Plant Operation Modes Quiz
12 Questions
0 Views

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to Lesson

Podcast

Play an AI-generated podcast conversation about this lesson

Questions and Answers

What is the first step to start the plant operation?

  • Switch on the lube pump for refrigeration package operation
  • Select the Manual mode for the respective compressor (correct)
  • Initiate the 'Ready to Start' signal to LCP
  • Start the respective compressor through the auto mode

How is the 'Ready to Start' indication lamp verified before starting the compressor?

  • By pressing the Load/Unload push buttons on LCP
  • By energizing/de-energizing solenoid valves
  • By switching on the lube pump
  • By ensuring necessary cooling water flow (correct)

What type of logic is considered for ESD interlocks in critical loops?

  • 2oo2
  • 1oo3
  • 2oo3 (correct)
  • 1oo2

How does the operator load/unload the compressor in Manual mode?

<p>By pressing Load/Unload push buttons on LCP (C)</p> Signup and view all the answers

What action follows after satisfying all the interlocks before starting the compressor?

<p>Initiating 'Ready to Start' signal to LCP (B)</p> Signup and view all the answers

Which push buttons are used by the operator to load/unload the compressor in Manual mode?

<p>(Field) Load / Unload push buttons (B)</p> Signup and view all the answers

What initiates the Loading / Unloading of the compressor in Auto Mode?

<p>MEG Outlet Temperature (B)</p> Signup and view all the answers

What is the consequence if the Actual Differential Oil Pressure falls below 1.5 Kg/cm2g?

<p>ESD tripping of the system (A)</p> Signup and view all the answers

How does the system ensure that the lube oil pump starts before the compressor in Manual mode?

<p>Operator's manual action (B)</p> Signup and view all the answers

Which parameter interlocks the secondary seal cooling pump to prevent its start?

<p>Discharge pressure + Differential Oil Pressure (C)</p> Signup and view all the answers

What prohibits the compressor from starting between two successive startups?

<p>Startup timer (B)</p> Signup and view all the answers

When should the standby lube oil pump be started manually?

<p>In case of Actual Differential Oil Pressure below 2.0 Kg/cm2g (B)</p> Signup and view all the answers