Railway Electrification Preparation Chapter IX

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to Lesson

Podcast

Play an AI-generated podcast conversation about this lesson

Questions and Answers

What should be checked to ensure the proper functioning of MHO relays?

  • Each relay and contact mechanism individually (correct)
  • General circuit connections
  • Only the annunciation system
  • The wiring diagrams only

Which of the following is NOT included in the checks for annunciations?

  • Buchholz trip
  • Transformer efficiency reading (correct)
  • 25 kV feeder circuit breaker trip
  • Winding temperature trip

What is the importance of checking the detailed wiring diagrams after installation?

  • To ensure no errors exist in the approved diagrams (correct)
  • To simplify the operational process
  • To evaluate compliance with manufacturer guidelines
  • To verify the visual aesthetic of the panel

What should be done if indicating instruments are found to be malfunctioning?

<p>Ensure movements are free and readings are correct (D)</p> Signup and view all the answers

What is a recommended method for detecting errors in detailed wiring diagrams?

<p>Preparing a simplified schematic or functional diagram (C)</p> Signup and view all the answers

What should be examined on the isolators to ensure their proper function?

<p>Surface cracks and manual operation (B)</p> Signup and view all the answers

Why is it important to check the terminal connections of Current Transformers (CT)?

<p>To ensure contact resistance is recorded (C)</p> Signup and view all the answers

What is the purpose of the earth terminal on a lightning arrester?

<p>To drain excess voltage to the ground (A)</p> Signup and view all the answers

What should be checked for the operation of isolators regarding interlocking?

<p>The functionality between the circuit breaker and isolator (B)</p> Signup and view all the answers

What is essential to confirm about the shielding conductors in a substation?

<p>They must be connected to the earth system (C)</p> Signup and view all the answers

What aspect of Lightning Arrestors should be visually examined?

<p>Hair-line cracks and chipped sheds (A)</p> Signup and view all the answers

What must be checked regarding the oil level in Potential Transformers (PT)?

<p>It needs to be topped up for testing (A)</p> Signup and view all the answers

What is the recommended training timeline for switching station attendants before the commissioning date?

<p>One month prior (C)</p> Signup and view all the answers

Which measurement method is used to measure individual levels of every frequency on the 'send' channel?

<p>Vacuum-Tube Voltmeter (C)</p> Signup and view all the answers

What should the measured levels on the receive side be between?

<p>-17 to -25 dBm (B)</p> Signup and view all the answers

What reading should the send-channel levels not be lower than?

<p>-22 dBm (A)</p> Signup and view all the answers

At which position should the VTVM selector switch be during normal measurements of active circuits?

<p>High Impedance (A)</p> Signup and view all the answers

When should the VTVM selector switch be changed to 150 Ohm or 1120 Ohm?

<p>When the output level is to be measured with the line disconnected (C)</p> Signup and view all the answers

What is the impedance of the send and receive circuits mentioned?

<p>1120 Ohm (D)</p> Signup and view all the answers

What permanent record should be noted after the final adjustment of the levels?

<p>Values of the attenuation pads (D)</p> Signup and view all the answers

What should be used to measure composite levels between tele-command and tele-signal cable pairs?

<p>Vacuum-Tube Voltmeter (B)</p> Signup and view all the answers

What is the impedance of the amplifier output?

<p>150 Ohm (C)</p> Signup and view all the answers

What is the primary requirement for the battery room environment?

<p>Dust-free and well ventilated (C)</p> Signup and view all the answers

What should be checked regarding the condition of the battery plates?

<p>There should be no corrosion or damage (B)</p> Signup and view all the answers

What must be ensured about the alarm bell in the battery system?

<p>It goes off if the supply is interrupted (B)</p> Signup and view all the answers

Which material should the battery stands be made from?

<p>Teakwood (C)</p> Signup and view all the answers

What is an important factor when inspecting the battery charger?

<p>It must have sufficient capacity for different charging types (C)</p> Signup and view all the answers

What type of paint should be used on the battery room walls and floor up to 2 m?

<p>Anti-sulphuric acid paint (B)</p> Signup and view all the answers

What should be checked regarding the inter-cell connectors in the battery system?

<p>They need to be tight and well vaseline (B)</p> Signup and view all the answers

Which design feature must the control room building possess?

<p>It should have a strong door (B)</p> Signup and view all the answers

What type of access should the substation area have?

<p>Good all-weather road and rail access (A)</p> Signup and view all the answers

What is the standard number of discs required for tension strings for a 132 kV supply?

