Power Supply Systems for Signalling Installations
80 Questions
0 Views

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to lesson

Podcast

Play an AI-generated podcast conversation about this lesson

Questions and Answers

What is the normal power supply voltage for signalling installations as per the guidelines?

The normal power supply voltage for signalling installations is 230 V AC (single phase) or 415 V AC (three phase).

What role do secondary batteries play in the power supply system for signalling circuits?

Secondary batteries are provided for signalling circuits to ensure functionality in case the main power supply fails.

How does the power supply system ensure that fixed stop signals remain operational?

The power supply system is designed so that fixed stop signals do not become blank when the main power supply fails.

In railway electrified areas, how is the electric supply for signalling installations typically provided?

<p>The electric supply is normally provided through Auxiliary Transformers (ATs) by tapping into the 25 KV OHE.</p> Signup and view all the answers

What measures are taken to ensure power supply in case of a power block on double/multi line sections?

<p>It is ensured that supply from at least one Auxiliary Transformer (AT) is available during a power block.</p> Signup and view all the answers

Why is a DG set required in single line sections of the power supply system?

<p>A DG set of suitable capacity is installed to provide backup power when the supply is drawn from a single Auxiliary Transformer.</p> Signup and view all the answers

What is the purpose of installing DG sets in big yards in addition to the supply from ATs?

<p>DG sets are installed to provide additional power capacity and serve as a backup supply alongside Auxiliary Transformers.</p> Signup and view all the answers

What features are provided at the power supply control panel as specified in the guidelines?

<p>The power supply control panel is equipped with facilities for automatic changeover between different source supplies.</p> Signup and view all the answers

What kind of change over facility is provided in the power supply control panel?

<p>A manual change over facility is provided.</p> Signup and view all the answers

What is the role of the Electrical Department regarding the power supply control panel?

<p>The Electrical Department is responsible for providing and maintaining the power supply control panel and associated arrangements.</p> Signup and view all the answers

How is power supplied to locations farther than two kilometers from the control panel?

<p>A separate set of Automatic Switches (ATs) and a power supply control panel shall be provided.</p> Signup and view all the answers

What is required for the operation of the Diesel Generators (DG sets) in case of remote management?

<p>DG sets shall be provided with push button start/stop facilities.</p> Signup and view all the answers

In a non-railway electrified area, what is the main source of power supply for Colour Light Signalling installations?

<p>Local power supply is used as the main source of supply.</p> Signup and view all the answers

How are solar panels utilized in signalling installations?

<p>Solar panels may charge a battery bank for integrated power supplies or signal lighting using inverters.</p> Signup and view all the answers

What is included in the power supply arrangement at the ASM office?

<p>The output supply from generators and local supply is connected to an auto/manual change-over panel.</p> Signup and view all the answers

What features should the standby diesel generators possess?

<p>Generators should be of standard make and of adequate capacity for reliable service.</p> Signup and view all the answers

What are the main components of a solar photovoltaic system?

<p>The main components are the Solar Array, Battery bank, Solar charge controller, Field junction box, Solar Module Mounting Structure, Earthing Kit, and Cables.</p> Signup and view all the answers

How should the number of solar panels for installation be determined?

<p>The number of solar panels should be based on the requirement of charging current and voltage.</p> Signup and view all the answers

What regular maintenance is recommended for solar panels?

<p>Regular cleaning of the solar panels' surface is recommended to remove dust.</p> Signup and view all the answers

What protection devices should be used in the power supply distribution system?

<p>Proper capacity HRC fuses or Miniature Circuit Breakers (MCBs) should be provided for protection against overload and short circuits.</p> Signup and view all the answers

What type of power supply is to be distributed for various equipment, and how?

<p>A 230 V power supply, selected from the auto/manual change-over panel, is distributed through a distribution panel.</p> Signup and view all the answers

What equipment should be procured as per approved specifications in power supply systems?

<p>Battery chargers, transformers, voltage regulators, transformer-rectifier sets, inverters, and batteries should be procured as per approved specifications.</p> Signup and view all the answers

What features should battery chargers for axle counters include?

<p>They should have in-built filters to maintain ripple content below a specified value.</p> Signup and view all the answers

What additional power equipment may be needed as a standby?

<p>Standby power equipment such as battery chargers, transformers, voltage regulators, and transformer-rectifier sets may be provided.</p> Signup and view all the answers

What type of DC-DC converters are allowed for obtaining different voltages from a common battery bank?

<p>Only approved types of DC-DC converters with isolated outputs are permitted.</p> Signup and view all the answers

What kind of power supply system should be used at CLS installations?

