NFPA13-16 Kap 8-8.8

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to Lesson

Podcast

Play an AI-generated podcast conversation about this lesson
Download our mobile app to listen on the go
Get App

Questions and Answers

According to NFPA standards, what is the maximum floor area that can be protected by sprinklers supplied by a single sprinkler system riser for an ordinary hazard occupancy?

  • 75,000 ft² (6968 m²)
  • 40,000 ft² (3720 m²)
  • 52,000 ft² (4830 m²) (correct)
  • 60,000 ft² (5574 m²)

In a multistory building exceeding two stories, what components are typically required at each individual floor level for fire sprinkler systems?

  • Pressure relief valve, flow switch, and check valve.
  • Floor control valve, check valve, and main drain valve.
  • Floor control valve, check valve, main drain valve, and flow switch. (correct)
  • Floor control valve, flow switch, and pressure gauge.

Under what conditions are detached buildings permitted to be supplied by the fire sprinkler system of an adjacent building?

  • When the buildings are separated by less than 10 feet.
  • When acceptable to the authority having jurisdiction. (correct)
  • When both buildings are owned by the same entity.
  • When the buildings are of similar construction type.

What should be done with the protective caps and straps on sprinklers before placing the sprinkler system in service?

<p>Remove them using tools according to the manufacturer’s instructions. (B)</p> Signup and view all the answers

Under what condition is the use of high-temperature sprinklers generally permitted?

<p>Throughout ordinary and extra hazard occupancies and storage occupancies. (C)</p> Signup and view all the answers

According to the standard, what type of sprinkler should typically be used in light hazard occupancies?

<p>Quick-response type sprinklers. (A)</p> Signup and view all the answers

What type of sprinkler is permitted in residential areas installed near specific heat sources?

<p>Sprinklers installed in accordance with specific tables outlining distances and temperature classifications. (B)</p> Signup and view all the answers

What is the primary restriction regarding the installation of sprinklers with a K-factor exceeding K-5.6 and having a 1⁄2 in. NPT in new sprinkler systems?

<p>They shall not be installed. (A)</p> Signup and view all the answers

In what type of construction are extended coverage sprinklers suitable for installation, given specific conditions?

<p>In unobstructed construction consisting of flat, smooth ceilings with a specific slope. (C)</p> Signup and view all the answers

In which type of sprinkler systems are residential sprinklers primarily used?

<p>Wet systems (C)</p> Signup and view all the answers

What is a key requirement for using Early Suppression Fast-Response (ESFR) sprinklers concerning the slope of the roof or ceiling above the sprinklers?

<p>The slope must not exceed a pitch of 2 in 12. (B)</p> Signup and view all the answers

When are draft curtains required when using ESFR sprinkler systems?

<p>When ESFR sprinkler systems are installed adjacent to sprinkler systems with standard-response sprinklers. (C)</p> Signup and view all the answers

What factor determines the temperature ratings for Control Mode Specific Application (CMSA) sprinklers?

<p>The specific requirements of the hazard involved as determined by large-scale fire testing (A)</p> Signup and view all the answers

What is a critical consideration for 'special sprinklers' intended for the protection of specific hazards or construction features?

<p>They should be evaluated and listed for performance under fire tests related to the intended hazard. (C)</p> Signup and view all the answers

When dry sprinklers are connected to wet pipe sprinkler systems protecting areas subject to freezing temperatures, what is the primary consideration for determining the minimum exposed length of the barrel of the dry sprinkler?

<p>The ambient temperature exposed to the discharge end of the sprinkler (B)</p> Signup and view all the answers

According to the standard, how should sprinklers be positioned to ensure adequate protection of an area?

<p>By controlling the positioning and allowable area of coverage for each sprinkler. (A)</p> Signup and view all the answers

What is the formula used to calculate the protection area of coverage of a sprinkler?

<p>AS = S × L (D)</p> Signup and view all the answers

What is critical to consider when determining the maximum distance between sprinklers?

<p>The centerline distance between adjacent sprinklers (B)</p> Signup and view all the answers

When measuring the distance from a sprinkler to a wall, what is the correct method according to the standard?

<p>Measure perpendicular to the wall. (D)</p> Signup and view all the answers

What is the standard's guidance on the alignment of sprinkler deflectors?

<p>They should be aligned parallel to ceilings, roofs, or the incline of stairs. (C)</p> Signup and view all the answers

What is the primary performance objective regarding obstructions to sprinkler discharge?

<p>To minimize obstructions to discharge. (C)</p> Signup and view all the answers

How should sprinklers be installed under fixed obstructions that are over 4 ft wide?

<p>Sprinklers should be installed below the obstruction and not more than 3 in. from its outside edge. (A)</p> Signup and view all the answers

Unless specific conditions are met, what is the general requirement for the clearance between the sprinkler deflector and the top of storage or contents of a room?

<p>18 inches or greater (C)</p> Signup and view all the answers

Under what area condition shall sprinklers be ommitted from skylights regardless of hazard classification?

<p>Skylights not exceeding 32 ft² in area separated by at least 10 ft (D)</p> Signup and view all the answers

When determining the protection area of coverage per sprinkler in a small room, how is the area calculated?

