Questions and Answers

An approved central station company is one that has been issued a valid certificate from ____________.

FDNY

A _________ is the open space that carries air between the ceilings and floor above.

plenum

An _________ alarm is one which functioned as designed, but which department response is unnecessary.

unnecessary

An _________ alarm is the result of improper installation or maintenance.

<p>unwarranted</p> Signup and view all the answers

The new fire code was adopted in __________ and vastly changed the requirements for supervision of all fire alarm systems.

<p>July 2008</p> Signup and view all the answers

Duties that can be performed by an S-95 COF holder include ___________ only.

<p>visual inspections only</p> Signup and view all the answers

The primary purpose of a ____________ is to warn occupants and to transmit signals indicating fire to the FDNY.

<p>fire alarm system</p> Signup and view all the answers

The primary purpose of a ______________ is to process signals received from initiating devices and to activate appropriate signals.

<p>fire alarm control panel</p> Signup and view all the answers

A ___________ signal is initiated when a device indicates the presence of fire.

<p>fire alarm</p> Signup and view all the answers

A _________ signal indicates that a system or device being monitored is in an abnormal state.

<p>supervisory</p> Signup and view all the answers

A __________ signal indicates that the alarm system, transmitter, or communications path is wholly or partially out of service.

<p>trouble</p> Signup and view all the answers

Routine handling of trouble signals should take a maximum of ___________ minutes from receipt of trouble signal by central station until initial investigation by telephone.

<p>four</p> Signup and view all the answers

The FDNY is not dispatched to respond to _________ or ________ signals.

<p>supervisory, trouble</p> Signup and view all the answers

Do not silence the building ___________ and ________ device until the fire alarm condition is verified by FDNY personnel.

<p>audible, visual</p> Signup and view all the answers

Smoke detectors must be cleaned at least _____________ by an S-78, S-97, T-97, or S-98 COF holder.

<p>once every six months.</p> Signup and view all the answers

Any abnormal conditions must be investigated and noted in the ___________.

<p>logbook</p> Signup and view all the answers

The fire alarm primary power source shall be generated electric power not exceeding ____________ volts.

<p>277/480</p> Signup and view all the answers

__________ shall not be a substitute for connection to a secondary power source.

<p>Batteries</p> Signup and view all the answers

The NFPA defines accessibility as __________________.

<p>Admitting close approach: not guarded by locked doors, elevation, and other effective means.</p> Signup and view all the answers

When smoke detectors report the need for maintenance to the FACP, it must be cleaned within __________.

<p>1 week</p> Signup and view all the answers

Ionization detectors use an _______________ and a source of ionizing.

<p>ionization chamber</p> Signup and view all the answers

Ionization smoke detectors monitor ___________, or electrically charged particles in the air.

<p>ions</p> Signup and view all the answers

_____________ detectors are better at sensing smoky fires, such as those caused by a smoldering mattress.

<p>Photoelectric</p> Signup and view all the answers

Projected beam-type detectors shall be kept clear of __________ obstacles.

<p>opaque</p> Signup and view all the answers

Projected beams shall be designed so that small angular movements do not cause ______________.

<p>nuisance alarms</p> Signup and view all the answers

The two types of photoelectric smoke detectors: light-______________ and light- ____________.

<p>obscuration, scattering</p> Signup and view all the answers

_____________ detectors contain multiple sensors that respond separately but provide only one alarm signal.

<p>Multi-criteria</p> Signup and view all the answers

____________ detectors contain multiple sensors and are capable of generating multiple alarms.

<p>Multi-sensor</p> Signup and view all the answers

____________ detectors employ more than one operating principle and operate independent of each other.

<p>Combination</p> Signup and view all the answers

____________ detectors are used to protect large areas. It is a light beam broken by combustible particles.

<p>Beam</p> Signup and view all the answers

___________ detectors shut down a building's HVAC system and re-direct airflow.

<p>Dust smoke</p> Signup and view all the answers

Fire alarm devices shall be protected, especially during ___________.

<p>installation</p> Signup and view all the answers

For air sampling type detectors, the maximum air sampling transport time from the farthest point shall not exceed ____________.

<p>120 seconds</p> Signup and view all the answers

Air-sampling detectors shall give a ____________ signal if the airflow is outside the manufacturer's specified range.

<p>trouble</p> Signup and view all the answers

Maximum allowable time for fire alarm output functions to operate once a smoke detector has been activated is __________ seconds.

<p>10</p> Signup and view all the answers

__________ heat detectors do not have to be replaced after it has activated the fire alarm.

<p>Rate of rise</p> Signup and view all the answers

________ heat detectors activate the alarm when the detector components melt at a preset temperature.

<p>Fixed-temperature heat detectors</p> Signup and view all the answers

__________ heat detectors are the most commonly used.

<p>Fixed-temperature</p> Signup and view all the answers

___________ detectors are required in any building that has fossil fuel burning equipment.

<p>Carbon monoxide</p> Signup and view all the answers

The _________ shall only be reset at the direction of a fire department representative.

<p>fire alarm control panel</p> Signup and view all the answers

Single action stations are usually found __________.

<p>indoors</p> Signup and view all the answers

Once activated, the fire alarm system cannot be re-set at the _____________.

<p>fire alarm manual pull station</p> Signup and view all the answers

A master plumber with an S-12 COF is allowed to perform maintenance on sprinkler systems in residential occupancies with less than ____________ sprinklers.

<p>30</p> Signup and view all the answers

When a ____________ condition is indicated, the COF holder should check the system in order to identify the part of the system that caused the signal.

