Sub-Stations and Switching Stations Overview

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to Lesson

Podcast

Play an AI-generated podcast conversation about this lesson

Questions and Answers

What should be checked to ensure the gas supply to the system is adequate?

  • Temperature only
  • Gas type only
  • Gas pressure switches only
  • Pressure and temperature (correct)

Which maintenance action is NOT required for the interrupting chamber of a vacuum circuit breaker?

  • Inspect the interrupting chamber for damage
  • Perform maintenance on the interrupting chamber (correct)
  • Clean the interrupting chamber surface
  • Ensure its functionality

Which factor is essential to check when ensuring the operating mechanism is functioning properly?

  • Gas levels
  • Pneumatic system for leakage (correct)
  • Electrical circuit types
  • Environmental temperature

What should be done with absorbent materials during maintenance?

<p>Renew them with minimal atmospheric exposure (D)</p> Signup and view all the answers

How should the working of the pressure gauge be confirmed?

<p>By checking against a known standard (A)</p> Signup and view all the answers

What is the voltage rating of the lead acid batteries used for control in traction sub-stations?

<p>110V, 200Ah (A)</p> Signup and view all the answers

Which of the following is a feature of mains operated battery chargers?

<p>Trickle charge and boost charging capabilities (B)</p> Signup and view all the answers

What should be performed on the operating mechanism to prevent rust?

<p>Check for water penetration (B)</p> Signup and view all the answers

In remote control equipment, what should be considered regarding battery placement?

<p>Connecting to TSS/SS batteries reduces the total number required (D)</p> Signup and view all the answers

What should inspecting officials do to avoid neglect of installations during inspections?

<p>Stagger inspections among themselves. (A)</p> Signup and view all the answers

What is recommended to do if schedules for new equipment have not been established?

<p>Follow original Equipment Manufacturer’s guidelines. (A)</p> Signup and view all the answers

What must be done before commencing work near live equipment?

<p>Switch off the power supply and implement safety measures. (D)</p> Signup and view all the answers

What is one of the actions to prevent unauthorized interference at substations?

<p>Implement surprise checks and periodical inspections. (C)</p> Signup and view all the answers

Which of the following is a recommended maintenance schedule for circuit breakers?

<p>Adhere to manufacturer-specific recommendations. (A)</p> Signup and view all the answers

What additional context should be considered while carrying out maintenance work?

<p>Local requirements along with the periodic attention items. (B)</p> Signup and view all the answers

Which type of circuit breakers have specific schedules mentioned in the Annexure?

<p>Both SF6 and vacuum circuit breakers. (D)</p> Signup and view all the answers

What should be included in the maintenance schedule for new equipment?

<p>Tentative schedules based on guidelines and local conditions. (C)</p> Signup and view all the answers

What aspect of inspections is emphasized for maintaining quality?

<p>Maintaining a consistent inspection frequency. (B)</p> Signup and view all the answers

What is crucial for employees when they are near unattended substations?

<p>To report any unusual activity to their supervisor. (A)</p> Signup and view all the answers

What should be done if insulators are badly chipped?

<p>Replace them (B)</p> Signup and view all the answers

What action should be taken if the silica-gel breather appears pink?

<p>Replace it with dry gel (A), Recondition the old silica-gel (B)</p> Signup and view all the answers

What is the first step in maintaining traction transformers?

<p>Clean the external components with a dry cloth (A)</p> Signup and view all the answers

What should be checked for damage in traction transformers?

<p>The explosion vent diaphragm (B)</p> Signup and view all the answers

Which material can be used to make minor chippings on insulators impervious to moisture?

<p>Araldite (C)</p> Signup and view all the answers

What should be done if there is oil leakage from the transformer?

<p>Tighten the bolts and replace gaskets if necessary (B)</p> Signup and view all the answers

What action should be taken if a battery is not in a fully charged condition?

<p>Boost charge should be given as required (A)</p> Signup and view all the answers

What is required to ensure a circuit breaker's control box is properly maintained?

<p>All accumulated dust must be removed (D)</p> Signup and view all the answers

What should be checked specifically on the low voltage side for potential transformers (PTs)?

<p>Fuse holders are in order (D)</p> Signup and view all the answers

During quarterly maintenance, what should be noted regarding the battery charger?