<p>By dividing the area of the room by the number of sprinklers in the room (D)</p> Signup and view all the answers

For standard pendent and upright spray sprinklers in light hazard occupancies with noncombustible unobstructed construction and a hydraulically calculated system, what is the maximum protection area?

<p>225 ft² (B)</p> Signup and view all the answers

In areas with angled or irregular walls, what is the criterion for the maximum horizontal distance between a sprinkler and any point of floor area protected by that sprinkler, relative to the allowable distance between sprinklers?

<p>It should not exceed 0.75 times the allowable distance. (D)</p> Signup and view all the answers

What is the standard minimum distance between sprinklers?

<p>6 ft (C)</p> Signup and view all the answers

What are the requirements that must be met to place sprinklers closer than 6 ft on center?

<p>Installing baffles that meet certain specifications (C)</p> Signup and view all the answers

How should the deflector distance be measured for ceilings that have insulation installed in a manner that causes it to deflect or sag down from the ceiling or roof structure?

<p>Measure as half of the distance of the deflection from the insulation high point to the insulation low point. (D)</p> Signup and view all the answers

According to the standard, what should be the position of the deflector to the ceiling, under unobstructed construction, within the area of coverage of the sprinkler?

<p>A minimum of 1 in. and a maximum of 12 in. (A)</p> Signup and view all the answers

According to NFPA standards, under what situation is it acceptable to supply multiple buildings with a single fire sprinkler riser?

<p>Multiple buildings attached by canopies, covered breezeways, common roofs, or a common wall(s). (D)</p> Signup and view all the answers

For ordinary hazard occupancies, what is the protection area and maximum spacing of standard pendant and upright spray sprinklers?

<p>Protection Area: 130 ft², Maximum Spacing: 15 ft (A)</p> Signup and view all the answers

For extra hazard occupancies with pipe schedule systems, what is the protection area and maximum spacing of standard pendant and upright spray sprinklers?

<p>Protection Area: 90 ft², Maximum Spacing: 12 ft (C)</p> Signup and view all the answers

What is the maximum floor area allowed for the extra hazard area when protected by a single fire sprinkler system that covers both extra hazard and ordinary hazard areas?

<p>Cannot exceed 40,000 ft² (C)</p> Signup and view all the answers

Where solvent cement is used as the pipe and fittings bonding agent, when should sprinklers be installed in the fittings?

<p>Sprinklers shall not be installed in the fittings prior to the fittings being cemented in place. (D)</p> Signup and view all the answers

According to the basic installation requirements for sprinklers, which principle applies regarding their placement?

<p>Sprinklers must be installed throughout the premises to provide satisfactory performance and not exceed maximum protection area. (D)</p> Signup and view all the answers

What is the primary consideration when determining the necessity of sprinklers inside furniture like portable wardrobe units or trophy cases?

<p>Whether the furniture is intended for occupancy. (D)</p> Signup and view all the answers

What is the restriction on an extra hazard area when protected by a single fire sprinkler system that also covers ordinary or light hazard areas?

<p>The extra hazard area must not exceed the floor area specified for that hazard, and the total area coverage must not exceed 52,000 ft2. (C)</p> Signup and view all the answers

What is the primary requirement for the installation of upright sprinklers?

<p>The frame arms must be parallel to the branch line, unless specifically listed for other orientation. (A)</p> Signup and view all the answers

What should be done with protective caps and straps on sprinklers immediately following their installation?

<p>They can be removed from all upright sprinklers or any sprinklers installed more than 10 ft above the floor. (C)</p> Signup and view all the answers

When are ordinary- and intermediate-temperature sprinklers typically used throughout buildings?

<p>When maximum ceiling temperatures do not exceed 100°F, unless specific exceptions are met. (A)</p> Signup and view all the answers

In what situation should sprinklers under glass or plastic skylights be of an intermediate-temperature classification?

<p>If the skylights are exposed to the direct rays of the sun. (A)</p> Signup and view all the answers

When can standard-response sprinklers be used in light hazard occupancies that typically require quick-response sprinklers?

<p>Only when modifications or additions are made to existing light hazard systems equipped with standard-response sprinklers. (A)</p> Signup and view all the answers

In light hazard occupancies, what is a condition related to quick-response sprinklers that requires all sprinklers within a compartment to be quick response?

<p>When quick-response sprinklers are installed, all sprinklers within a compartment must be quick-response unless otherwise permitted. (C)</p> Signup and view all the answers

What is the maximum water pressure at which sprinklers with a nominal K-factor of less than K-5.6 can operate in light hazard occupancies?

<p>7 psi (C)</p> Signup and view all the answers

Under what conditions may sprinklers with nominal K-factors of K-4.2 be installed on dry pipe and preaction systems?

<p>When piping is corrosion resistant or internally galvanized, protecting light hazard occupancies. (D)</p> Signup and view all the answers

What is a general guideline on selecting sprinklers for use as indicated in the standard?

<p>Sprinklers should be selected for use as indicated in the standard and positioned and spaced as described in the spacing requirements. (C)</p> Signup and view all the answers

According to the standard, what is the limitation on using quick-response sprinklers in extra hazard occupancies?