<p>10 discs (A)</p> Signup and view all the answers

How many discs are used for suspension strings at a distance of 1.6 km from the sub-station?

<p>8 discs (B)</p> Signup and view all the answers

For railway crossings, which type of towers should be provided?

<p>Anchor type towers (D)</p> Signup and view all the answers

What is the minimum required insulation resistance for power conductors?

<p>100 Meg Ohm (D)</p> Signup and view all the answers

What device should every tower be fitted with during a detailed inspection?

<p>Anticlimbing device (D)</p> Signup and view all the answers

Which color discs are to be provided on terminal towers to indicate phases?

<p>Red, yellow, and blue (A)</p> Signup and view all the answers

What action should be taken after defects are rectified during inspection?

<p>A general inspection should be carried out (C)</p> Signup and view all the answers

What should be done to warn the public before the lines are energized?

<p>Wide publicity should be given (A)</p> Signup and view all the answers

What is required to confirm the completion of inspections before energization?

<p>A joint certificate from inspecting officers (D)</p> Signup and view all the answers

What should be recorded during the continuity test of each conductor?

<p>Results from the continuity tester (C)</p> Signup and view all the answers

What are the two distinct parts of the pre-commissioning inspections and tests?

<p>Detailed inspection and General inspection (D)</p> Signup and view all the answers

Which of the following standards should be considered during preparations for commissioning?

<p>Comprehensive statutory rules and relevant specifications (C)</p> Signup and view all the answers

Which element is NOT included in the major heads outlined for detailed preparation work in Railway Electrification?

<p>Control systems (D)</p> Signup and view all the answers

What is the primary focus of the chapter's outlined preparations for commissioning?

<p>Technical aspects requiring attention before energization (D)</p> Signup and view all the answers

What is the significance of amendments to rules and standards during pre-commissioning preparations?

<p>They ensure that outdated information does not compromise safety (A)</p> Signup and view all the answers

Which of the following does not form part of the legal framework for ensuring the safety of railway electrification?

<p>Banking and Finance Codes (A)</p> Signup and view all the answers

How should the procedures indicated in the manual be approached during preparations for commissioning?

<p>They are mere suggestions and may require modifications according to latest standards (D)</p> Signup and view all the answers

What condition must be evaluated to ensure the proper sealing of a cabinet in a substation?

<p>Insect-proof status (A)</p> Signup and view all the answers

What must be checked to ensure isolators operate correctly?

<p>The smooth movement and full contact of switch blades (D)</p> Signup and view all the answers

What should be examined on the potential transformers (PT) to ensure proper functioning?

<p>The oil level and dielectric strength (B)</p> Signup and view all the answers

Which component connection is critical for lightning arrestors to function properly?

<p>Connection to a reliable earth terminal (D)</p> Signup and view all the answers

What aspect of the isolators needs verification regarding circuit breakers?

<p>Functionality of interlocking mechanisms (C)</p> Signup and view all the answers

Which examination step is essential for ensuring the safety of shielding and earthing in a substation?

<p>Verifying that the area is well screened against atmospheric surges (D)</p> Signup and view all the answers

What is a necessary condition regarding the terminal connections of Current Transformers (CT)?

<p>They must have low resistance measured preferably with a Ductor (A)</p> Signup and view all the answers

During the inspection of lightning arrestors, which condition should specifically be checked?

<p>The presence of hair-line cracks on the porcelain housing (B)</p> Signup and view all the answers

What must be ensured regarding the insulation resistance of transformers?

<p>That it is consistent between primary and secondary (C)</p> Signup and view all the answers

What is a necessary component to ensure that cabin staff understands the purpose of 'Yellow Warning Collars'?

<p>They should be instructed regarding their purpose. (B)</p> Signup and view all the answers

Which statement accurately describes the responsibility of the OHE supervisors?

<p>They are responsible for updating the sectioning diagrams. (A)</p> Signup and view all the answers

What is essential for Station Masters regarding the system of power blocks?

<p>They need to be well-informed about safety precautions related to train movements. (D)</p> Signup and view all the answers

What kind of training format is suggested for Station Masters and related staff regarding the new electrified traction rules?

<p>A short orientation course at the Zonal Training School. (B)</p> Signup and view all the answers

Which steps are taken to ensure the proper operation of protective relays before commissioning?

<p>Laboratory checks, post-installation checks, and confirmatory tests. (D)</p> Signup and view all the answers

What must be confirmed in writing by the staff with respect to new procedures concerning unwired lines?

