility of the property owner.
Electrical Theory and Calculations
- Key electrical formulas include Ohm's Law: I (Amperes) = E (Voltage) / R (Resistance), and voltage drop calculations for single-phase: Vd = (2K x L x I) / Cm.
- Class A circuits provide redundancy; Class B circuits do not have a redundant path, stopping operational capability at a single open.
- Class D circuits are considered fail-safe, while Class E circuits are not monitored for integrity.
Hazardous Location Classifications
- Class 1 locations involve flammable gases and vapors, while Class 2 refers to combustible dust, and Class 3 includes easily ignitable fibers.
- Class Division designations specify additional conditions, such as the regular presence of hazardous materials due to operations or equipment failure.
Miscellaneous Regulations
- Fire alarm systems require components to be installed within specific height guidelines (e.g., initiating pull boxes at a maximum height of 48 inches).
- Proper handling of hazardous components like lead-acid batteries is crucial for safety.
- Understanding and adhering to these safety regulations significantly impacts the efficient and safe operation of fire alarm systems.