<p>Quick-response sprinklers are not permitted for use in extra hazard occupancies under the density/area design method. (C)</p> Signup and view all the answers

Under what ceiling conditions are sidewall sprinklers typically installed?

<p>Light hazard occupancies with smooth, horizontal or sloped, flat ceilings. (A)</p> Signup and view all the answers

In what type of construction are extended coverage sprinklers suitable for installation under specific conditions, according to standards?

<p>In unobstructed construction consisting of flat, smooth ceilings with a slope not exceeding a pitch of 1 in 6. (C)</p> Signup and view all the answers

Besides deluge systems, in what scenario are open sprinklers permitted to be used?

<p>To protect special hazards or exposures or in other special locations. (C)</p> Signup and view all the answers

What is a key requirement for residential sprinklers concerning their usage in different types of sprinkler systems?

<p>They should be used only in wet systems unless specifically listed for use in dry or preaction systems. (A)</p> Signup and view all the answers

What is a key condition for using ESFR sprinklers regarding the roof or ceiling slope above the sprinklers?

<p>The slope must not exceed a pitch of 2 in 12. (B)</p> Signup and view all the answers

What is a critical requirement when ESFR sprinkler systems are installed adjacent to sprinkler systems with standard-response sprinklers?

<p>A draft curtain of noncombustible construction and at least 2 ft in depth must separate the two areas. (C)</p> Signup and view all the answers

What is a primary factor in determining the temperature rating for CMSA sprinklers?

<p>Sprinkler temperature ratings must be the same as those indicated in specific tables or those used in large-scale fire testing. (D)</p> Signup and view all the answers

What is required for 'special sprinklers' when used for the protection of specific hazards or construction features?

<p>They must be evaluated and listed for performance under fire tests related to the intended hazard. (B)</p> Signup and view all the answers

What is the primary consideration for the minimum exposed length of the barrel of dry sprinklers connected to wet pipe sprinkler systems protecting areas subject to freezing?

<p>The ambient temperature exposed to the discharge end of the sprinkler. (B)</p> Signup and view all the answers

How is the protection area of coverage per sprinkler determined?

<p>By multiplying the S dimension (distance along branch lines) by the L dimension (distance between branch lines). (C)</p> Signup and view all the answers

What is a general rule for the maximum distance from sprinklers to walls?

<p>It should not exceed one-half of the allowable maximum distance between sprinklers. (B)</p> Signup and view all the answers

What should deflectors of sprinklers be aligned parallel to?

<p>Ceilings, roofs, or the incline of stairs. (B)</p> Signup and view all the answers

Where must sprinklers be installed under fixed obstructions over 4 ft in width?

<p>Not more than 3 inches from the outside edge of the obstruction. (D)</p> Signup and view all the answers

What is the general minimum distance between sprinklers to prevent wetting adjacent sprinklers?

<p>6 ft (D)</p> Signup and view all the answers

According to the standard, what conditions must be satisfied to place sprinklers closer than 6 ft on center?

<p>Baffles must be arranged to protect the actuating elements, and these baffles must meet specific size and positioning requirements. (C)</p> Signup and view all the answers

How should the deflector distance be measured for ceilings that have insulation installed in a manner that causes it to sag down from the ceiling or roof structure?

<p>As half of the distance of the deflection from the insulation high point to the insulation low point. (D)</p> Signup and view all the answers

Under unobstructed construction, what is the required range for the distance between the sprinkler deflector and the ceiling?

<p>A minimum of 1 in. and a maximum of 12 in. (A)</p> Signup and view all the answers

According to the basic requirements for sprinkler installation, what principle should guide the spacing, location, and positioning of sprinklers?

<p>Sprinklers should be positioned to achieve optimal activation time and water distribution for satisfactory performance. (B)</p> Signup and view all the answers

In a multistory building that is five stories high, what is the requirement for sprinkler system components at each floor level?

<p>Each floor must have a floor control valve, a check valve, and a flow switch for water flow isolation and control. (A)</p> Signup and view all the answers

Under what condition is it permissible for multiple buildings to be supplied by a single fire sprinkler riser?

<p>If the buildings are attached by canopies, covered breezeways, common roofs, or a common wall(s). (B)</p> Signup and view all the answers

Before a sprinkler system is placed in service, what action must be taken regarding the protective caps and straps on the sprinklers?

<p>Protective caps and straps must be removed from all sprinklers. (C)</p> Signup and view all the answers

In which scenario is the use of high-temperature sprinklers generally considered acceptable?

<p>Throughout ordinary and extra hazard occupancies, storage occupancies, and as allowed in this standard and other NFPA codes and standards. (B)</p> Signup and view all the answers

According to the standard, where are sprinklers with intermediate-temperature classification typically installed?

<p>In specific locations as required by 8.3.2.5 such as near uncovered steam mains or under glass skylights. (C)</p> Signup and view all the answers

What is the acceptable use of standard-response sprinklers in light hazard occupancies requiring quick-response sprinklers?

<p>Only permitted for modifications or additions to existing light hazard systems already equipped with standard-response sprinklers, or for individual replacements. (C)</p> Signup and view all the answers

What is the implication if quick-response sprinklers are installed within a compartment of a building?