<p>Their understanding of the operational guidelines. (B)</p> Signup and view all the answers

What is the minimum distance an earthed structure should be from live OHE for safety?

<p>2 m (B)</p> Signup and view all the answers

What factors must be inspected on a 25 kV feeder line before energization?

<p>Tower footing resistance and insulation resistance. (D)</p> Signup and view all the answers

What procedure is recommended after defects are rectified during inspection?

<p>Re-inspection and documentation of repairs. (C)</p> Signup and view all the answers

Which of the following is NOT a requirement for testing protective relays?

<p>Recalibration of meters only after installation. (B)</p> Signup and view all the answers

What should be included in the detailed and general inspection for 25 kV feeder lines?

<p>Ensuring clearances to road and rail crossings are in accordance with approved plans. (B)</p> Signup and view all the answers

What is a critical requirement for the installation of protective relays?

<p>Familiarization with Manufacturers' instruction manuals. (A)</p> Signup and view all the answers

What must every tower be fitted with during a detailed inspection of the feeder lines?

<p>Proper protective devices. (A)</p> Signup and view all the answers

What does the commissioning engineer need to verify about protective relays after they have been energized?

<p>They have been correctly set and function as intended. (D)</p> Signup and view all the answers

What is the primary consequence of an under-rated trip battery circuit fuse?

<p>It is liable to deteriorate and ultimately fail. (C)</p> Signup and view all the answers

What is required to ensure that a battery fuse is adequately protected?

<p>Alarms are provided to alert the operator of failures. (B)</p> Signup and view all the answers

During insulation resistance testing, what should be done with earthing links?

<p>They should be removed prior to testing. (B)</p> Signup and view all the answers

Which component is essential for conducting a primary injection test?

<p>A primary injection set. (C)</p> Signup and view all the answers

What should be the state of fuses in the control circuit regarding their size?

<p>They should be correctly rated, never undersized. (D)</p> Signup and view all the answers

What is the implication of having connections in the trip circuit that are not tight?

<p>It can result in damaged wiring and potential breaks. (A)</p> Signup and view all the answers

What should be monitored when manually closing relay contacts?

<p>Whether the appropriate device has operated. (B)</p> Signup and view all the answers

What type of ammeter is mentioned for use during testing?

<p>Moving coil center-zero type low range ammeter. (B)</p> Signup and view all the answers

What should happen after modifications are made following testing?

<p>Verification from the Manufacturer should be obtained. (A)</p> Signup and view all the answers

Which aspect of the primary injection test's setup is crucial?

<p>Heavy current should be provided at low voltage. (D)</p> Signup and view all the answers

Flashcards

Equipment Condition Check

Inspect equipment for damage, cleanliness, and proper functioning of components like fuses, operation counters, and supports.

Insulator Inspection

Examine insulators for cracks, cleanliness, and smooth manual operation of the isolator.

Isolator Interlocking

Verify proper connection between the circuit breaker and its isolator, and ensure the isolator is grounded independently.

Transformer Insulation

Measure insulation resistance between primary/secondary windings and ground, verifying oil levels (if applicable) and dielectric strength.

Signup and view all the flashcards

Transformer Terminal Connections

Ensure secure and well-made connections to transformers, recording contact resistance (if applicable).

Signup and view all the flashcards

Lightning Arrester Inspection

Visually inspect lightning arrestors for cracks and cleanliness. Ensure proper grounding connections

Signup and view all the flashcards

Substation Shielding

Verify screening conductors protect the substation against surges, grounded firmly to the earth system.

Signup and view all the flashcards

Signal Level Measurement

Measuring and recording signal strength at various points in a communication system.

Signup and view all the flashcards

Individual Frequency Levels

Measuring the strength of each frequency component in the signal.

Signup and view all the flashcards

Receiving Channel Levels

Measuring the signal strength at the receiving end of a channel.

Signup and view all the flashcards

Composite Levels

Measuring the combined signal strength of multiple channels.

Signup and view all the flashcards

Control Centre Level Measurement

Measuring signal levels at the central monitoring point using a Selective Level Meter.

Signup and view all the flashcards

Attenuation Pads

Devices used to reduce signal strength.

Signup and view all the flashcards

Line Impedance

Electrical resistance of a signal transmission line to direct current.

Signup and view all the flashcards

VTVM/TVM 'High' Impedance

Operation of the vacuum-tube voltmeters(VTVM) / Transistorized voltmeters(TVM) in high impedance position for measuring higher signal strengths.

Signup and view all the flashcards

Commissioning

Completing the installation and testing of the equipment to enable the operation.