<p>Check the earth connection to the body (A)</p> Signup and view all the answers

What should be ensured regarding the weather-proof gaskets in the circuit breaker control box?

<p>They must be in good condition (C)</p> Signup and view all the answers

How should the oil level in equipment be rectified?

<p>By replacing faulty parts and restoring the oil level (C)</p> Signup and view all the answers

What must be measured and recorded for auxiliary transformers during maintenance?

<p>Insulation resistance of transformer winding (C)</p> Signup and view all the answers

How often should the mechanism of circuit breakers be operated manually?

<p>At least twice during maintenance (D)</p> Signup and view all the answers

What should be checked on booster transformers concerning earthing connections?

<p>Confirm proper connection to the earth electrodes or rails (C)</p> Signup and view all the answers

What is the primary responsibility of the Senior Section Engineer in Power Supply Installations?

<p>To ensure the safe and efficient operation and maintenance of traction power supply installations. (D)</p> Signup and view all the answers

Which of the following is NOT a duty of the Senior Section Engineer?

<p>Ensure the equipment is never maintained. (D)</p> Signup and view all the answers

What should the Senior Section Engineer do in the event of equipment breakdowns?

<p>Ensure his organization is ready to deal promptly with any break-downs. (A)</p> Signup and view all the answers

Which method is important for ensuring the reliability of power supply?

<p>Keeping constant liaison with supply authorities and assisting when needed. (B)</p> Signup and view all the answers

What is crucial for the maintenance of protective relays?

<p>Adhering to the program of testing and maintenance of protective relays. (A)</p> Signup and view all the answers

How should the Senior Section Engineer manage spare parts and stores?

<p>Monitor their availability and initiate timely actions as necessary. (D)</p> Signup and view all the answers

What is a key responsibility in training the staff under the Senior Section Engineer's control?

<p>To instruct, train, and supervise them to operate and maintain equipment properly. (A)</p> Signup and view all the answers

What is a significant risk associated with high voltage equipment due to excessive moisture in oil?

<p>Internal flashover between live parts and earth (B)</p> Signup and view all the answers

What type of circuit breaker is now standardized to overcome maintenance limitations of oil-type breakers?

<p>SF6 type circuit breakers (B)</p> Signup and view all the answers

Which property of SF6 gas contributes to its effectiveness in circuit breakers?

<p>High dielectric strength (C)</p> Signup and view all the answers

What by-product is produced from arcing in SF6 circuit breakers?

<p>Metallic fluoride (A)</p> Signup and view all the answers

What is a common maintenance issue with minimum oil type circuit breakers?

<p>Frequent need for oil replacement due to service conditions (A)</p> Signup and view all the answers

What characteristic of SF6 gas minimizes the impact of its decomposition after long periods of arcing?

<p>Exceptional thermal stability (A)</p> Signup and view all the answers

What maintenance instruction is critical for circuit breakers and interrupters?

<p>Referencing manufacturer's detailed instructions (D)</p> Signup and view all the answers

What is essential to ensure the proper functioning of the control panel?

<p>Inspecting fuses for the correct size and signs of aging. (A)</p> Signup and view all the answers

Which check is mandatory for the interrupters during maintenance?

<p>Testing for proper alignment of blade tips in the fixed contact jaws. (B)</p> Signup and view all the answers

What should be verified regarding the battery charger during routine checks?

<p>The sizing of fuses within the battery charger. (D)</p> Signup and view all the answers

In the context of ensuring the soundness of earth connections, what must be checked?

<p>The last recorded earth resistance readings. (C)</p> Signup and view all the answers

Which aspect is crucial when checking remote control equipment?

<p>Testing the general function of relays and selectors. (B)</p> Signup and view all the answers

What is the maximum acceptable pressure for gas supply during maintenance?

<p>The prescribed operational threshold (D)</p> Signup and view all the answers

Which action is critical when renewing the absorbent in the interrupting unit?

<p>Minimizing exposure to the atmosphere (A)</p> Signup and view all the answers

Which of the following steps is NOT essential for the operating mechanism maintenance check?

<p>Evaluating stock levels of spare parts (C)</p> Signup and view all the answers

Which condition must be fulfilled for the maintenance of vacuum circuit breakers?