<p>All sprinklers within that compartment must be quick-response, unless otherwise permitted. (C)</p> Signup and view all the answers

Under what conditions are sprinklers with K-factors less than K-5.6 permitted in a fire sprinkler system?

<p>They are only permitted if the system is hydraulically calculated and installed only in wet pipe sprinkler systems. (C)</p> Signup and view all the answers

What is the restriction regarding the installation of sprinklers with a K-factor exceeding K-5.6 and having a 1⁄2 in. NPT in new sprinkler systems?

<p>They shall not be installed in new sprinkler systems. (D)</p> Signup and view all the answers

What condition must be met for using sidewall sprinklers?

<p>Sidewall sprinklers shall only be installed in light hazard occupancies with smooth, horizontal or sloped, flat ceilings. (B)</p> Signup and view all the answers

What is a main condition regarding residential sprinklers?

<p>They shall only be used in wet systems unless specifically listed for use in dry systems or preaction systems. (C)</p> Signup and view all the answers

What factor affects the sprinkler temperature ratings for Control Mode Specific Application (CMSA) sprinklers?

<p>Sprinkler temperature ratings shall be the same as those indicated in Table 8.3.2.5(a) and Table 8.3.2.5(b) or those used in large-scale fire testing to determine the protection requirements for the hazard involved. (D)</p> Signup and view all the answers

According to standards, what is important to consider when using ‘special sprinklers’ for specific hazards or construction features?

<p>They need to be evaluated and listed for performance under fire tests related to the intended hazard. (A)</p> Signup and view all the answers

In the context of sprinkler positioning, what is the requirement for sprinkler deflectors?

<p>They must be aligned parallel to ceilings, roofs, or the incline of stairs. (D)</p> Signup and view all the answers

What action is required from sprinklers installed under fixed obstructions that are over 4 ft in width?

<p>Sprinklers must be installed below the obstruction and be no more than 3 in. from the outside edge. (D)</p> Signup and view all the answers

When considering clearance from sprinkler deflectors to storage, what is the generally required minimum clearance?

<p>A clearance of 18 in. or greater between the deflector and the top of storage or contents of the room is required. (B)</p> Signup and view all the answers

Under which area condition are sprinklers permitted to be omitted from skylights, regardless of hazard classification?

<p>If the skylights do not exceed 32 ft2 in area and are separated by at least 10 ft horizontally from any other unprotected skylight or unprotected ceiling pocket. (B)</p> Signup and view all the answers

What is generally the minimum distance between sprinklers?

<p>6 ft (1.8 m) (C)</p> Signup and view all the answers

Flashcards

Sprinkler Installation Requirements

Requirements for spacing, location, and position of sprinklers are based on installing sprinklers throughout the premises, not exceeding maximum protection area, providing satisfactory performance, and allowing omissions as per standard.

System Valve Accessibility

System valves and gauges must be accessible for operation, inspection, tests, and maintenance.

System Protection Area

Limits the maximum floor area on any one floor to be protected by sprinklers supplied by any one sprinkler system riser or combined system riser based on hazard type.

Floor Control Valve Assemblies

Multistory buildings exceeding two stories must have a floor control valve, check valve, main drain valve, and flow switch for each floor level, allowing isolation, control, and water flow annunciation.

Signup and view all the flashcards

Sprinkler Systems in Detached Buildings

Detached buildings require separate fire sprinkler systems unless they meet specific criteria or are approved by the authority having jurisdiction.

Signup and view all the flashcards

Sprinkler Installation per Listing

Sprinklers must be installed according to their listing, unless construction features require unusual water distribution to achieve specific results.

Signup and view all the flashcards

Upright Sprinkler Orientation

Upright sprinklers should be installed with the frame arms parallel to the branch line, unless listed for other orientations.

Signup and view all the flashcards

Sprinkler Protective Caps

Protective caps and straps must be removed from all sprinklers before the sprinkler system is placed in service, following the manufacturer’s instructions.

Signup and view all the flashcards

Sprinkler Temperature Ratings

Unless specific exceptions are met, ordinary- and intermediate-temperature sprinklers should be used throughout buildings.

Signup and view all the flashcards

Sprinkler Temperature Selection

Practices for providing sprinklers of other than ordinary-temperature classification based on proximity to heat sources, with temperature selection in accordance with specific tables and figures.

Signup and view all the flashcards

Minimum Storage Sprinkler Temperature

The minimum temperature rating of ceiling sprinklers in general storage, rack storage, rubber tire storage, and baled cotton storage applications must be 150°F (66°C).

Signup and view all the flashcards

Sprinkler Thermal Sensitivity

Sprinklers in light hazard occupancies must be quick-response type, residential sprinklers, quick response CMSA sprinklers, ESFR sprinklers or standard-response sprinklers under specific conditions.

Signup and view all the flashcards

Temperature Ratings Table

Defines temperature ratings of sprinklers based on distance from heat sources

Signup and view all the flashcards

Sprinkler K-Factor Minimum

Sprinklers should have a minimum nominal K-factor of 5.6 (80) unless specific exceptions are met for light hazard occupancies.