Signup and view all the flashcards

Porcelain Discs for 132kV

Suspension strings normally use 9 discs, and tension strings use 10 discs for 132 kV power lines. For graded insulation and distances up to 1.6 km from the substation, the number is reduced to 8 for suspension and 9 for tension strings.

Signup and view all the flashcards

Duplicate Strings (Road/Rail)

Extra suspension/tension strings are required for road crossings, and anchor towers with duplicate tension insulators are necessary for railway crossings, adhering to railway crossing regulations.

Signup and view all the flashcards

Insulation Resistance Measurement

Power conductor insulation resistance should be measured between substations using a megger (2500V or 5000V) and must be at least 100 Megaohms.

Signup and view all the flashcards

Continuity Test

A megger continuity tester must be used to confirm the continuous function of each power conductor from substation to substation, and these results must be logged.

Signup and view all the flashcards

Tower Accessories

Towers should have anti-climbing devices, enamelled number plates, and phase-indicating red, yellow, and blue circular discs on terminal towers. Also, danger boards are needed near roads/public.

Signup and view all the flashcards

General Inspection and Energization

After repairs, a joint inspection by the Senior DEE/DEE(TrD), construction organization, and contractor will ensure the installation is ready for energization. Spot checks confirm detailed inspections.

Signup and view all the flashcards

Public Warning for Energization

Warn the public about energization and the risks to trespassers through appropriate channels. Give clear public notices.

Signup and view all the flashcards

Station Transformer Inspection

Detailed inspection of the station transformer, following the same procedures used to inspect the main transformer.

Signup and view all the flashcards

Control Room Requirements

Control room should be clean, well-ventilated, have a strong door, and ample workspace around the control panel for testing.

Signup and view all the flashcards

Battery Room Conditions

Battery rooms must be well-ventilated, protected from dust and moisture, with painted floors and walls.

Signup and view all the flashcards

Battery Support and Protection

Batteries should be supported on teakwood stands, painted with anti-sulfuric acid paint, and rest on porcelain insulators to prevent leakage.

Signup and view all the flashcards

Battery Charging Log Review

Check the battery log book for the first charging period, ensuring adherence to manufacturer's charging rate and cycle instructions.

Signup and view all the flashcards

Battery Gas Containment

Ensure battery gas cannot enter the equipment room to prevent damage.

Signup and view all the flashcards

Battery Plate Condition Check

Inspect plate condition, measure cell specific gravity and cell voltage under load, and check inter-cell connectors for tightness.

Signup and view all the flashcards

Battery Fuse Inspection

Verify the correct capacity of battery fuses and eliminate any risk of supply failure.

Signup and view all the flashcards

Battery Charger Inspection

Inspect battery charger capacity (normal, boost, trickle charge), ensure compliance with specifications, check meters, fuses, and indicating lamps.

Signup and view all the flashcards

Substation Drainage and Access

Substation must have good drainage, all-weather road and rail access, and a well-fenced perimeter with lockable gates.

Signup and view all the flashcards

Traction Transformer and Oil Drainage

Ensure a baffle wall between the traction power transformer and oil drainage arrangements with a soak pit, following IE Rule 64 (2).

Signup and view all the flashcards

MHO relay

A relay used for distance protection in electrical power systems, typically for detecting faults outside a specific distance from the relay location.

Signup and view all the flashcards

Wrong Coupling

A faulty connection between two substations, disrupting intended electrical pathways.

Signup and view all the flashcards

EHV transformer circuit breaker auto-trip

Automatic tripping mechanism designed to cut off power to the transformer in case of an issue with high voltage equipment involved.

Signup and view all the flashcards

Buchholz alarm/trip

A safety device in transformers that detects gas build-up, which typically signifies a fault inside the transformer.

Signup and view all the flashcards

Winding temperature alarm/trip

A system that alerts or automatically cuts off power to prevent overheating of transformer windings.

Signup and view all the flashcards

Oil temperature alarm/trip

A monitoring system that checks transformer oil for overheating.

Signup and view all the flashcards

Low oil trip

An automatic shutdown of the transformer to prevent a catastrophic failure when the oil level drops too low.

Signup and view all the flashcards

25 kV transformer circuit breaker trip

The automatic mechanism that shuts down a circuit breaker that handles electricity at 25,000 volts if a fault or overload is detected.

Signup and view all the flashcards

25 kV feeder circuit breaker trip

A safety device that shuts down the 25,000V feeder circuit breakers when a fault is detected or excessive current flows.

