Philippines Electronics Code Book 2: Fire Alarms
32 Questions
0 Views

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to Lesson

Podcast

Play an AI-generated podcast conversation about this lesson

Questions and Answers

What is the minimum required audible alarm level in a building where fire alarm systems are installed?

  • 75 dbA
  • 65 dbA (correct)
  • 70 dbA
  • 50 dbA

What color are manual fire push or pull stations typically?

  • Red (correct)
  • Green
  • Yellow
  • Blue

In which of the following facilities is a one-way emergency voice alarm communication sub-system required?

  • Buildings with less than 15 floors
  • Residential buildings with floor area less than 25,000 sq.m
  • Private homes
  • Transportation terminals (correct)

What is the required capacity for the secondary power supply for fire alarm systems?

<p>24 hours (D)</p> Signup and view all the answers

Who is responsible for preventing false alarms in fire alarm systems?

<p>The owner of protected structures (C)</p> Signup and view all the answers

What type of communication sub-system is required for a system with an FACP of more than 10 zones?

<p>Two-way telephone communication sub-system (B)</p> Signup and view all the answers

Which of the following requirements must be followed for the installation of fire alarm systems?

<p>Installation must comply with the Philippine electrical code (C)</p> Signup and view all the answers

What is the operating voltage for the primary power supply of fire alarm systems?

<p>220 - 240 VAC single phase (B)</p> Signup and view all the answers

What is the primary focus of the code regarding fire detection and alarm systems?

<p>Design and application of fire detection systems. (D)</p> Signup and view all the answers

Which of the following areas is explicitly mentioned as requiring fire detection?

<p>Above drop ceilings greater than 1 meter. (D)</p> Signup and view all the answers

What characterizes an addressable device in fire detection and alarm systems?

<p>It can be individually identified or controlled. (D)</p> Signup and view all the answers

Which of these statements correctly identifies a conventional device?

<p>It lacks an electromechanical or software address. (B)</p> Signup and view all the answers

Which function is NOT included in the requirements for fire detection and alarm systems?

<p>Routine repair of fire-suppression systems. (D)</p> Signup and view all the answers

What should be inferred about the term 'shall' as used in the code?

<p>It indicates a mandatory requirement. (C)</p> Signup and view all the answers

Which statement about areas that do not require fire detection is accurate?

<p>Toilets less than 4 sq.m. do not need detection. (C)</p> Signup and view all the answers

What is a significant requirement for all FDAS installations according to the code?

<p>They must comply with the minimum performance levels. (A)</p> Signup and view all the answers

What type of smoke detector should be used for ceilings higher than 6 meters?

<p>Beam-type smoke detector (B)</p> Signup and view all the answers

In which of the following conditions should smoke detectors NOT be installed?

<p>In rooms with temperature below 5°C (D)</p> Signup and view all the answers

Which qualification is required for a FDAS designer?

<p>Registered Professional Electronics Engineer (C)</p> Signup and view all the answers

What is the maximum relative humidity allowed for the installation of heat detectors?

<p>93% (B)</p> Signup and view all the answers

If the total floor area is more than 8000 sq m, which type of fire detection system must be used?

<p>Both B and C (A)</p> Signup and view all the answers

Which type of detector is suitable for detecting carbon monoxide?

<p>Carbon monoxide detector (B)</p> Signup and view all the answers

In what scenario should duct-smoke detectors be installed?

<p>In air ducts of all air handling units (A)</p> Signup and view all the answers

What is the recommended spacing for heat detectors?

<p>Not more than 7.5m apart (A)</p> Signup and view all the answers

What is one of the qualifications required for a person to install FDAS?

<p>Registered Professional Electronics Engineer or Electronics Engineer (A)</p> Signup and view all the answers

Which of the following is NOT a requirement for the installation of wires and cables in FDAS?

<p>Must be underground to prevent exposure (A)</p> Signup and view all the answers

What is included in the final test of the FDAS?

<p>Testing insulation resistance and operation of devices (B)</p> Signup and view all the answers

Who is responsible for entering into a maintenance contract for FDAS?

<p>The owner of the protected building (D)</p> Signup and view all the answers

Which document must be maintained and available at the Fire Command Center?

<p>As-built drawings and operation manuals (D)</p> Signup and view all the answers

What training should a competent person handling FDAS have?

<p>Training in maintaining and testing FDAS (B)</p> Signup and view all the answers

What is the purpose of keeping a log record book for FDAS?