Signup and view all the flashcards

Pendent and Upright Sprinklers

Upright and pendent spray sprinklers are permitted in all occupancy hazard classifications and building construction types unless specific requirements apply.

Signup and view all the flashcards

Sidewall Sprinklers

Requirements of Sidewall sprinklers.

Signup and view all the flashcards

Residential Sprinkler Use

Residential sprinklers are permitted in dwelling units and their adjoining corridors, provided they are installed according to their listing.

Signup and view all the flashcards

ESFR Sprinklers

Specifies requirements for ESFR sprinklers including applications in unobstructed and noncombustible obstructed construction and limitations on roof or ceiling slope.

Signup and view all the flashcards

Sprinkler Positioning

Position sprinklers to protect the area, controlling positioning and area of coverage.

Signup and view all the flashcards

Calculating Coverage Area

The protection area of coverage per sprinkler is determined along branch lines, considering distance between sprinklers or to walls.

Signup and view all the flashcards

Max Coverage Area

The maximum allowable protection area of coverage for a sprinkler must comply with indicated values, but not exceed 400 ft2 (37 m2).

Signup and view all the flashcards

Max Distance Between Sprinklers

Maximum distance permitted between sprinklers is based on the centerline distance between adjacent sprinklers.

Signup and view all the flashcards

Distance to Walls

The distance from sprinklers to walls shall not exceed one-half of the allowable maximum distance between sprinklers.

Signup and view all the flashcards

Minimum Wall Distance

Specifies the minimum distance permitted between a sprinkler and the wall.

Signup and view all the flashcards

Deflector Position

Specifies deflector position distances below ceilings based on the type of sprinkler and construction

Signup and view all the flashcards

Obstructions

Sprinklers should be located to minimize obstructions to discharge, or add more sprinklers to ensure coverage. Continuous or noncontinuous obstructions less than or equal to 18 in. (450 mm) below the deflector need to comply with requirements.

Signup and view all the flashcards

Clearance to Storage

Clearance between the deflector and the top of storage or contents of the room needs to be 18 in. (450 mm) or greater.

Signup and view all the flashcards

Standard Sprinklers: General

All requirements in Section 8.5 apply to standard pendent and upright spray sprinklers, except as modified in Section 8.6.

Signup and view all the flashcards

Maximum Coverage Area

Maximum allowable protection area of coverage for a sprinkler must comply with indicated values.

Signup and view all the flashcards

Wall Distance

Distance from sprinklers to walls should not be more than half of the allowable distance between sprinklers.

Signup and view all the flashcards

Study Notes

  • Chapter 8 outlines the installation requirements for sprinkler systems, emphasizing spacing, location, and positioning to ensure effective fire protection.

Basic Installation Principles

  • Sprinklers are required throughout the premises unless specifically allowed to be omitted by standards.
  • Sprinklers should not exceed maximum protection area limits.
  • Positioning and location must ensure satisfactory activation and water distribution.
  • Deviations from clearance requirements are permitted if tests demonstrate no impairment to fire control or suppression.
  • Increased clearance between sprinklers and ceilings is allowed if sensitivity and performance are comparable to standard installations, based on tests or calculations.
  • Sprinklers are not required inside electrical, mechanical, or air handling equipment not intended for occupancy.
  • System valves and gauges must be accessible.

System Protection Area Limitations

  • Light hazard: 52,000 ft2 (4830 m2)
  • Ordinary hazard: 52,000 ft2 (4830 m2)
  • Extra hazard (hydraulically calculated): 40,000 ft2 (3720 m2)
  • Storage (high-piled or covered by NFPA standards): 40,000 ft2 (3720 m2)
  • Mezzanine floor area is excluded from these limits.
  • In mixed hazard systems, the extra hazard or storage area must not exceed its specified limit, and the total area must not exceed 52,000 ft2 (4830 m2).

Floor Control Valve Assemblies

  • Multistory buildings over two stories require a floor control valve, check valve, main drain valve, and flow switch on each floor for water flow isolation, control, and annunciation.
  • These are not required if top-level sprinklers are supplied by piping from the floor below.
  • These are not required if the total area of all floors combined is within the system protection area limits.
  • These are not required for dry systems in parking garages.

Multiple and Detached Buildings

  • Multiple buildings connected by canopies, breezeways, common roofs, or walls can be supplied by a single fire sprinkler riser, provided the system size complies with area limitations.
  • Detached buildings need separate fire sprinkler systems unless the authority having jurisdiction approves connection to an adjacent building's system.

Sprinkler Usage Guidelines

  • Install sprinklers according to their listing.
  • Exceptions exist for unusual water distribution needs due to construction or special situations, where listed sprinklers can be installed outside their typical positions.
  • Upright sprinklers typically have frame arms parallel to the branch line, unless listed otherwise.
  • When using solvent cement, do not install sprinklers in fittings before cementing.
  • Protective caps and straps must be removed per manufacturer's instructions before system activation, but can be removed immediately after installation for upright sprinklers or those over 10 ft (3.0 m) above the floor.