Signup and view all the flashcards

Transformer circuit breaker inter-trip

A system that causes other circuit breakers to shut down when a fault is detected on a transformer circuit breaker that involves other circuit breakers involved in the process.

Signup and view all the flashcards

Control panel instruments

Check all indicating instruments for free movement and accuracy of readings on a control panel.

Signup and view all the flashcards

Relay operation test plugs

Test plugs used to ensure relay operation by checking if they fit correctly.

Signup and view all the flashcards

Indicating lamps

Verify functioning of the lamps. Employ a switch for when unattended to save electricity.

Signup and view all the flashcards

CB tripping in 110 V DC failure

Verify circuit breakers automatically trip when the 110V DC power fails.

Signup and view all the flashcards

Wiring diagram scrutiny

Carefully review control circuit and wiring diagrams, and prepare simplified/functional diagrams to detect potential errors.

Signup and view all the flashcards

Wiring verification

Check the wiring colour code, identifying tags, and the control panel against the approved wiring diagram.

Signup and view all the flashcards

Insulation and continuity tests

Conduct insulation and continuity tests to ensure the wiring's integrity and record the results.

Signup and view all the flashcards

Pre-Commissioning Inspections

Detailed inspections and tests conducted before energizing new railway electrification schemes.

Signup and view all the flashcards

Commissioning

Completing the installation and testing of equipment to enable operation.

Signup and view all the flashcards

Traction Sub-stations

Sections of the railway electrification infrastructure responsible for powering train propulsion.

Signup and view all the flashcards

Transmission lines and 25 kV feeders

Components carrying electric power to the traction sub-stations.

Signup and view all the flashcards

Protective equipment

Safety devices that prevent damage or injury in the system.

Signup and view all the flashcards

Switching Stations

Locations within the electrification system where power paths are controlled and switched.

Signup and view all the flashcards

Remote Control Equipment

Devices that allow control and monitoring of the system's components from a distance.

Signup and view all the flashcards

Overhead equipment

The overhead components of the railway system that provide electricity to trains.

Signup and view all the flashcards

Safety Rules Compliance

Adhering to all relevant Indian laws, regulations, and specifications during commissioning.

Signup and view all the flashcards

Detailed inspection

Thorough checks performed by senior railway officials.

Signup and view all the flashcards

General inspection

Overall checks performed by divisional officers.

Signup and view all the flashcards

Equipment General Condition

Check equipment for damage, cleanliness, proper functioning of components like fuses and operation counters, and the condition of supports.

Signup and view all the flashcards

Insulator Inspection

Examine insulators for surface cracks, cleanliness, and smooth isolator operation (manual).

Signup and view all the flashcards

Isolator Interlocking

Verify proper connections between circuit breaker and isolator, and ensure the isolator is independently grounded.

Signup and view all the flashcards

Current/Potential Transformer Insulation

Measure insulation resistance of primary and secondary windings to earth and between windings. Check oil level & dielectric strength (if applicable).

Signup and view all the flashcards

Transformer Terminal Connection

Verify secure connections for transformers and record contact resistance (if possible).

Signup and view all the flashcards

Lightning Arrester

Inspect lightning arrestors for cracks and cleanliness and ensure proper grounding.

Signup and view all the flashcards

Substation Shielding

Check that screening conductors protect the substation against atmospheric surges, and are properly grounded.

Signup and view all the flashcards

Energizing Transmission Lines

Activating the transmission line after meeting safety requirements, including clearances and protective gear testing.

Signup and view all the flashcards

25 kV Feeder Inspection

Detailed inspection of 25 kV feeder lines, including tower earthing, crossings, and other aspects, similar to how transmission lines are checked.

Signup and view all the flashcards

Protective Relay Testing

Ensuring all protective relays function correctly before commissioning a traction installation, in three stages (lab, installation, and post-energization).

Signup and view all the flashcards

Relay Setting and Calibration

Checking the condition of protective relays, including inspecting for damage, and taking them to the relay testing laboratory for proper functioning.

Signup and view all the flashcards

Relay Contact Closure Check

Manually closing the relay contacts to confirm that the assigned device operates correctly.

Signup and view all the flashcards

Fuse Rating

Control circuit fuses must have the correct amperage rating.

Signup and view all the flashcards

Trip Battery Fuse

The fuse in the circuit powering the trip mechanism.

Signup and view all the flashcards

Oversized Fuses

Fuses slightly larger than required in a control circuit.

Signup and view all the flashcards

Undersized Fuses

Fuses smaller than required for a control circuit.

