4 - Devices and Networks
37 Questions
0 Views

4 - Devices and Networks

Created by
@FasterNephrite1826

Podcast Beta

Play an AI-generated podcast conversation about this lesson

Questions and Answers

What setting must be configured for an Ethernet device to enable time synchronization?

  • Time Synch Ethernet Enabled (correct)
  • Communication settings
  • Time Synch ION Enabled
  • Clock and time synchronization
  • Which of the following is essential for proper setup of PowerLogic ION devices?

  • Setting up a communication network (correct)
  • Installing additional hardware
  • Programming the device firmware
  • Using third-party monitoring tools
  • What is included in the minimum PowerLogic device setup?

  • User interface customization options
  • IoT integration preferences
  • CT and PT ratios programmed (correct)
  • Advanced diagnostic tools
  • For a serial device, which option must be configured to enable time synchronization?

    <p>Time Synch ION Enabled</p> Signup and view all the answers

    Which configuration utility is recommended for device configuration in PowerLogic ION Setup?

    <p>Setup Assistant</p> Signup and view all the answers

    What type of device is BoardA.HVAC1?

    <p>ION 9000</p> Signup and view all the answers

    Which communication type is used by the PM5100 series device?

    <p>Serial</p> Signup and view all the answers

    Which IP address is associated with the ION 9000 device?

    <p>192.168.100.112</p> Signup and view all the answers

    What is required for proper operation of PowerLogic devices?

    <p>A minimum set of parameters must be configured</p> Signup and view all the answers

    What parameters ensure accurate timestamps for onboard data logs?

    <p>Internal clocks</p> Signup and view all the answers

    Which address range corresponds to VM 4 to 6 for BoardA.Lighting1?

    <p>x</p> Signup and view all the answers

    Which type of system configuration is mentioned as part of the parameters for PowerLogic devices?

    <p>Delta or Wye</p> Signup and view all the answers

    What is one of the communication methods that can be configured for PowerLogic devices?

    <p>Ethernet</p> Signup and view all the answers

    Which type of network generally provides better performance according to the content?

    <p>Ethernet networks</p> Signup and view all the answers

    What is one recommendation for optimizing real-time data polling?

    <p>Set polling periods according to user needs</p> Signup and view all the answers

    Which device should be connected directly through Ethernet for better power quality monitoring?

    <p>ION9000</p> Signup and view all the answers

    What action should be taken regarding devices that are not currently functional?

    <p>Disable these devices</p> Signup and view all the answers

    When is it advisable to schedule log uploads?

    <p>During times of low system usage</p> Signup and view all the answers

    What should be avoided when polling data from devices?

    <p>Polling with high speed when not needed</p> Signup and view all the answers

    Which statement best describes how communications occur between the software and devices?

    <p>Through on-demand requests and periodic data polling</p> Signup and view all the answers

    For what purpose should the Daisy Chain Calculator tool be used?

    <p>To connect high-end devices effectively</p> Signup and view all the answers

    What basic settings can be configured using the front panel of the PM8000?

    <p>Metering (system type, CT, PT)</p> Signup and view all the answers

    Which of the following configurations requires the use of ION Setup?

    <p>Power quality detection</p> Signup and view all the answers

    What is the role of the Meter Verification in ION Setup?

    <p>To verify the wiring of PTs and CTs</p> Signup and view all the answers

    Why is time synchronization important for devices in PME?

    <p>It maintains accurate time across devices</p> Signup and view all the answers

    Which configuration is performed for Modbus devices in ION Setup?

    <p>Data recording and memory allocation</p> Signup and view all the answers

    What synchronization mechanism does PME use to ensure time accuracy?

    <p>Serial Networks and Ethernet Networks</p> Signup and view all the answers

    What type of displays can be configured for an ION device?

    <p>Custom front panel displays</p> Signup and view all the answers

    What is the first step required for full device time synchronization?

    <p>Configure a time source to send time synchronizations</p> Signup and view all the answers

    Which feature is NOT included in the basic settings of the PM8000 front panel?

    <p>Data recording</p> Signup and view all the answers

    What happens if an ION9000 is configured to receive time synchronizations from multiple sources?

    <p>It will cause conflicts and may not show accurate time.</p> Signup and view all the answers

    Which time synchronization method is most suitable for systems requiring high accuracy?

    <p>GPS</p> Signup and view all the answers

    What is a recommended practice to avoid multiple time synchronization signals in the network?

    <p>Use a common protocol across all devices</p> Signup and view all the answers

    Which of the following is NOT a time synchronization source for power quality monitoring?

    <p>Bluetooth</p> Signup and view all the answers

    To enable time synchronization on an ION device, which tab should you access in ION Setup?

    <p>Timezone tab</p> Signup and view all the answers

    What is a critical requirement for systems where time synchronization is not considerably critical (± 1 s)?