Temperature Ratings

  • Ordinary and intermediate temperature sprinklers should be used throughout buildings unless specific conditions require otherwise.
  • Use temperature ratings based on maximum ceiling temperatures per Table 6.2.5.1 when exceeding 100°F (38°C).
  • High-temperature sprinklers are allowed in ordinary and extra hazard occupancies, storage occupancies, and as per NFPA codes.
  • Follow specific practices and Table 8.3.2.5(a), (b), (c), and Figure 8.3.2.5 for sprinkler temperature classifications.
  • High-temperature sprinklers are needed in the high-temperature zone, intermediate-temperature in the intermediate-temperature zone.
  • Intermediate-temperature sprinklers are required within 12 in. (300 mm) to the side or 30 in. (750 mm) above uncovered steam mains, heating coils, or radiators.
  • High-temperature sprinklers are required within 7 ft (2.1 m) of a low-pressure blowoff valve discharging freely in a large room.
  • Intermediate-temperature sprinklers are required under glass or plastic skylights exposed to direct sunlight.
  • Intermediate-temperature sprinklers are required in unventilated, concealed spaces under uninsulated roofs or in unventilated attics.
  • Intermediate-temperature sprinklers are required in unventilated show windows with high-powered electric lights near the ceiling.
  • Use high- or extra high–temperature sprinklers for commercial-type cooking equipment and ventilation systems, determined via temperature measurement.
  • Sprinklers near heat sources in residential areas should follow Table 8.3.2.5(c).
  • Ordinary-temperature sprinklers adjacent to heating ducts discharging air below 100°F (38°C) do not need separation per Table 8.3.2.5(a).
  • Intermediate-temperature sprinklers or higher are required in walk-in coolers and freezers with automatic defrosting.
  • Change sprinklers to match temperature changes with occupancy changes.
  • Ceiling sprinklers should have a minimum temperature rating of 150°F (66°C) in general storage, rack storage, rubber tire storage, roll paper storage, and baled cotton storage.

Thermal Sensitivity

  • Use quick-response, residential, quick-response CMSA, ESFR sprinklers or standard-response sprinklers in light hazard occupancies.
  • Standard-response sprinklers acceptable for modifications/additions to existing light hazard systems or individual replacements.
  • Where quick-response sprinklers are installed, all sprinklers within a compartment must be quick-response, unless specified otherwise.
  • Standard-response sprinklers can be used if no listed quick-response sprinklers are available in the required temperature range.
  • These rules do not apply to in-rack sprinklers.
  • A sprinkler listed for both standard-response and quick-response protection at different coverage areas can be installed at the spacing for either listing within a compartment.
  • When converting existing light hazard systems to quick-response or residential sprinklers, all sprinklers in a compartment must be changed.

K-Factor and Thread Size Limitations

  • Sprinklers should have a minimum K-factor of 5.6 (80) unless exceptions apply.
  • Smaller orifice sprinklers are allowed in light hazard occupancies not requiring the water volume of a K-5.6 (80) sprinkler at 7 psi (0.5 bar), with restrictions:
    • The system must be hydraulically calculated.
    • Use only in wet pipe systems or per 8.3.4.3 or 8.3.4.4.
    • A listed strainer is required on the supply side of sprinklers with a nominal K-factor less than K-2.8 (40).
  • Sprinklers with nominal K-factors less than K-5.6 (80) are permitted per 11.3.2 for exposure fire protection.
  • K-4.2 (57) sprinklers can be used on dry pipe and preaction systems protecting light hazard occupancies with corrosion-resistant or internally galvanized piping.
  • Sprinklers with a K-factor exceeding K-5.6 (80) and a 1⁄2 in. (15 mm) NPT should not be installed in new systems.

Application of Sprinkler Types

  • Sprinklers should be selected as specified and spaced per Section 8.5.

Standard Upright and Pendent Spray Sprinklers

  • Allowed in all occupancy hazard classifications and building construction types, unless 8.15.1.6 applies.
  • Quick-response sprinklers are not for use in extra hazard occupancies using the density/area design method.

Sidewall Spray Sprinklers

  • Light hazard occupancies with smooth, horizontal or sloped, flat ceilings.
  • Ordinary hazard occupancies with smooth, flat ceilings, if specifically listed.
  • Areas below overhead doors.

Extended Coverage Sprinklers

  • Unobstructed construction with flat, smooth ceilings with slopes not exceeding 1 in 6 (16.7 percent).
  • Unobstructed or noncombustible obstructed construction, if specifically listed.
  • Within trusses or bar joists with web members not greater than 1 in. (25 mm) or spaced greater than 71⁄2 ft (2.3 m) on center, and ceiling slope not exceeding 1 in 6 (16.7 percent).
  • Under smooth, flat ceilings with slopes not exceeding 1 in 3 (33.3 percent), if specifically listed.
  • Extended coverage sidewall sprinklers installed per 8.9.4.2.2 on slopes exceeding a ceiling pitch of 2 in 12.
  • In each bay of obstructed construction with solid structural members extending below the deflector.
  • Areas below a single overhead door(s).

Open Sprinklers

  • Use in deluge systems for special hazards or exposures or in special locations.
  • Install according to applicable requirements for their automatic counterparts.

