NFPA13-16 kap 8.8-8.17

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to Lesson

Podcast

Play an AI-generated podcast conversation about this lesson
Download our mobile app to listen on the go
Get App

Questions and Answers

For extended coverage sprinklers used in extra hazard or high-piled storage, what is the maximum sprinkler spacing permitted when following the requirements of 8.5.2 and 8.5.3?

  • 12 ft (3.7 m)
  • 14 ft (4.3 m) (correct)
  • 16 ft (4.9 m)
  • 18 ft (5.5 m)

What is the maximum allowable area of coverage for any sprinkler, regardless of the values indicated in Table 8.8.2.1.2?

  • 450 ft² (41.8 m²)
  • 400 ft² (37 m²) (correct)
  • 350 ft² (32.5 m²)
  • 300 ft² (27.9 m²)

When walls are angled or irregular, what is the maximum horizontal distance allowed between an extended coverage sprinkler and any point of protected floor area?

  • Equal to the allowable distance between sprinklers
  • 0.75 times the allowable distance between sprinklers (correct)
  • 0.5 times the allowable distance between sprinklers
  • 1.25 times the allowable distance between sprinklers

Under what condition are sprinklers permitted to be spaced less than 8 ft (2.4 m) on center?

<p>With the arrangement of specific baffles protecting the actuating elements. (C)</p> Signup and view all the answers

For extended coverage upright sprinklers and baffles, how far above the deflectors should the tops of the baffles extend?

<p>Between 2 in. and 3 in. (50 mm and 75 mm) (A)</p> Signup and view all the answers

What is the acceptable deflector position from ceilings for extended coverage sprinklers under unobstructed construction?

<p>A minimum of 1 in. (25 mm) and a maximum of 12 in. (300 mm) (B)</p> Signup and view all the answers

When is the requirement for a deflector to be a minimum of 1 in. (25 mm) and a maximum of 12 in. (300 mm) from the ceiling waived?

<p>All of the above (D)</p> Signup and view all the answers

If a vertical change in ceiling elevation within the area of coverage of a sprinkler creates a distance of more than 36 in. (900 mm) between the upper ceiling and the sprinkler deflector, how should the change in elevation be treated?

<p>As a wall for the purpose of sprinkler spacing. (C)</p> Signup and view all the answers

For sprinklers installed under or near the peak of a peaked roof or ceiling, what is the maximum vertical distance allowed between the deflector and the peak?

<p>3 ft (900 mm) (D)</p> Signup and view all the answers

What is the minimum clear distance required between a sprinkler and an obstruction in the horizontal orientation (e.g., light fixtures and truss chords), according to 8.8.5.2.1.3?

<p>36 in. (900 mm) (B)</p> Signup and view all the answers

What is the minimum distance a sprinkler must be positioned away from obstructions to discharge when obstruction dimension is unknown?

<p>Four times the dimension of the obstruction (B)</p> Signup and view all the answers

What is the minimum clearance required between the sprinkler deflector and the top of storage when using extended coverage upright and pendent spray sprinklers?

<p>18 in. (450 mm) (C)</p> Signup and view all the answers

Under what conditions are sprinklers NOT required in ceiling pockets?

<p>All of the above (D)</p> Signup and view all the answers

What is the standard increment for listing dimensions for extended coverage sidewall sprinklers?

<p>2 ft (600 mm) (D)</p> Signup and view all the answers

When can sidewall sprinklers be installed on opposing or adjacent walls?

<p>When no sprinkler is located within the maximum protection area of another sprinkler. (B)</p> Signup and view all the answers

What is the minimum distance from an end wall that sidewall sprinklers should be located?

<p>4 in. (100 mm) (D)</p> Signup and view all the answers

For extended coverage sidewall spray sprinklers, unless otherwise specified, what is the acceptable range for the distance between the deflector and the ceiling?

<p>4 in. to 6 in. (100 mm to 150 mm) (D)</p> Signup and view all the answers

When are horizontal sidewall sprinklers permitted to be located in a zone 6 in. to 12 in. (150 mm to 300 mm) or 12 in. to 18 in. (300 mm to 450 mm) below ceilings?

<p>When listed for such use below noncombustible or limited-combustible ceilings. (B)</p> Signup and view all the answers

When soffits used for the installation of sidewall sprinklers are less than or equal to 8 in. (200 mm) in width or projection from the wall, what requirement applies?