<p>An integrated power supply system of approved type must be used.</p> Signup and view all the answers

How should maintenance-free cells be charged?

<p>They should be charged only with chargers suitable for maintenance-free cells as per approved specifications.</p> Signup and view all the answers

What is the formula for deriving the current rating of a battery charger?

<p>The current rating of the charger equals the load current plus $AH/10$ capacity of the cell.</p> Signup and view all the answers

What requirements are placed on the battery room environment?

<p>The battery room must have acid-proof flooring, acid-proof tiles, be well-ventilated, and have exhaust fans.</p> Signup and view all the answers

What should be done to ensure the proper installation of batteries?

<p>Batteries should be installed in a separate area away from heat sources, on insulated surfaces, and with adequate clearance.</p> Signup and view all the answers

What protective measures should be taken for battery racks?

<p>Racks should be protected with acid-resistant paint and mounted on approved insulators.</p> Signup and view all the answers

What is required for the arrangement of batteries in a storage area?

<p>Batteries should be kept properly aligned, suitably numbered, and have adequate clearance between cells.</p> Signup and view all the answers

What should the initial charging of batteries conform to?

<p>The initial charging of batteries shall be done as per the manufacturer's instructions.</p> Signup and view all the answers

What type of container should be used for mixing battery grade sulfuric acid with water?

<p>Only a glass, porcelain, rubber, or other acid-proof container should be used.</p> Signup and view all the answers

In what order should acid and water be mixed for battery electrolyte preparation?

<p>Acid should always be added to water.</p> Signup and view all the answers

What should be monitored when receiving charged secondary cells?

<p>The level of electrolyte should be noted; if below the prescribed level, it may need replacement.</p> Signup and view all the answers

What is the maximum allowable voltage loss in wires connecting power equipment?

<p>The maximum allowable voltage loss is 0.5%.</p> Signup and view all the answers

What type of battery leads should be used, and how should they be identified?

<p>Battery leads should be color-coded (Red for positive, Black for negative, Green for earth).</p> Signup and view all the answers

Who is responsible for maintaining records of capacity tests upon installation?

<p>An official not below the rank of SSE/JE (Signal) shall maintain the records.</p> Signup and view all the answers

What kind of power supply arrangement is desirable at large stations?

<p>A ring main type of power supply arrangement is desirable.</p> Signup and view all the answers

What conditions must be met for a power supply scheme to differ from the standard Railway Board/RDSO guidelines?

<p>Approval from the Principal Chief Signal and Telecommunication Engineer is required.</p> Signup and view all the answers

How should power supply be structured in double/multi line sections to ensure reliability during a power block?

<p>The power supply should be drawn from Auxiliary Transformers on both up and down OHE lines.</p> Signup and view all the answers

What is the primary reason for installing a DG set on a single line section's power supply system?

<p>To provide a backup power source in case the single Auxiliary Transformer fails.</p> Signup and view all the answers

Why is it necessary to have adequate capacity secondary batteries for signalling applications?

<p>They ensure continuous operation of signals during main power supply failures.</p> Signup and view all the answers

In big railway yards, what additional power supply solution is implemented alongside Auxiliary Transformers?

<p>Diesel Generators (DG sets) of adequate capacity are installed.</p> Signup and view all the answers

How is the power supply managed at stations equipped with local power sources?

<p>Local sources act as a standby power supply when the main source is unavailable.</p> Signup and view all the answers

What key feature should a power supply control panel offer in signalling installations?

<p>It should facilitate automatic changeover between different power sources.</p> Signup and view all the answers

What is the maximum voltage variation allowed in the wires connected to power equipment as per the guidelines?

<p>The maximum allowable voltage loss is unspecified but it should be minimized to ensure efficiency.</p> Signup and view all the answers

What factors influence the decision on the number of solar panels to install?

<p>The decision is based on the requirement of charging current and voltage.</p> Signup and view all the answers

What essential maintenance task should be performed on solar panels?

<p>Regular cleaning should be done to remove dust from the surface of the solar panels.</p> Signup and view all the answers

What types of devices should be included to protect the power supply distribution system?

<p>HRC fuses and Miniature Circuit Breakers (MCBs) should be included for protection.</p> Signup and view all the answers

What visual aids are important for the personnel monitoring the power supply?

<p>Visual indications showing the availability of power supplies from various feeders are important.</p> Signup and view all the answers

What specifications must be followed when procuring power supply equipment?

<p>All power supply equipment must be procured as per approved specifications.</p> Signup and view all the answers

What specific feature must battery chargers for axle counters possess?