<p>No specific maintenance is needed for the interrupting chamber (D)</p> Signup and view all the answers

For lead acid batteries in traction sub-stations, how should their capacity be correlated with charging systems?

<p>The charger rating should match the battery's capacity (D)</p> Signup and view all the answers

What is the voltage range for lead acid batteries used at switching stations?

<p>110V or 72V (B)</p> Signup and view all the answers

What should be checked in the pneumatic system as part of the operating mechanism maintenance?

<p>For any signs of leakage (B)</p> Signup and view all the answers

What is a common practice regarding battery chargers in traction sub-stations and switching stations?

<p>Trickle and boost charging options should be available (D)</p> Signup and view all the answers

What should be done with the connections of control circuit wires during maintenance?

<p>They should be checked for looseness (D)</p> Signup and view all the answers

What is the approximate cell voltage at the end of a full charge for new batteries receiving a charge at a 10-hour rate?

<p>2.5 to 2.75 V (A)</p> Signup and view all the answers

Which factor does NOT influence the voltage of a battery cell at the end of a charge?

<p>Current flow rate (A)</p> Signup and view all the answers

At what cell voltage level should a battery NEVER be discharged below?

<p>1.85 V (D)</p> Signup and view all the answers

What color should the active material in the positive plates of a healthy cell be after more than 12 months of use?

<p>Chocolate brown (D)</p> Signup and view all the answers

What indicates a weak cell when inspecting battery plates?

<p>Irregular gassing (B)</p> Signup and view all the answers

What is the primary cause of noticeable drop in terminal voltage in lead-acid cells?

<p>Sulphated plates (D)</p> Signup and view all the answers

During battery maintenance, how should flakes of brown scale detached from positive plates be handled?

<p>They should be dislodged gently. (B)</p> Signup and view all the answers

What is the relationship between the voltage of a cell and its state of charge?

<p>Voltage only indicates charge when discharging. (C)</p> Signup and view all the answers

What color indicates the active material of healthy negative plates according to their age?

<p>Light grey or bluish grey (A)</p> Signup and view all the answers

What should be done to voltmeters when not in use to ensure accuracy?

<p>Calibrate them periodically. (C)</p> Signup and view all the answers

What color of deposits indicates that a lead-acid battery is in a discharged condition?

<p>Whitish (C)</p> Signup and view all the answers

What should be done immediately if excessive shedding of active material from positive plates is noticed?

<p>Reduce the rate of charge (C)</p> Signup and view all the answers

Which inspection method is recommended for the inter-cell connectors of a battery?

<p>Checking for tightness and corrosion (B)</p> Signup and view all the answers

When a weak cell is found, what is the immediate action that should be taken?

<p>Examine for short circuits (B)</p> Signup and view all the answers

What preventive measure can be applied to inter-cell connectors to avoid corrosion?

<p>Light Vaseline application (B)</p> Signup and view all the answers

Which certification should specialist staff hold for the maintenance of protective relays?

<p>TR-7 (A)</p> Signup and view all the answers

What is the recommended action if copper inter-row connectors show signs of corrosion?

<p>Clean the corrosion and repaint (D)</p> Signup and view all the answers

What should each Supervisor maintain regarding protective relays?

<p>A detailed register of each relay (B)</p> Signup and view all the answers

What should be done if all cells in a battery show whitish deposits?

<p>Apply a boost charge at an appropriate rate (A)</p> Signup and view all the answers

What type of paint should be applied to exposed copper work in the battery area?

<p>Acid-proof paint or enamel (C)</p> Signup and view all the answers

Flashcards

Senior Section Engineer's Power Supply Duties

Responsible for safe and efficient operation of traction power supply installations, sub-stations, switching stations, booster, and auxiliary transformers within their assigned area.

Maintenance Schedules

Prescribed plans for inspection and repair, ensuring equipment is always ready.

Liaison with Traction Power Controller

Coordination with the traction power controller for reliable power supply.

Breakdown Response

The team's preparedness to quickly address equipment failures.

Signup and view all the flashcards

Protective Relays Maintenance

Following a schedule for inspecting and maintaining safety equipment like protective relays and bonding.

Signup and view all the flashcards

Staff Training & Supervision

Ensuring staff follows safety procedures and properly utilizes equipment in maintenance tasks.