Signup and view all the flashcards

Primary Injection Test

A test using a primary injection set to check the functionality of windings.

Signup and view all the flashcards

Insulation Resistance

The electrical resistance to ground measured for parts of the system.

Signup and view all the flashcards

Electrification Operational Rules

Rules governing the operation of an electrified railway section, including general and subsidiary rules, and upgraded station working rules for electric traction.

Signup and view all the flashcards

Staff Training

Training for station masters, section controllers, cabin staff, and other categories on the new 25 kV traction rules and procedures, preferably in a Zonal Training School.

Signup and view all the flashcards

Sectioning Diagram

Large-scale diagrams showing the sections, isolating switches, wired/unwired lines, etc. for electrified railway sections, displayed at each station.

Signup and view all the flashcards

OHE Sectioning Diagram

A diagram displaying the overhead line equipment (OHE) sections for the relevant railway section, displayed in the Section Controller's office.

Signup and view all the flashcards

Yellow Warning Collars

Safety equipment used to warn of potential hazard areas; signal cabin staff must be instructed on their purpose, specifically in relation to unwired lines and power blocks.

Signup and view all the flashcards

Power Blocks/Protection

Station Masters and Section Controllers must understand power block systems, longitudinal and cross protection on electrified lines, and precautions for train movements, especially oversize consignments.

Signup and view all the flashcards

Competency Certificates

Station Masters and Assistant Station Masters receive certificates after practical training on operating specific isolators, following TPC instructions.

Signup and view all the flashcards

First Aid for Electrical Shock

First aid boxes and resuscitation charts for electrical shock victims must be available at every station, providing essential safety measures.

Signup and view all the flashcards

Study Notes

Chapter IX: Preparation for Commissioning

  • Prior to commissioning new railway electrification schemes, detailed preparation work is necessary.
  • Instructions for various equipment are issued separately in technical manuals.
  • Key aspects for preparation are outlined in this chapter.
  • Traction sub-stations, transmission lines and 25 kV feeders, protective equipment, switching stations, remote control equipment, and overhead equipment are all major points of focus.
  • The chapter discusses technical aspects for attention during inspections, tests before energization, and commissioning.

20901 Reference to Rules and Statutory Rules

  • Safety of public, railway staff, and property is ensured through strict compliance with various rules.
  • Indian Electricity Act 1910 (latest revision), Indian Electricity Rules (latest edition), Indian Railway Act (amended as needed), General Rules for Indian Railways, associated subsidiary rules, Indian Railways' Schedule of Dimensions, 1935 Rules for Opening of a Railway or Section of a Railway for Public Carriage of Passengers (amended as needed), Bonding and Earthing Code, and relevant IS or IRS specifications and codes of practice for various equipment are all covered.

20902 Pre-Commissioning Inspections

  • Pre-commissioning inspections and tests cover two parts:
  • Detailed inspection at the level of ACE and Senior Subordinates.
  • General inspection at the level of Divisional Officers.
  • These inspections cover all installations and are independent of inspections performed by administrative officers.
  • Relevant officers and staff must be involved in the inspections and verification of work quality during construction.
  • Defects and deficiencies are rectified before transferring sections to the open line.
  • The three categories of defects and deficiencies are vital safety items, non-vital safety items with related serious shortcomings, and less critical issues.

20904 Planning of Power Supply

  • Sub-stations in electric traction require substantial care during erection and commissioning.
  • Careful tests are needed, using reliable and calibrated instruments.
  • Section-by-section energization and partial traction-change commissioning should be adequately planned where needed.
  • Operational order for sub-stations should be decided via consultation to maintain reliable supply to energized sections.
  • The dates when the authorities require power supply must be communicated well in advance to ensure proper scheduling.
  • Sub-station connections and transmission line crossings must be completed beforehand.
  • Distribution of load for electric traction systems across the grid must be balanced to avoid strain.

20905 Commissioning of Traction Transformers

  • Steps for commissioning traction transformers include drying, checking the tap-changer mechanism, verifying transformer bushing condition, ensuring oil tightness, ensuring sufficient oil, and verifying the functionality of Buchholz relay.

20906 Precautions During Commissioning of Traction Transformer

  • Staff should take care to remove all loose articles from clothes, secure tools, and maintain dry conditions to avoid moisture entering during operations.
  • Maintenance of electrical contacts and equipment should also be done.