<p>Battery chargers must have in-built filters to maintain ripple content below a specified value.</p> Signup and view all the answers

What types of additional equipment may be considered as standby for power supply systems?

<p>Standby equipment may include battery chargers, transformers, and voltage regulators.</p> Signup and view all the answers

How should power supply from the auto/manual change-over panel be distributed?

<p>Power supply should be distributed through underground power cables of approved type.</p> Signup and view all the answers

What is the primary purpose of using a separate transformer for feeding signals and track feed chargers?

<p>To isolate the signal power supply from the charger, preventing interference and ensuring stable signal integrity.</p> Signup and view all the answers

Describe the required environment for the installation of secondary cells in battery rooms.

<p>Battery rooms must have acid-proof flooring, proper ventilation, and be free from direct sunlight and heat sources.</p> Signup and view all the answers

How must batteries be aligned and numbered during installation?

<p>Batteries should be properly aligned with adequate spacing between cells and clearly numbered for easy identification.</p> Signup and view all the answers

What factors should be considered when determining the current rating of a battery charger?

<p>The current rating should include both the load current and one-tenth of the ampere-hour capacity of the cell.</p> Signup and view all the answers

What precautions should be taken when installing racks for batteries?

<p>Racks must be insulated, painted with acid-resistant paint, and positioned for easy access and maintenance.</p> Signup and view all the answers

What type of power supply system is mandated for CLS installations?

<p>An integrated power supply system of an approved type is required for CLS installations.</p> Signup and view all the answers

Why should maintenance-free cells only be charged with specific chargers?

<p>Chargers must be suitable for maintenance-free cells to ensure compatibility and prevent damage during charging.</p> Signup and view all the answers

What is the significance of ventilation in the battery room?

<p>Ventilation prevents the accumulation of harmful fumes that can damage equipment and pose safety risks.</p> Signup and view all the answers

What specific type of acid must be used as an electrolyte when charging batteries?

<p>Battery grade sulphuric acid conforming to IS 266.</p> Signup and view all the answers

What is the proper procedure for mixing sulfuric acid and water for battery electrolyte?

<p>Always add acid to water while stirring to keep the temperature below 50°C.</p> Signup and view all the answers

Which types of containers are acceptable for mixing battery electrolyte?

<p>Containers made of glass, porcelain, rubber, or any acid-proof material.</p> Signup and view all the answers

What should be done if the electrolyte level of charged secondary cells is below the prescribed level?

<p>Restore the level by adding battery grade acid of the recommended specific gravity.</p> Signup and view all the answers

What must be done after receiving charged secondary cells regarding the electrolyte?

<p>Note the level of the electrolyte and check for spillage during transit.</p> Signup and view all the answers

What is the recommended maximum voltage loss allowed in wires connecting power equipment?

<p>No more than 0.5% loss in voltage.</p> Signup and view all the answers

What type of personnel is required to maintain records of the capacity test during installation?

<p>An official not below the rank of SSE/JE (Signal).</p> Signup and view all the answers

What color coding is used for battery leads, and what does each color represent?

<p>Red for positive, Black for negative, and Green for earth terminal.</p> Signup and view all the answers

Explain the significance of using separate MCBs for various S&T locations connected to the power supply control panel.

<p>Separate MCBs ensure that each S&amp;T location can be independently controlled and protected from overloads or faults, enhancing safety and reliability.</p> Signup and view all the answers

What is the role of the Automatic change-over switch in IB Signals power supply?

<p>The Automatic change-over switch allows for seamless transition between different power supply sources to ensure continuous operation of IB Signals.</p> Signup and view all the answers

How does the installation of solar panels contribute to power supply in signaling applications?

<p>Solar panels provide a renewable energy source that can charge battery banks, supplying necessary power for signaling and telecommunications.</p> Signup and view all the answers

What conditions must be met for the installation of standby diesel generators in non-railway electrified areas?

<p>The generators must be of standard make, have adequate capacity, and ensure reliable and trouble-free service.</p> Signup and view all the answers

Describe the procedure for extending power supply to locations beyond two kilometers from the control panel.

<p>For locations over two kilometers, a separate set of Automatic Transfers (ATs) and a power supply control panel must be established.</p> Signup and view all the answers

What is the importance of remote operation capability for Diesel Generators (DG sets)?

<p>Remote operation capability allows for convenient management and control of DG sets, enhancing accessibility and response times.</p> Signup and view all the answers

Identify the key components required for the solar photovoltaic system installation at wayside stations.

<p>The key components include solar panels, battery banks, and inverters to process and store the energy generated.</p> Signup and view all the answers

Discuss the impact of using local power supply as the main source in Colour Light Signaling installations.