Signup and view all the flashcards

Spare Parts Management

Monitoring spare parts stock and taking action to replenish supplies needed for maintenance and operation.

Signup and view all the flashcards

Gas Pressure Maintenance

Monitor gas pressure and temperature; supply gas if pressure is low; check pressure switches.

Signup and view all the flashcards

Interrupting Unit Cleaning

Clean porcelain, inspect/replace contacts, replace absorbent, and evacuate the breaker quickly.

Signup and view all the flashcards

Operating Mechanism Check

Verify stroke, check clearances, re-lubricate parts, assess pressure gauge and pneumatic system leakage, check housing for issues and ensure fasteners are tight.

Signup and view all the flashcards

Vacuum Circuit Breaker Maintenance

Follow guidelines for general maintenance (operating mechanism, housing), but vacuum bottle(interrupting chamber) does not require specific maintenance, except for the pneumatic circuit.

Signup and view all the flashcards

Lead Acid Battery Importance

Essential equipment in power supply installations; proper maintenance is crucial.

Signup and view all the flashcards

Battery Locations (Traction Sub-stations)

110V, 200Ah lead acid cells used for control, protection, and indication circuits in traction sub-stations.

Signup and view all the flashcards

Battery Locations (Switching Stations)

110V or 72V, 40Ah lead acid batteries for circuit breakers, interrupters, and motor-operated isolators in switching stations.

Signup and view all the flashcards

Remote Control Batteries

Batteries of suitable voltage and capacity, connected to sub/switching station batteries to reduce the number of batteries at a location.

Signup and view all the flashcards

Battery Charger Requirements

Mains-operated chargers should provide trickle charge or boost charging and should be sized according to battery capacity.

Signup and view all the flashcards

Poor Work Quality Conditions

Environmental factors that negatively impact the quality of work.

Signup and view all the flashcards

Staggered Inspections

Scheduling inspections to avoid overlapping among inspectors, ensuring all locations are inspected within a set timeframe.

Signup and view all the flashcards

Maintenance Work Periodicity

The schedule for performing maintenance tasks, which can be adjusted based on local needs.

Signup and view all the flashcards

New Equipment Maintenance

Establishing maintenance schedules for new equipment, using manufacturer guidelines and external recommendations.

Signup and view all the flashcards

SF6 Circuit Breaker Maintenance

Maintenance schedules for SF6 type circuit breakers, as defined by manufacturers.

Signup and view all the flashcards

Live Equipment Work

Work on or near active electrical equipment is not allowed unless power is off and other safety measures are implemented.

Signup and view all the flashcards

Unauthorized Interference

Preventing unauthorized access to and tampering with unattended electrical equipment.

Signup and view all the flashcards

Surprise Checks

Unannounced inspections that help deter unauthorized actions at substations/switching stations.

Signup and view all the flashcards

Electrical Staff Vigilance

Duty of all electrical department staff members to remain aware of and observe for any activity of unauthorized intervention.

Signup and view all the flashcards

Battery Specific Gravity

A measure of the battery's charge level, indicating the concentration of acid in the electrolyte.

Signup and view all the flashcards

Boost Charging Batteries

Applying a higher charging current to a depleted battery to quickly restore its charge.

Signup and view all the flashcards

PTs and CTs Maintenance

Regular inspection and maintenance of Potential Transformers (PTs) and Current Transformers (CTs) to ensure accurate voltage and current readings.

Signup and view all the flashcards

Booster Transformer Earthing

Ensuring the booster transformer is properly connected to the earth for safety and to prevent electrical shocks.

Signup and view all the flashcards

Auxiliary Transformer Insulation Resistance

Measuring the resistance of the transformer winding to prevent electrical leakage and ensure insulation integrity.

Signup and view all the flashcards

Insulator Inspection

Visually inspect insulators for damage like cracks or chips, clean with a dry cloth, and replace badly damaged insulators.

Signup and view all the flashcards

Minor Insulator Damage

Minor chips on insulators can be sealed with a thin layer of epoxy resin to prevent moisture from entering.

Signup and view all the flashcards

Transformer Oil Level Check

Check the oil level in the transformer's sight gauge glass and ensure it's within the specified range. Replenish oil if necessary.