<p>supervisory</p> Signup and view all the answers

All subsystems are subject to FDNY inspection and test for issuance of _______________.

<p>letter of approval</p> Signup and view all the answers

In large buildings, the fire annunciator may be associated with ____________ control and _____________ systems.

<p>smoke purge, communications</p> Signup and view all the answers

The _______________ alarm method activates all audio/visual devices throughout the building when a fire is detected.

<p>general</p> Signup and view all the answers

The ______________ alarm method activates audio/visual devices only on the floor of alarm as well as the floors immediately above and below.

<p>selective</p> Signup and view all the answers

Two-way communication systems must be tested at least once every ______________ months.

<p>6</p> Signup and view all the answers

Unmonitored fire command centers must be inspected at least _____________.

<p>weekly</p> Signup and view all the answers

Monitored fire command centers must be conducted at least ___________.

<p>annually</p> Signup and view all the answers

_________ visual inspection is highly recommended by the FDNY.

<p>Daily</p> Signup and view all the answers

The __________ should be maintained at the building's FACP.

<p>alarm log book</p> Signup and view all the answers

The log book should be a ________ book.

<p>bound</p> Signup and view all the answers

The four sections in the alarm book should contain the following:

<p>daily entries, system off-line entries, activated alarm entries, and notification entries.</p> Signup and view all the answers

Smoke detectors must be cleaned at least once every ______________.

<p>6 months.</p> Signup and view all the answers

Study Notes

Fire Alarm Systems Overview

  • An approved central station company is certified by the FDNY.
  • A plenum is the area that allows air circulation between ceilings and the floor above.
  • Unnecessary alarms indicate that the alarm functioned correctly; however, a department response is not required.
  • Unwarranted alarms result from poor installation or maintenance.

Regulatory Changes

  • The new fire code adopted in July 2008 significantly altered supervision requirements for fire alarm systems.

S-95 COF Holder Responsibilities

  • Duties performed by an S-95 holder are limited to visual inspections only.

Fire Alarm System Functions

  • The primary function of a fire alarm system is to alert occupants and relay fire signals to the FDNY.
  • A fire alarm control panel processes signals from initiating devices and activates appropriate alerts.

Signal Types

  • A fire alarm signal indicates detectable fire presence.
  • A supervisory signal denotes an abnormal state in devices being monitored.
  • A trouble signal shows that the system, transmitter, or communication path is partially or fully inoperable.

Signal Management

  • Central station trouble signal handling should occur within four minutes of receipt.
  • The FDNY does not respond to supervisory or trouble signals.

Alarm Conditions

  • Do not silence audible and visual alarm devices until the fire alarm condition is confirmed by FDNY personnel.
  • Smoke detectors require cleaning every six months by certified COF holders.
  • Any abnormal conditions must be documented in the logbook.

Power Specifications

  • Fire alarm primary power must not exceed 277/480 volts.
  • Batteries cannot serve as a standalone power source; a secondary power source is necessary.

Maintenance Requirements

  • When smoke detectors notify the fire alarm control panel of maintenance needs, cleaning must occur within one week.
  • Ionization detectors utilize an ionization chamber to detect electrically charged particles (ions).

Detector Types and Functions

  • Photoelectric detectors excel at detecting smoky fires, such as smoldering materials.
  • Projected beam-type detectors must remain free from opaque obstacles and designed to prevent nuisance alarms.
  • Multi-criteria detectors use multiple sensors for a single alarm signal, while multi-sensor detectors can generate multiple alarms.

HVAC and Air Sampling

  • Dust smoke detectors deactivate a building's HVAC system and adjust airflow.
  • For air sampling type detectors, maximum air sampling transport time should not surpass 120 seconds.
  • Trouble signals trigger if airflow deviates from specified ranges.

Alarm Output and Response Times

  • Maximum allowable time for alarm functions to initiate after smoke detector activation is ten seconds.
  • Rate of rise heat detectors do not require replacement following alarm activation.

Specific Equipment Requirements

  • Carbon monoxide detectors are mandatory in buildings with fossil-fuel-burning equipment.
  • The fire alarm control panel can only be reset under a fire department representative's direction.

Maintenance and Inspection Protocols

  • Single action stations are typically located indoors.
  • The fire alarm system cannot be reset at manual pull stations once activated.
  • A certified plumber can maintain residential sprinkler systems if there are less than 30 sprinklers.

Inspection Standards

  • FDNY inspects all subsystems for approval letters.
  • In larger buildings, fire annunciators may work in conjunction with smoke purge and communication systems.
  • The general alarm method activates all devices in the building; selective methods activate those on the alarm floor and adjacent floors.

Testing Frequencies

  • Two-way communication systems require testing every six months.
  • Unmonitored fire command centers must be inspected weekly, while monitored centers require annual inspections.
  • Daily visual inspections are highly recommended by the FDNY.

Alarm Management Documentation

  • An alarm logbook is maintained at the building's fire alarm control panel, and it should be bound.
  • The logbook comprises daily entries, system offline notes, activated alarm records, and notification entries.

Studying That Suits You

Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

Quiz Team

Description

Test your knowledge with this set of flashcards focused on the supervision of fire alarm systems. Each card will challenge you with terminology and definitions relevant to this essential safety topic. Perfect for those studying industry standards and procedures.

More Like This

F80 Exam Flashcards
78 questions
Fire Alarm Systems and Codes Overview
25 questions
Técnico en Alarmas de Incendio TFM 12
8 questions
Use Quizgecko on...
Browser
Browser