<p>To maintain a record of installation tests and outcomes (D)</p> Signup and view all the answers

When must the installation of the FDAS be inspected after the first year of acceptance?

<p>By an Authority Having Jurisdiction (AHJ) (D)</p> Signup and view all the answers

Flashcards

Addressable Device

A fire detection and alarm system component that can be individually identified or used to control other functions.

Annunciator

A fire detection and alarm system component showing lights or text to show the status of the system.

Conventional Device

A fire detection component (smoke, heat, etc.) without individual identification or control.

Mandatory Requirement

A rule that must be followed, expressed as 'shall' in the code.

Signup and view all the flashcards

FDAS

Fire Detection and Alarm System

Signup and view all the flashcards

Areas Requiring Detection

Spaces like high ceilings, stairwells and tunnels need fire detectors.

Signup and view all the flashcards

Areas Exempt from Detection

Small toilets and bathrooms do not need fire detectors.

Signup and view all the flashcards

Automatic Detection

Fire detection that happens automatically without any human input.

Signup and view all the flashcards

FDAS Component Compatibility

Individual fire detection and alarm system (FDAS) components must be compatible with each other and approved by recognized authorities.

Signup and view all the flashcards

FDAS Designer Qualifications

FDAS designers must be registered Professional Electronics Engineers (PECE) and experienced in FDAS design, application, installation, and testing as verified by IECEP.

Signup and view all the flashcards

Large Building FDAS System

For buildings over 8000 sq m, a semi-addressable or addressable fire detection system is required; otherwise, a conventional system is sufficient.

Signup and view all the flashcards

Manual Detection

A fire alarm system activated manually by a person using push or pull stations, usually red and located at 1.4 meters above the floor.

Signup and view all the flashcards

Indoor Smoke Detector Coverage

Smoke detectors must provide complete indoor coverage of the entire building or facility.

Signup and view all the flashcards

Smoke Detector Installation Restrictions

Smoke detectors cannot be installed in areas below 5°C, above 45°C, or with relative humidity over 93%.

Signup and view all the flashcards

Audible Alarm

An alarm sound that is clearly audible throughout the building, with a minimum sound level of 65 decibels or 10 decibels louder than the background noise.

Signup and view all the flashcards

Visual Notification

A visual signal, such as flashing lights, used along with audible alarms in areas where people wear hearing protection.

Signup and view all the flashcards

Heat Detector Temperature Rating

Heat detectors must be spaced no further than 7.5 meters apart and have a temperature rating at least 11°C above the maximum expected temperature; avoid locations over 93% humidity.

Signup and view all the flashcards

One-Way Emergency Voice Alarm

A communication system allowing announcements to be broadcast but not allowing people to speak back. It's mandatory in several buildings like airports and malls.

Signup and view all the flashcards

High Ceiling Smoke Detectors

For ceilings over 6m, use beam-type smoke detectors that stay clear of any blocking objects.

Signup and view all the flashcards

Duct Smoke Detectors

Air handling units of centralized air conditioning systems must have duct-smoke detectors that are suitable for the expected duct conditions (velocity, temperature, humidity).

Signup and view all the flashcards

Two-Way Telephone Communication

A communication system allowing both sending and receiving of messages. It's required for larger fire alarm systems.

Signup and view all the flashcards

Primary Power Supply

The main source of power for the fire alarm system, typically a direct 220-240 VAC single phase.

Signup and view all the flashcards

Secondary Power Supply

A backup power source for the fire alarm system, capable of providing power for 24 hours.

Signup and view all the flashcards

False Alarm Prevention

The owner of a building with a fire alarm system is responsible for preventing false alarms. Any alarm at the control panel should be treated as a real fire until proven otherwise.

Signup and view all the flashcards

Who can install FDAS?

A registered Professional Electronics Engineer (PECE) or Electronics Engineer (ECE) with experience in installing, maintaining, and testing FDAS, as certified by IECEP.

Signup and view all the flashcards

FDAS Wire Protection

All wires and cables must be protected within conduits, flexible conduits, cable ducts/trays/ladders, or other raceways to prevent damage, corrosion, and fire.

Signup and view all the flashcards

Minimum Wire Gauge

The minimum wire gauge for FDAS wiring is 0.9 sq.mm.

Signup and view all the flashcards

FDAS Testing

FDAS must be tested according to applicable standards, covering insulation resistance, device verification, system operation, initiating device function, and notification device sound pressure.