Signup and view all the flashcards

Transformer Oil Temperature

Record the maximum oil temperature on the dial indicator and reset the indicator after each inspection.

Signup and view all the flashcards

Transformer Explosion Vent

Inspect the explosion vent diaphragm for any damage and ensure it's free of oil. This vent serves as a safety device in case of a pressure build-up.

Signup and view all the flashcards

Silica-Gel Breather

Check the silica-gel breather for moisture absorption. If it turns pink, replace it with dry silica-gel. A wet breather indicates moisture entering the transformer.

Signup and view all the flashcards

Transformer Gas Collection

Check for gas collection inside the transformer. If gas is present, it might indicate internal faults.

Signup and view all the flashcards

Transformer Oil Leakage

Inspect the transformer for oil leakage, particularly at the body, conservator tank, drain valve, and foundations. Address any leakage by tightening bolts or replacing gaskets.

Signup and view all the flashcards

Transformer Heater Check

Ensure the transformer's heater, located in the marshalling box, is functioning properly and that all terminal connections are in order.

Signup and view all the flashcards

Circuit Breaker Mechanism Inspection

Clean the circuit breaker's control box, examine the interior, and check for signs of moisture, corrosion, or worn parts. Ensure protective gaskets are in good condition.

Signup and view all the flashcards

SF6 Circuit Breakers

A type of circuit breaker that uses sulfur hexafluoride (SF6) gas as an insulating and arc-quenching medium. SF6 gas offers excellent electrical insulation, thermal stability, and arc-quenching properties.

Signup and view all the flashcards

SF6 Gas Properties

SF6 gas is inert, thermally stable, and has exceptional dielectric strength (resistance to electrical breakdown). It also has excellent arc-quenching properties, meaning it can quickly extinguish electrical arcs.

Signup and view all the flashcards

SF6 Decomposition

During arcing, a small amount of SF6 gas decomposes into solid byproducts. These byproducts are usually metallic fluoride which appears as a fine grey powder with good dielectric strength.

Signup and view all the flashcards

Absorbent in SF6 Breakers

A high-quality absorbent material is incorporated into the SF6 circuit breaker to remove any decomposed gaseous byproducts, ensuring the gas remains pure and effective.

Signup and view all the flashcards

Oil Circuit Breakers

Circuit breakers that use oil as insulation and to quench electrical arcs. They were used in older systems but require frequent oil replacement and maintenance.

Signup and view all the flashcards

Maintenance of Circuit Breakers

Regular maintenance of all types of circuit breakers (SF6, oil, vacuum) is crucial to ensure their reliable operation and prevent potential failures.

Signup and view all the flashcards

Circuit Breaker Manufacturer's Instructions

Always refer to the manufacturer's detailed instructions for the correct installation, commissioning, operation, and maintenance procedures for all types of circuit breakers/interrupters.

Signup and view all the flashcards

PT & AT Check

Regularly inspect Potential Transformers (PTs) and Auxiliary Transformers (ATs) for leakage of oil, ensuring they function properly.

Signup and view all the flashcards

Isolator Check

Ensure the correct alignment of blade tips in the fixed contact jaws of isolators, and check the alignment of arcing horns.

Signup and view all the flashcards

Battery Charger & Batteries Check

Inspect the acid level, sedimentation, specific gravity, and voltage of batteries. Check for sulfation and tightness of inter-cell connectors. Ensure proper functioning and size of the charger fuses.

Signup and view all the flashcards

Interrupter Check

Check the control box gaskets for water and dust tightness. Verify smooth local and remote operation and inspect the mechanism. Also, monitor oil level and look for leakages.

Signup and view all the flashcards

Switching Station Check

Inspect the switchyard for vegetation, fencing, cable trenches, and trench cabins. Ensure proper maintenance and security.

Signup and view all the flashcards

Lead Acid Battery Condition

The health of a lead acid battery can be assessed by the color of the deposits on the plates. Whitish deposits indicate undercharging, while brown deposits indicate a healthy battery. Excessive shedding of active material from the positive plates signals overcharging.

Signup and view all the flashcards

Battery Deposits - Overcharging

Overcharging a battery leads to excessive shedding of active material from the positive plates, resulting in brown-colored deposits. This indicates the battery is being stressed.