20907 Tests on Transformer Windings

  • Insulation resistance tests are conducted using a megger at specified temperatures.
  • Insulation resistance values are determined between EHV winding/earth, 25kV winding/earth, and between EHV and 25kV windings.
  • Phasing out tests are used for single phase transformers.

20908 Circuit Breakers and Interruptors

  • Circuit breaker mounting should be vertical and secure.
  • The operating mechanism and roller/bearing movement must be checked for proper functioning.
  • All pins, locking plates and split pins should be secure.
  • Electrical wiring, its insulation and terminal screws must be properly checked for tightness and contact conditions.
  • Functionality of operation /closing solenoids/motors should be tested.
  • Checking of dielectric strength of oil and other maintenance aspects.
  • The porcelain housing condition must be assessed.

20909 Isolators

  • Inspect insulators for cracks and cleanliness.
  • Check operation of switch blades, spring pressure, interlocking mechanisms, and earthing (grounding).

20910 Current and Potential Transformers

  • Check insulation resistance using a megger between primary and secondary winding to earth, and between primary and secondary.

20911 Lightning Arrestors

  • Inspect outer porcelain housings (looking for cracks or chips).
  • Ensure that earth connections to lightning arrestors are solid and direct.
  • Connection to the general earthing grid, and to an independent earth electrode.

20912 Shielding and Earthing

  • Confirm proper protection and metallic casings connectivity.
  • Ensure correct neutral terminals connection to the substation earthing grid and comply with "Code for Earthing Power Supply Installations" (Appendix 111).

20913 Busbars and Insulators

  • Visual inspection for cracks and any paint marks.
  • Confirm smooth and clean contact surfaces for current carrying joints and pressure, suitable for different metals.

20914 Clearances

  • Minimum clearances are defined for live equipment in different conditions (e.g., still air, maximum temperature).
  • Measures, such as fencing and safety procedures, are necessary within a workplace

20915 Auxilaiary Power Supply for Traction Substations & Control Room

  • Consideration for a 3-phase, 415/240 V, 50Hz supply of 100 kVA to meet power needs at the substation and control room, if possible.

20916 Batteries & Battery Charger

  • Ensure battery room has good ventilation, protection from dust and moisture.
  • Battery plates conditions are inspected(including the specific gravity of each cell and voltage across each cell on load. ).
  • Check for proper functioning of battery charger capacity, indicating lamps and earths.

20917 General

  • Substation area inspections to ensure proper drainage, roads, rail access, fences, and oil drainage arrangements.
  • Correct numbering schemes for transformers, isolators, circuit breakers, feeders and correspondence in control panels, and on the mimic diagram board must be verified.

20918 General Inspection of Substations and Commissioning

  • Confirming defects and deficiencies rectification.
  • Joint inspections, by the related departments, are performed before energization.
  • Inspections of equipment, including protective relays, and the care taken during erection.
  • Compliance with Indian Electricity Act and Rules.

20919 Detailed Inspection of Transmission Lines

  • A joint-effort inspection is done once contractors declare a section ready regarding the critical installation elements.
  • Inspection team includes ACE (TrD), construction/contractor staff, and railway representatives.
  • Any defects are noted, and rectification should be promptly addressed to ensure timely energization.

20920 Compliance with Rules and Approved

  • Detailed compliance with Indian Electricity Act and Indian Electricity Rules.
  • Conformity with specific specifications and sag/tension charts for clearances.

20921 Visual Inspection

  • Visual inspection of masts(checking for defects or damage - paint and other elements)
  • Testing the integrity and cleanliness of insulators.
  • Checking tightness of bolts and nuts, and other installation elements including any necessary painting.
  • Measurements of tower footings to meet minimum requirements and sag of earth wires and conductors.

20922 Clearances and Sag

  • Clearances for different locations, like open routes, roads, and accessible areas, between live conductors and earth /various structures are mandatory.

20923 Earthing

  • Correct and individual earthing connections for each tower with a maximum resistance of 10 ohms.

20924 Insulators and Insulation Resistance

  • Visual inspections for chips, cracks, cleanliness, and arcing/horns on insulators are mandatory at prescribed intervals or distances along line and from stations.
  • Measurements of insulation resistance using 2500 V to 5000 V megger are required with specific values given.

20925 Continuity Test

  • Continuity testing across each conductor is done, and the results are documented.

20926 Accessories

  • Checking and confirming that each tower has the necessary accessories (enamelled number plates, circular discs, and danger boards)

20927 General Inspection and Energization

  • Inspections by Sr. DEE/DEE(TrD) and relevant construction/contractor staff.
  • Ensuring proper working conditions for the installation and tele-command signals.
  • Verification and documentation of earlier inspections.