<p>Using local power supply reduces dependency on external sources, enhancing efficiency and reliability in signal operations.</p> Signup and view all the answers

Study Notes

Power Supply Systems for Signalling Installations

  • Power supply for signalling installations is to be in accordance with policy, from the Principal Chief Signal and Telecommunication Engineer of the Railway.
  • Secondary batteries are required for signalling circuits at all locations.
  • Standard power supply is either 230V AC (single-phase) or 415V AC (three-phase).
  • Fixed stop signals must not go blank if the main power source fails.
  • Approved secondary batteries with adequate capacity are necessary.

Sources of Power Supply in Electrified Areas

  • Electric supply for signalling and telecommunication installations in electrified areas is normally from Auxiliary Transformers (ATs), which tap 25KV overhead electric lines (OHE).
  • Double/multi-line sections use ATs located on both up and down OHE lines, with one AT on each line as backup (in case of a power block).
  • Single-line sections use a single AT and a backup diesel generator (DG) set with appropriate capacity.
  • If local power is available, it acts as a backup.
  • In large yards, DG sets are used in addition to ATs and local sources.
  • All power supplies from ATs, local sources, and DGs are routed to a control panel at the office/cabin or LC gate.
  • The panel enables automatic switchover between different power sources.
  • Manual switchover is also available.

Power Supply in Non-Electrified Areas

  • Colour Light Signalling (CLS) installations use local power as the main source with two standby diesel generators for backup.
  • The generators' output and local supplies feed a control panel, compatible with electrified area arrangements, in the ASM office.
  • Solar Photovoltaic systems/panels are an approved option for power supply at remote locations.

Power Supply Distribution

  • Power distribution to installations and cabins occurs through underground cables.
  • High-capacity fuses (HRC fuses) or Miniature Circuit Breakers (MCBs) are used for overload/short-circuit protection.
  • Clear visual indicators show power supply availability from various feeders.
  • A panel distributes 230V power to various devices (IPS, transformers, rectifiers, battery chargers, etc.).
  • Surge protection devices (lightning and overloads) are provided for equipment safety.
  • Optional Data Loggers can monitor power supply for record keeping.

Power Supply Equipment

  • Essential equipment includes battery chargers, transformers, voltage regulators, inverters, batteries, etc.
  • Battery chargers have in-built filters to reduce ripple content.
  • Standby equipment (battery chargers, transformers, etc.) can be used
  • DC-DC converters or integrated systems may be used for different voltages.
  • Maintenance-free cells used with suitable chargers/maintenance per specifications.

Installation of Secondary Cells

  • Use approved secondary cells in a separate, well-ventilated room with acid-proof flooring.
  • Avoid direct sunlight and heat sources near cells.
  • Ensure proper ventilation.
  • Adequately number & arrange cells.
  • Use the proper electrolyte (sulfuric acid, water) correctly, following manufacturer's instructions.
  • Install and maintain batteries per specific parameters and use required tools.

Power Supply Equipment Maintenance

  • Operators must ensure power supply equipment (change-over panels, DC-DC converters, etc.) is in good working order.
  • Periodic checks of modules, switches, fuses, and meters are required.
  • Maintain detailed records of voltage and load current for all equipment.
  • Annual insulation testing of transformers using a specific voltage.

Diesel Generator (DG) Set Maintenance

  • A suitable location is required with a proper foundation for DG sets.
  • Mount on anti-vibration pads for noise and vibration reduction.
  • Check all electrical connections and ensure they are secure.
  • Monitor and maintain electrolyte levels in the batteries.
  • The periodic maintenance of the DG set involves cleaning fuel tanks and other parts and using specific tools.
  • Maintenance should be performed by trained mechanics and personnel.
  • Check for leaks in fuel hoses, radiator hoses, and other parts.
  • Periodic performance testing.

Other Important Notes

  • All equipment should be properly labelled and documented.
  • Maintain comprehensive logs of all maintenance work, tests, and operations.
  • Follow all safety procedures for working with power equipment.

Studying That Suits You

Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

Quiz Team

Description

This quiz covers the essential aspects of power supply systems used for signalling installations in railway systems. It examines the standards and requirements for both primary and secondary power sources, including the roles of transformers and backup systems. Test your knowledge on the policies and technical specifications related to these crucial components.

More Like This

Power Supply Basics
8 questions

Power Supply Basics

SincereFrenchHorn avatar
SincereFrenchHorn
Power Supply Unit and Electrical Concepts
30 questions
Power Supply and Indian Railways
8 questions
Power Supply Systems for Signalling Installations
80 questions
Use Quizgecko on...
Browser
Browser