Residential Sprinklers

  • Use in dwelling units and adjoining corridors, installed per their listing.
  • Only in wet systems unless listed for dry or preaction systems.
  • All sprinklers in a compartment must be residential sprinklers.

Early Suppression Fast-Response (ESFR) Sprinklers

  • Use only in wet pipe systems unless listed for dry systems.
  • Roof or ceiling slope above sprinklers must not exceed 2 in 12 (16.7 percent).
  • Permitted in buildings with unobstructed and noncombustible obstructed construction.
  • Install in each channel formed by solid structural members (beams, stems) exceeding 12 in. (300 mm) in depth.
  • Follow requirements of 8.12.2 and 8.12.3 for minimum sprinkler spacing and area of coverage.
  • Use a noncombustible draft curtain at least 2 ft (600 mm) deep to separate ESFR sprinkler systems from standard-response systems, with a clear aisle of at least 4 ft (1.2 m) maintained below.
  • ESFR sprinkler temperature ratings should be ordinary unless intermediate- or high-temperature ratings are required by 8.3.2.
  • ESFR sprinklers designed to meet criteria in Chapters 12-20 can protect light and ordinary hazard occupancies.

Control Mode Specific Application (CMSA) Sprinklers

  • Use in wet, dry, or preaction systems, installed per their listing.
  • Temperature ratings should be the same as Table 8.3.2.5(a) and (b) or those used in large-scale fire testing, unless specified otherwise.
  • Install intermediate- and high-temperature sprinklers in specific locations per 8.3.2.
  • Use ordinary, intermediate, or high temperature–rated sprinklers for wet pipe systems in storage occupancies.
  • Use high temperature–rated sprinklers for dry pipe systems in storage occupancies.
  • Quick-response CMSA sprinklers designed per Chapters 12-20 can protect light and ordinary hazard occupancies.
  • Standard-response CMSA sprinklers designed per Chapters 12-20 can protect ordinary hazard occupancies.

Special Sprinklers

  • Use for specific hazards or construction features if evaluated and listed for performance under conditions.
  • Fire tests related to the intended hazard.
  • Distribution of the spray pattern with respect to wetting of floors and walls.
  • Distribution of the spray pattern with respect to obstructions.
  • Evaluation of the thermal sensitivity of the sprinkler.
  • Performance under horizontal or sloped ceilings.
  • Area of design.
  • Allowable clearance to ceilings.
  • K-factor size per 6.2.3, temperature ratings per Table 6.2.5.1.
  • The protection area of coverage should not exceed 400 ft2 (37 m2) for light and ordinary hazard occupancies.
  • The protection area of coverage should not exceed 196 ft2 (18.2 m2) for extra hazard and high-piled storage occupancies.

Dry Sprinklers

  • For dry sprinklers connected to wet pipe systems in freezing areas, the exposed barrel length should follow Table 8.4.9.1(a) or (b).
  • Barrel length is measured from the fitting face to the inside surface of the insulation, wall, or ceiling closest to the fitting.
  • Seal the clearance space around the sprinkler barrel for dry sprinklers connected to wet pipe systems in insulated freezer structures.

Position, Location, Spacing, and Use of Sprinklers

  • Locate, space, and position sprinklers according to Section 8.5.
  • Position to protect consistently with standard objectives, controlling positioning and allowable coverage area.
  • Requirements of 8.5.2-8.5.7 apply to all sprinkler types unless modified by more restrictive rules in Sections 8.6-8.12.

Protection Areas per Sprinkler

  • Protection area of coverage per sprinkler (As) is determined along branch lines:
    • Determine the distance between sprinklers (or to wall or obstruction).
    • Choose the larger of either twice the distance to the wall or the distance to the next sprinkler.
    • Define dimension as S.
  • Between branch lines:
    • Determine the perpendicular distance to the sprinkler on the adjacent branch line (or to a wall or obstruction).
    • Choose the larger of either twice the distance to the wall or obstruction or the distance to the next sprinkler.
    • Define dimension as L.
  • Coverage area calculation: As = S x L
  • Maximum allowable protection area of coverage for a sprinkler (As) should be per the section for each sprinkler type.
  • Maximum area of coverage for any sprinkler is 400 ft2 (37 m2).

Sprinkler Spacing

  • Maximum distance between sprinklers is based on centerline distance between adjacent sprinklers, measured along the ceiling slope, and according to the applicable section for each sprinkler type.
  • Distance from sprinklers to walls must not exceed one-half of the allowable maximum distance between sprinklers, measured perpendicular to the wall, to the wall behind furniture, or to the wall when sprinklers are near windows.
  • Minimum distance between a sprinkler and the wall should comply with the value indicated in the applicable section for each sprinkler type, measured perpendicular to the wall.
  • Maintain a minimum distance between sprinklers preventing wetting of adjacent sprinklers and skipping, according to the applicable section for each sprinkler type.