<p>Additional sprinklers are not required below the soffit. (A)</p> Signup and view all the answers

When are pendent sprinklers required under a soffit?

<p>When the soffit exceeds 8 in. (200 mm) in width or projection from the wall. (A)</p> Signup and view all the answers

What is the location requirement for a sidewall sprinkler installed under a sloped ceiling with a slope exceeding 2 in 12?

<p>At the high point of the slope, positioned to discharge downward along the slope. (B)</p> Signup and view all the answers

What is the minimum distance a sidewall sprinkler should be located from light fixtures or similar obstructions?

<p>8 ft (2.4 m) (B)</p> Signup and view all the answers

In light hazard occupancies, under what conditions are privacy curtains NOT considered obstructions to sidewall sprinkler discharge?

<p>They are supported by fabric mesh on a ceiling track, openings in the mesh are equal to 70 percent or greater, and the mesh extends a minimum of 22 in. (550 mm) down from the ceiling. (B)</p> Signup and view all the answers

What is the minimum distance between sprinklers within a compartment for residential sprinklers?

<p>8 ft (2.4 m) (D)</p> Signup and view all the answers

How should residential sprinklers be positioned if installed at the peak below a sloped ceiling or roof surface?

<p>With the deflector horizontal. (B)</p> Signup and view all the answers

If soffits used for the installation of residential sidewall sprinklers exceed 8 in. (200 mm) in width, what is required?

<p>Additional sprinklers must be installed below the soffit. (D)</p> Signup and view all the answers

What is the maximum allowable distance between sprinklers for CMSA sprinklers under obstructed combustible construction?

<p>10 ft (3 m) (D)</p> Signup and view all the answers

What is the minimum and maximum distance below ceilings for CMSA sprinklers under unobstructed construction?

<p>A minimum of 6 in. (150 mm) and a maximum of 8 in. (200 mm) (A)</p> Signup and view all the answers

The requirements of 8.11.5.1.2 do not apply where sprinklers are positioned in which configuration?

<p>On opposite sides of the obstruction (B)</p> Signup and view all the answers

For CMSA sprinklers, what is the minimum distance that upright sprinklers must be offset horizontally from a pipe over 4 in. nominal in diameter?

<p>12 in. (300 mm) (D)</p> Signup and view all the answers

What is the clearance between the deflector and the top of storage when using CMSA sprinklers?

<p>36 in. (900 mm) (A)</p> Signup and view all the answers

What is the maximum area of coverage allowed for ESFR sprinklers, unless specific conditions are met for deviation?

<p>100 ft² (9.3 m²) (B)</p> Signup and view all the answers

For ESFR sprinklers, under what height conditions can the distance between sprinklers be up to 12 ft (3.7 m)?

<p>Storage height less than or equal to 25 ft (7.6 m) and ceiling height less than or equal to 30 ft (9.1 m) (B)</p> Signup and view all the answers

If a sprinkler is moved along the branch line a maximum of 1 ft (300 mm) from its allowable spacing to eliminate obstructions created by structural elements, what condition must be met?

<p>All of the above (D)</p> Signup and view all the answers

ESFR Pendent sprinklers with a nominal K-factor of K-22.4 (320) and K-25.2 (360) shall be positioned...

<p>so that deflectors are a maximum 18 in. (450 mm) and a minimum 6 in. (150 mm) below the ceiling (B)</p> Signup and view all the answers

What is the minimum horizontal clear space from any ESFR sprinkler to a bottom chord of a bar joist?

<p>1 ft (300 mm) (B)</p> Signup and view all the answers

If an obstruction width is 2 in. (50 mm) or less, how should sprinklers be arranged?

<p>A minimum of 2 ft (600 mm) below the elevation of the sprinkler deflector or is positioned a minimum of 1 ft (300 mm) horizontally from the sprinkler. (B)</p> Signup and view all the answers

What is the greatest floor area allowed that can be protected by a single in-rack sprinkler system?

<p>40,000 ft2 (3720 m2) (A)</p> Signup and view all the answers

When must water shields for in-rack sprinklers be provided directly above the in-rack sprinklers?

<p>When there is more than one level and sprinklers are not shielded by horizontal barriers when storing Class I - IV Commodities. (B)</p> Signup and view all the answers

What specific rules do in-rack sprinklers NOT need to adhere to?

<p>Obstruction criteria and clearance from storage requirements of Section 8.5 (D)</p> Signup and view all the answers

For extended coverage sprinklers, how is the protection area of coverage determined?