Signup and view all the flashcards

Battery Deposits - Undercharging

Undercharging a battery leads to the formation of whitish deposits on the plates, indicating the battery is in a discharged state.

Signup and view all the flashcards

Battery Boost Charging

Boost charging is a quick solution for a deeply discharged battery. It involves applying a higher charging current to rapidly restore the charge level.

Signup and view all the flashcards

Battery Trickle Charging

Trickle charging involves providing a low and continuous charge to maintain a battery's health and prevent it from being fully discharged.

Signup and view all the flashcards

Inter-cell Connectors Importance

Inter-cell connectors need to be clean, tight, and in good contact with cell lugs to ensure proper electrical flow between cells within a battery.

Signup and view all the flashcards

Inter-cell Connectors Maintenance

Maintaining inter-cell connectors involves inspecting for cleanliness, tightness, and corrosion. Applying Vaseline can help prevent corrosion.

Signup and view all the flashcards

Copper Connector Corrosion

Inspect copper connectors for any signs of copper sulfate corrosion, which can be cleaned up to prevent further damage.

Signup and view all the flashcards

Protective Relays Staff

Specialized staff trained in the maintenance, testing, and calibration of protective relays is crucial for maintaining the safety and reliability of electrical systems.

Signup and view all the flashcards

Protective Relay Register

A register should be maintained for each protective relay, recording details such as installation date, maintenance history, and calibration information.

Signup and view all the flashcards

Gas Pressure Check

During maintenance, check the gas pressure and temperature. If the pressure is below the specified value, supply gas. Also, verify the settings of the gas pressure switches.

Signup and view all the flashcards

Battery Importance

Lead-acid batteries are critical components in power supply installations, and proper maintenance is crucial for their reliable operation.

Signup and view all the flashcards

Battery Locations

Batteries are installed in traction sub-stations (110V, 200Ah), switching stations (110V or 72V, 40Ah) and at remote control locations. The remote control equipment is often connected to the battery at the sub-station/switching station to reduce the number of batteries needed.

Signup and view all the flashcards

Why is a vacuum circuit breaker special?

Vacuum circuit breakers have a special vacuum bottle component that doesn't require regular maintenance, unlike other types of circuit breakers.

Signup and view all the flashcards

What is the most important thing to remember about lead-acid batteries?

Lead-acid batteries are essential for power supply installations, and proper maintenance is crucial for their reliable operation.

Signup and view all the flashcards

Study Notes

Sub-Stations and Switching Stations

  • This chapter is divided into four sections: Organization, Operation of sub-stations, Guiding Notes on Maintenance, and a recommended schedule for power supply equipment maintenance.
  • Section I covers the organization and duties of Senior Section Engineer (Power Supply Installations).
  • Section II covers important points relating to the operation of transformers and protective devices.
  • Section III covers important points for the maintenance of power supply equipment.
  • Section IV provides a recommended schedule for power supply equipment maintenance.
  • Appendices to the volume include documents on the Earthing of Power Supply Installations, Relay Setting at Traction Substations and Switching Posts, Maintenance Depots, Tools and Plants with Transport Facilities, and Specifications and Drawings for Railway Electric Traction issued by RDSO.
  • Divisional setup of senior subordinates can be arranged on two types of patterns: Territorial basis and functional basis.
  • Duties of Senior Section Engineer (Power Supply Installations) include ensuring safe and efficient operation and maintenance of traction power supply installations, including substations, switching stations, booster transformers, and auxiliary transformers in their jurisdiction.
  • The Senior Section Engineer must be conversant with equipment ratings, power demand trends, and correct maintenance methods
  • Responsibilities include supervision of maintenance, coordination with other engineers to ensure reliable power supply, and readiness to deal with breakdowns.
  • Staff training and adherence to safety regulations are crucial aspects of the role.
  • Spare parts and tool inventory management, and periodic verification are important for the Senior Section Engineer.
  • Sub-stations and switching stations have to be maintained for continuous power supply, with redundancy to support critical equipment failures in the system.
  • An inspection book and log book are maintained at every sub-station to record observations by supervisory officials during periodic inspections.
  • Oil temperatures, ambient temperatures, currents, and voltage measurements are recorded to detect any anomalies for immediate remedial action.
  • Traction transformers have overload ratings, such as 50% for 15 minutes and 100% for 5 minutes.
  • Maximum permissible temperature rises for windings and oil under various overload capacities are determined by resistance and thermometer methods.
  • Tap settings on traction transformers are managed using off-load changers that enable local or remote control with steps of 5% from +10% to -15%.
  • Daily 24-hour voltage recordings are taken to decide on the correct tap setting and ensure that the OHE voltage never falls below 19 kV.
  • Oil purification is crucial to remove contaminants like water, carbon deposits, dirt, sludge, dissolved moisture, and gases to maintain dielectric strength.
  • Specific tests are performed on transformer oil, such as breakdown voltage, acidity, crackle test, and moisture, to quality control levels.
  • Installation resistance checks are made while equipment is drying out of oil.
  • Protective devices, such as alarm and trip contacts, are vital for safe operation of traction transformers by detecting excessive temperature and overload levels.
  • Differential protection and Buchholz relays help in detecting internal faults in transformers to help with quick correction.