Signup and view all the flashcards

Final FDAS Test

A final test is performed on the entire FDAS system, based on applicable standards and requirements.

Signup and view all the flashcards

FDAS Documentation

The owner of a protected building must provide operation and maintenance manuals, as-built drawings, a written sequence of operation, a record of completion, and a log record book.

Signup and view all the flashcards

FDAS Maintenance Contract

The owner must contract with the manufacturer, distributor, or a competent contractor for regular maintenance of the FDAS.

Signup and view all the flashcards

FDAS Competent Person

A competent person trained by the manufacturer is required to supervise and handle all aspects of FDAS, including interpreting signals, taking actions, and performing maintenance and testing.

Signup and view all the flashcards

Study Notes

Philippines Electronics Code Book 2: Fire Detection Alarm System

  • This code book outlines requirements for designing, installing, maintaining, testing, and inspecting fire detection and alarm systems (FDAS) in the Philippines.
  • It does not cover fire suppression systems.

Chapter 1: Scope and Fundamentals

  • The code details the design and application of FDAS, including signal initiation, notification, annunciation, emergency communication, and emergency voice evacuation.
  • Automatic fire detection and alarm systems must adhere to the general, design, and installation requirements within this code.

Chapter 2: Design Requirements

  • Components of FDAS must be compatible with each other and approved by relevant institutions.

Chapter 3: Installation Requirements

  • FDAS installation must meet Philippine Electrical Code and Revised Fire Code of the Philippines 2008 requirements.
  • Installation must be performed by qualified personnel (e.g., registered Professional Electronics Engineer [PECE] or Electronics Engineer [ECE]).
  • Wires and cables must be protected in conduits, cable ducts, or similar raceways.
  • System testing is mandatory, along with final acceptance testing.
  • Operating and maintenance manuals must be provided to the user.

Chapter 4: Maintenance, Testing, and Inspection

  • Building owners should contract with a qualified company or individual for routine maintenance.

  • The system must be tested routinely, and documentation of these tests kept.

  • An annual inspection by the AHJ (Authority Having Jurisdiction) is required.

  • Qualified personnel (e.g., registered Professional Electronics Engineer [PECE] or Electronics Engineer [ECE]) are required for this testing and inspection.

  • System designers must adhere to the FDAS design requirements.

  • The owner is responsible for preventing false alarms.

Definition of Terms

  • Addressable Device: A fire detection and alarm system component uniquely identified for status and control.
  • Annunciator: An FDAS component with lamps or an alphanumeric display indicating status.
  • Conventional Device: A component (e.g., smoke detector, heat detector, manual fire alarm station) without a unique address.

Specific Requirements

  • Areas more than 600mm/1m in height under the floor or above raised ceilings need FDAS in the building.
  • FDAS is not required in areas less than 4 sq. meters (toilets, bathrooms etc) and certain other small areas.
  • Automatic fire detection must cover the entire indoor space of the building. -Smoke detectors should not be installed in rooms with temperatures below 5 °C, above 45 °C, or humidity above 93 %.
  • Heat detectors should not be installed above 93% humidity.
  • Beam-type smoke detectors are suitable for ceilings over 6 meters high.
  • Duct-smoke detectors are needed in air conditioning units.
  • Flame detectors selection depends on spectral response matching to the fire type.
  • Carbon monoxide detectors are needed in dwelling units with attached garages and units with installed fuel-burning appliances.
  • Manual detection systems use push/pull stations located 1.4 meters above the floor.
  • Notification appliances should be audible throughout the building, with a minimum of 65 dbA, and visual notification where needed.
  • One-way emergency voice alarm communication is needed in certain facilities (e.g., airports, shopping malls, residential buildings).
  • Two-way telephone communication is needed if there are more than 10 zones in a conventional system or over 200 automatic detectors in an addressable system.
  • The primary power supply to the system needs to be 220-240 VAC single phase.
  • The secondary power supply capacity needs to operate for a minimum of 24 hours.

Studying That Suits You

Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

Quiz Team

Description

This quiz covers the essential aspects of the Philippines Electronics Code Book 2, focusing on fire detection and alarm systems (FDAS). It discusses the design, installation, and maintenance requirements as stipulated in the code, along with related regulations. Testing and inspection procedures are also addressed.

More Like This

Use Quizgecko on...
Browser
Browser