<p>Prescribed by the listing of the sprinkler. (A)</p> Signup and view all the answers

What establishes the listing dimensions for extended coverage sprinklers protection areas?

<p>Even-numbered square protection areas. (C)</p> Signup and view all the answers

For extended coverage sprinklers, what is the method for determining sprinkler spacing when listed for extra hazard or high-piled storage?

<p>Requirements outlined in Section 8.5.2 and 8.5.3. (A)</p> Signup and view all the answers

What is the method used to calculate the maximum distance permitted between sprinklers?

<p>Based on the centerline distance between sprinklers on the branch line or adjacent branch lines. (D)</p> Signup and view all the answers

How is the maximum distance measured between sprinklers installed on a sloped ceiling?

<p>Measured along the slope of the ceiling. (B)</p> Signup and view all the answers

What is the rule regarding the minimum distance of sprinklers from a wall?

<p>Sprinklers must be located a minimum of 4 in. from a wall unless listed for less. (B)</p> Signup and view all the answers

What is the minimum length requred for baffles intended to allow sprinklers to be spaced less than 8 ft on center?

<p>8 in. (A)</p> Signup and view all the answers

For sprinklers that are installed with baffles, how far below the deflector of a pendent sprinkler must the bottom of the baffle extend?

<p>At least even with the deflector (D)</p> Signup and view all the answers

What are the standard requirements for the distance between a sprinkler deflector and the ceiling for unobstructed construction?

<p>Maximum 12 in., minimum 1 in. (D)</p> Signup and view all the answers

In the event of a vertical change in ceiling elevation within the coverage area of a sprinkler, when does the change need to be treated as a wall for sprinkler spacing purposes?

<p>When the distance between the upper ceiling and the sprinkler deflector exceeds 36 in. (C)</p> Signup and view all the answers

For sprinklers installed below noncombustible structural members, what is the maximum distance allowed between the sprinkler deflector and the ceiling/roof deck?

<p>22 in. (D)</p> Signup and view all the answers

Where sprinklers are installed in each bay of combustible or noncombustible obstructed construction, what is the allowable range for the distance between the deflectors and the ceiling?

<p>A minimum of 1 in. and a maximum of 12 in. (C)</p> Signup and view all the answers

What is the requirement for the orientation of sprinkler deflectors in relation to ceilings or roofs?

<p>Aligned parallel to ceilings or roofs. (D)</p> Signup and view all the answers

For roofs and ceilings with a pitch not exceeding 2 in 12, how are they classified for sprinkler deflector orientation, and how should sprinklers be installed?

<p>Classified as horizontal; sprinklers should be installed with deflectors horizontal. (C)</p> Signup and view all the answers

What is the primary criterion for locating sprinklers to minimize obstructions to discharge?

<p>To ensure adequate coverage of the hazard. (D)</p> Signup and view all the answers

Sprinklers shall be positioned away from obstructions a distance of four times the maximum dimension of the obstruction EXCEPT when which condition is met?

<p>Sprinklers are positioned with respect to obstructions as defined by Table 8.8.5.1.2. (C)</p> Signup and view all the answers

What is the maximum clear distance that is required to obstructions in the horizontal orientation (e.g., light fixtures and truss chords)?

<p>36 in. (A)</p> Signup and view all the answers

What is one of the arrangements for isolated obstructions located against the wall?

<p>Obstructions that are not over 30 in. in width are permitted to be protected in accordance with Figure 8.8.5.1.2(b). (B)</p> Signup and view all the answers

For light hazard occupancies, what conditions must be met for privacy curtains NOT to be considered obstructions to sprinkler discharge?

<p>Curtains are supported by fabric mesh on a ceiling track with specific opening requirements. (C)</p> Signup and view all the answers

What is one of the factors that necessitates sprinklers to be installed under fixed obstructions?

<p>The obstructions are over 4 ft wide. (C)</p> Signup and view all the answers

What is the required clearance between the sprinkler deflector and the top of storage when using extended coverage upright and pendent spray sprinklers?

<p>18 in. or greater. (B)</p> Signup and view all the answers

For extended coverage sidewall spray sprinklers, up to what length are listing dimensions in 2 ft increments?

<p>28 ft (C)</p> Signup and view all the answers

Under what conditions are residential sprinklers not permitted to be used?