    <p>Using either Power Monitoring Expert server or NTP is acceptable</p> Signup and view all the answers

    Which of the following protocols is designed for high accuracy time synchronization?

    <p>GPS</p> Signup and view all the answers

    Study Notes

    Time Synchronization Configuration

    • Each device needs a single time synchronization source
    • Two steps are required:
      • Configure the time source
      • Configure the devices to receive synchronizations
    • Example: both a Power Monitoring Expert server and an NTP server are sending time synchronizations on the same network.
    • In this case, an ION9000 should be configured to only receive time synchronizations from one of these servers (eg: Power Monitoring Expert server).

    Time Synchronization Sources

    • Systems where time synchronization is not critical for power quality monitoring, sequence of events recording (SER), revenue billing, or system stability, can use these sources:
      • Power Monitoring Expert Server
      • DNP
      • NTP
      • DLMS
    • Systems that require stricter time synchronization (±1 ms), for example in power quality monitoring, SER, revenue billing, or system stability, can use these sources:
      • PTP
      • GPS
      • IRIG-B
    • Use a protocol that is common to all devices to avoid multiple time synchronization signals in the network.

    Enable time synchronization on an ION device

    • Connect to the device using ION Setup.
    • Change the CL1 Time Sync Source for clock on the Timezone tab.
    • This can also be done on the meter front panel.

    Network Performance

    • Ethernet networks provide better performance than serial networks
    • Communications between the software and devices consist of:
      • On-demand, real-time data requests, used for diagrams and dashboards displays
      • Periodic polling and uploading of data logs, events, and waveform records

    Optimizing the on-demand and background polling performance

    • Set real-time data polling periods to meet the user's needs, avoiding fast polling when unneeded
    • Disable devices that are not commissioned and functional
    • Only log measurements that are necessary to meet user needs
    • Schedule log uploads when the system is being used less, such as at night or off hours
    • Use ethernet instead of serial to connect high-end ION9000 devices with power quality monitoring features
    • Use the Daisy Chain Calculator tool.

    Add a site, Modbus device and an Ethernet Device

    • Example:
      • BoardA, Lighting1, PM5100 series, serial (5), 192.168.100.102
      • BoardA, HVAC1, PM5350, serial (1), 192.168.100.102
      • BoardA, HVAC1, ION9000, ethernet, 192.168.100.112, 192.168.100.113, 192.168.100.116, 192.168.100.117

    Meter Configuration

    • Minimum parameters must be configured on all PowerLogic devices:
      • Basic Metering: system type (delta or wye), CT and PT ratios
      • Communication: serial or ethernet ports, IP address, subnet, gateway, Modbus ID, baud rate
      • Clock: internal clocks ensure accurate timestamps for alarms and data logs, synchronize with the Power Monitoring Expert server

    Basic Configuration

    • Can be done using the front panel or ION Setup.
    • Front panel provides limited settings:
      • Metering (system type, CT, PT)
      • Communications
      • Display
      • Clock
      • Alarms
      • Language
      • Security
    • ION Setup provides various settings:
      • Data recording and memory allocation
      • Power quality detection
      • Input metering for WAGES
      • Digital/analog outputs
      • Custom front panel displays

    Advanced Configuration

    • This configuration must be done through ION Setup.
    • Parameters can be configured using:
      • Setup Screens (for Modbus devices)
      • Setup Assistant (for ION devices)

    Meter Verification and Phasor Viewer in ION Setup

    • Meter verification helps answer questions like:
      • Are the measurements close to the expected value?
    • Phasor Viewer helps answer questions like:
      • Are the PTs and CTs wired correctly?

    Time Synchronization

    • Devices require time synchronization for accurate time in PME
    • Different synchronization mechanisms achieve different time accuracy levels
    • PME can synchronize devices to the PME server computer clock
    • This can be done over serial and ethernet networks.

    Enable time synchronization on an ION device

    • In Management Console:
      • For ethernet devices: set Time Synch Ethernet Enabled to Yes in the ethernet device configuration.
      • For serial devices: set Time Synch ION Enabled to Yes in the Ethernet Gateway.

    Key Points to Remember

    • PowerLogic ION Setup is recommended for device configuration.
    • This setup can be used to:
      • Create a network of devices for initial and future device configuration
      • Configure ION devices using the Setup Assistant
      • Configure Modbus devices using Setup Screens
    • Minimum setup for PowerLogic devices involves:
      • Programming CT and PT ratios and system type (delta or wye)
      • Configuring communication settings
      • Configuring clock and time synchronization for devices with onboard alarms and data logs.

    Studying That Suits You

    Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

    Quiz Team

    Related Documents

    Devices and Networks PDF

    Description

    This quiz covers the configuration of time synchronization sources in power systems, emphasizing the importance of a single time source for devices. Learn about various synchronization protocols and their application in scenarios that require precise timekeeping for monitoring and billing.

    More Like This

    Use Quizgecko on...
    Browser
    Browser