20928 25 kV Feeders

  • Inspection of 25kV line elements(such as towers, isolation elements, etc.) and through continuity.
  • Checking clearances, comparing this with the planned/approved drawings.

20929 Testing of Protective Relays

  • Equipment testing before commissioning.
  • Three stages: prior-to-installation checks, post-installation and commissioning checks and confirmatory checks.
  • Checking of all relays on the equipment for their correct operation.
  • Ensuring correct operation during various circumstances.
  • Checking relay functioning in the laboratory followed by commissioning and final checks after energization.

20930 Inspection of Setting of Relays and Calibration of Meters

  • Checking of relay functionality with specific settings.
  • Documentation of testing settings and calibration data.
  • Correct relay operation for current and potential coils is crucial for proper functioning.

20931 Protective Devices at Sub-stations

  • The types of protective devices to be checked in each electrical transformer station are: Differential protection, Restricted earth fault protection for EHV, 25 kV sides; Buchholz relay, Winding temperature protection and Oil temperature protection
  • Indicating devices, such as oil level indicator for low oil levels
  • Indicators for winding/oil temperature are present on the control panels for monitoring.

20936 Primary Injection Test

  • Primary injection tests are carried out to ensure overall soundness of the circuits; including appropriate connections for testing

20937 Voltage Transformer Ratio and Polarity Check

  • Procedures are described to confirm voltage transformer ratio and polarity using standard methods.

20938 Electrical Operation of Indicators and Associated Devices

  • Checks for proper functioning of shunt-connected indicators, annunciators, auxiliary elements and (DC/Master) relays for specified minimum voltage levels.

20939 Secondary Injection Test

  • Testing of relay settings including operating times and minimum closing values for induction/instantaneous armature, directional relays etc., and their characteristics.

20940 Alarm and Trip Check

  • Ensure appropriate (fuse) circuits operate according to plan.
  • Relay operations (manual and automatic) must be validated with alarm/trip indications.

20941 Load Test

  • Final validation of voltmeter and ammeter operation when normal load currents are passed.
  • Evaluating performance of differential (Protection) circuits under external/internal fault conditions.
  • Check polarity of CT and PT for correct operation

20942 Confirmatory Test of OHE Protective Relays

  • Tests under de-energized conditions to confirm relay operation during fault scenarios.

20943 Power Supply

  • Power supply for switching stations is sourced from 10kVA transformers.
  • Voltage records of transformers is mandatory.

20944 Installation of Equipment

  • Interruptors, isolators, busbars, lightning arresters, wiring, batteries, and their chargers are included in checks.
  • Minor differences in installations within switching stations.

20945 Clearances

  • Live conductor clearances above ground level for 25 kV.
  • Minimum distances between live and earth/earthed parts.
  • Clearance parameters regarding safety and operation of electrical equipment

20946 Auxiliary Transformers & Booster Transformers

  • Inspections and tests of (auxiliary/booster) transformers as per prescribed procedures

20947 General

  • Fencing, gates and safety features for switching stations should be examined.
  • Verify that the ground around the equipment is properly drained and leveled.
  • Ensure accessibility for maintenance works at all locations.

20948 Interlocking

  • Validate correct operation of double-pole isolators, combined with interlocks, and their position indication locks and RC control circuits to prevent accidental operation during critical conditions.

20949 Feeding Posts

  • Verification of proper relay operation and safety during different scenarios (such as low voltage/faults) and emergency feeds

20950 Number Plates and Boards

  • Ensure verification of the numbering of equipment (interruptors, isolators, etc.) with control panel schematics and diagrams.
  • Presence of and conformity with safety, warning, and clearance boards for personnel and public.

20951-20965

  • Earthing/bonding of structural steel and equipment.
  • Insulation resistance testing, continuity checks and checks for correctness of connections in different location(s).
  • Verification and maintenance checks of various relay systems and control equipment along with their corresponding indicators.
  • Preparation and procedures for operating electrified services and testing with live conditions.
  • Divisional Officers' inspection and certificate of conformity for proper functioning of installations prior to commencement/start of service.

Studying That Suits You

Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

Quiz Team

Related Documents

More Like This

Electrical Connections for Rail Jumper
80 questions
Railway Project Surveys and Estimates
79 questions
Railway Electrification Survey
81 questions

Railway Electrification Survey

ScenicHummingbird6529 avatar
ScenicHummingbird6529
Use Quizgecko on...
Browser
Browser