Guiding Notes on Maintenance

  • Maintenance of traction assets needs to minimize outages and maintain safety.
  • Recommendations from OEMs and guidelines from RDSO are important in defining scope and schedule for maintenance.
  • A schedule of tightening torque for fasteners is provided.
  • Condition Monitoring of transformers and associated equipment is vital.
  • Deterioration of insulation and oil in oil filled equipment (e.g., transformers) due to thermo-chemical reactions with heat, moisture, and oxygen impacts efficiency, and is monitored.
  • Dissolved gas analysis (DGA) helps assess the condition of insulation, detect incipient faults, and evaluate status of oil.

Overhaul of Transformers

  • Transformers can be overhauled either as preventative care or due to internal faults.
  • All overhauls should be done in the Central Repair Shop.
  • Procedures for draining oil, removing leads, and safely removing the core.
  • Cleaning of the transformer tank, and repairs to the gasket.
  • Ensuring all work tools, cables etc are accounted for during these repairs.
  • Procedures for assessing the cause of any internal faults.
  • Detailed procedure for safely removing the core, and steps to follow if one coil has burnt out are outlined.

Circuit Breakers and Interrupters

  • Various types of circuit breakers and interrupters are discussed (e.g., SF6 type, Vacuum type, Oil type)
  • Maintenance guidelines are given for different types of circuit breakers.

Lead Acid Batteries

  • Lead-acid batteries are vital for power supply installations and require regular maintenance.
  • Their location (e.g., traction sub-stations, switching stations, remote control equipment) is specified.
  • Guidelines on maintenance involve checking the general battery room condition, electrolyte specific gravity, charging current, cell voltage, plate and deposit conditions, and inter-cell connectors.
  • Specific gravity values for testing are described.
  • Important notes regarding safe working conditions in the battery room are included.

Fortnightly Maintenance.

  • A complete general inspection of the sub-station, focusing on cleanliness and drainage are performed regularly.

Monthly maintenance.

  • Visual inspection of all earth connections to ensure proper operation and that components are properly tightened.
  • Oil levels, and other relevant component checks are performed.

Quarterly Maintenance

  • Testing transformer oil for BDV, Acidity or crackle related issues is performed.
  • Checks on all alarm and protection devices are performed

Half yearly maintenance.

  • An inspection is carried out to ensure that the grid networks have not changed.

Yearly Maintenance

  • Sub-station fences, lighting, and doors are inspected

Data Collection and Analysis

  • DGA should be done on a regular basis.
  • Dissolved gas analysis is performed on the oil from the transformer to check on its internal condition.
  • Results are stored and analyzed for trends or faults.

Physical Properties of SF6 Gas

  • Important physical characteristics of SF6 gas are listed, such as molecular weight, melting point/sublimation point, critical temperature/pressure, critical density, dielectric constant, thermal conductivity at 30°C, solubility density at different temperatures.

Studying That Suits You

Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

Quiz Team

Related Documents

More Like This

Power Supply Unit and Electrical Concepts
30 questions
Power Supply in ECDIS
10 questions

Power Supply in ECDIS

UnparalleledForethought4398 avatar
UnparalleledForethought4398
Use Quizgecko on...
Browser
Browser