Deflector Position

  • Select distances between the sprinkler deflector and the ceiling based on sprinkler type and construction type.
  • For corrugated metal deck roofs up to 3 in. (75 mm) deep, measure the distance to the sprinkler from the bottom of the deck; for deeper decks measure to the highest point.
  • For ceilings with insulation installed directly against the underside, measure deflector distance from the bottom of the insulation:
    • If installed flat and parallel, measure to the underside of the insulation.
    • If deflecting or sagging, measure as half the deflection distance, but not above the low point; if deflection exceeds 6 in. (150 mm), measure to the high point.
  • Heat collectors should not be used.
  • Align deflectors parallel to ceilings, roofs, or the incline of stairs.

Obstructions to Sprinkler Discharge

  • Locate sprinklers to minimize obstructions or provide additional sprinklers for adequate hazard coverage.
  • Position sprinklers away from obstructions like truss webs/chords, pipes, columns, and fixtures per minimum distances.
  • Install sprinklers under fixed obstructions over 4 ft (1.2 m) wide, no more than 3 in. (75 mm) from the outside edge and with deflectors no more than 12 in. (300 mm) below the obstruction; use intermediate-level rack type sprinklers adjacent to obstructions.
  • Sprinklers are not required under noncombustible obstructions over 4 ft (1.2 m) wide if the bottom is 24 in. (600 mm) or less above the floor.
  • Sprinklers are not required under obstructions not fixed, like conference tables.
  • Sprinklers installed under obstructions should match the ceiling type (spray, CMSA, ESFR, residential) unless otherwise permitted; spray sprinklers are permitted under overhead doors.
  • Sprinklers under open gratings should be of the intermediate level/rack storage type or shielded from overhead sprinklers.
  • In closets and compartments up to 400 ft3 (11.3 m3), a single sprinkler at the highest ceiling level is enough regardless of obstructions or minimum wall distance.

Clearance from Deflector to Storage

  • Maintain 18 in. (450 mm) or greater clearance between the deflector and the top of storage or contents unless other standards specify more.
  • A minimum clearance of 36 in. (900 mm) is permitted for special sprinklers.
  • Less than 18 in. (450 mm) clearance is allowed if proven by successful large-scale fire tests.
  • Clearance from the top of storage to sprinkler deflectors should be at least 36 in. (900 mm) for rubber tire storage.

Skylights

  • Sprinklers can be omitted from skylights up to 32 ft2 (3.0 m2) separated by at least 10 ft (3.0 m) horizontally from any other unprotected skylight or ceiling pocket; when installed directly beneath, the distance to the ceiling is measured as if the skylight wasn't there.
  • Skylights up to 32 ft2 (3.0 m2) can have a plastic cover.

Standard Pendent and Upright Spray Sprinklers

  • Section 8.5 requirements apply, modified by Section 8.6.

Protection Areas per Sprinkler

  • Protection area of coverage per sprinkler (As) is determined per 8.5.2.1, but this does not apply in a small room as defined in 3.3.22.
  • In small rooms, the coverage area is the room's area divided by the number of sprinklers, with maximums per Table 8.6.2.2.1(a) through (d), but not exceeding 225 ft2 (20.9 m2).

Sprinkler Spacing

  • Maximum distance between sprinklers complies with Table 8.6.2.2.1(a) through (d).
  • Distance from sprinklers to walls should not exceed one-half the allowable distance between sprinklers as indicated in Table 8.6.2.2.1(a) through (d), measured perpendicular to the wall.
  • These requirements do not apply where walls are angled or irregular, and the maximum horizontal distance between a sprinkler and any point of floor area protected does not exceed 0.75 times the allowable distance, provided the maximum perpendicular distance is not exceeded.
  • These requirements do not apply within small rooms, where sprinklers can be within 9 ft (2.7 m) of any single wall, but spacing limitations of 8.6.3 and area limitations of Table 8.6.2.2.1(a) must be observed.
  • Under curved surfaces, the horizontal distance measured at floor level from the wall to the nearest sprinkler should not be greater than one-half the allowable distance between sprinklers.
  • Sprinklers should be located a minimum of 4 in. (100 mm) from a wall.
  • Sprinklers should be spaced at least 6 ft (1.8 m) on center, unless baffles are used.
  • Baffles must be solid, rigid, stay in place, and be at least 8 in. (200 mm) long and 6 in. (150 mm) high, with the top between 2-3 in. (50 mm and 75 mm) above upright sprinkler deflectors and the bottom at least even with pendent sprinkler deflectors.
  • In-rack sprinklers and old-style sprinklers in fur storage vaults can be less than 6 ft (1.8 m) on center.

Deflector Position for Standard Sprinklers

  • In unobstructed construction, the distance between the deflector and the ceiling should be a minimum of 1 in. (25 mm) and a maximum of 12 in. (300 mm).

Studying That Suits You

Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

Quiz Team

More Like This

NFPA 13 Storage Definitions Flashcards
16 questions

NFPA 13 Storage Definitions Flashcards

ManeuverableForgetMeNot2590 avatar
ManeuverableForgetMeNot2590
NFPA13-16 Kap5
31 questions

NFPA13-16 Kap5

TerrificTopaz6846 avatar
TerrificTopaz6846
NFPA13-16 kap 8.8-8.17
94 questions

NFPA13-16 kap 8.8-8.17

TerrificTopaz6846 avatar
TerrificTopaz6846
Use Quizgecko on...
Browser
Browser