<p>Ceilings with slopes greater than 4 in 12 or ceiling with heights greater than 24 ft unless specifically listed for this purpose (D)</p> Signup and view all the answers

If upright or pendent sprinklers are installed at the peak below a sloped ceiling or roof surface, how should they be positioned?

<p>With the deflector horizontal. (D)</p> Signup and view all the answers

You can disregard the blades of ceiling fans when positioning sprinklers for residential upright and pendant spray sprinklers when the plan view of the fan is at least 50 percent open. What's another stipulation?

<p>So long as the fan is less than 60in in diameter (C)</p> Signup and view all the answers

For CMSA sprinklers under obstructed combustible construction, what is the maximum allowable distance between sprinklers?

<p>10 ft (D)</p> Signup and view all the answers

For CMSA sprinklers under unobstructed construction, what is the typical distance recommended between the sprinkler deflector and the ceiling?

<p>A minimum of 6 in. and a maximum of 8 in. (C)</p> Signup and view all the answers

For CMSA sprinklers, where must sprinklers be positioned when obstructions are 8 in. or less in width?

<p>The sprinklers must be positioned where they are located at least at a distance three times greater than the maximum dimension of the obstruction from the sprinkler. (B)</p> Signup and view all the answers

What is the horizontal offset that an upright CMSA sprinkler needs to be, at minimum, from a pipe that has a nominal diameter of over 4 in.? What is the alternative option to this?

<p>12 in. / supplied by a riser nipple (sprig) to elevate the sprinkler deflector a minimum of 12 in (C)</p> Signup and view all the answers

What is the minimum clearance between the deflector and the top of storage when using CMSA sprinklers?

<p>36 in. (A)</p> Signup and view all the answers

For ESFR sprinklers, a conditional deviation is permitted for sprinkler spacing; a sprinkler can be moved along the branch line from its allowable spacing to eliminate obstructions created by structural elements. What conditions must apply for this deviation?

<p>Coverage for that sprinkler cannot exceed 110 ft² per sprinkler; must never exceed 12 ft between sprinklers. (D)</p> Signup and view all the answers

For ESFR sprinklers, what is the horizontal clear space requirement from any ESFR sprinkler to a bottom chord of a bar joist?

<p>1 ft (D)</p> Signup and view all the answers

For in-rack sprinkler systems, above what level of in-rack sprinklers are water shields required for storage of Class I through Class IV commodities?

<p>Above the ground level (C)</p> Signup and view all the answers

What area is protected when determining the maximum system size for a single system of sprinklers in racks?

<p>The area protected by a single system of sprinklers in racks must not exceed 40,000 ft2 of floor area occupied by the racks. (A)</p> Signup and view all the answers

Sprinklers shall be permitted to be omitted from exterior soffits, eaves, overhangs, and decorative frame elements EXCEPT when which parameter is met?

<p>Combustible soffits, eaves, overhangs, and decorative frame elements shall not have openings or unprotected penetrations directly into the building. (D)</p> Signup and view all the answers

Where vertical shafts have combustible surfaces, at what frequency MUST one sprinkler at least be installed?

<p>Every other floor level (B)</p> Signup and view all the answers

For extended coverage sprinklers, how is the protection area determined?

<p>As prescribed by the sprinkler's listing. (D)</p> Signup and view all the answers

For extended coverage sprinklers under obstructed construction, what range should the deflectors be located from the ceiling?

<p>Any one of these arrangements is permitted. (C)</p> Signup and view all the answers

When can sprinklers be installed on opposing or adjacent walls for extended coverage sidewall sprinklers?

<p>Provided no sprinkler is located within the maximum protection area of another sprinkler. (D)</p> Signup and view all the answers

Under what condition can sprinklers be placed without regard to ceiling fan blades?

<p>The plan view of the fan is at least 50% open. (A)</p> Signup and view all the answers

For extended coverage upright sprinklers, what is the maximum vertical distance allowed between the deflector and the peak of a peaked roof?

<p>3 ft (900 mm) (C)</p> Signup and view all the answers

What is the primary objective when locating sprinklers to minimize obstructions to discharge?

<p>To minimize obstructions to discharge, ensuring adequate coverage of the hazard. (D)</p> Signup and view all the answers

How are roofs and ceilings with a pitch not exceeding 2 in 12 (16.7 percent) classified for sprinkler deflector orientation?

<p>They are classified as horizontal and permit horizontal deflector installation. (D)</p> Signup and view all the answers

What condition requires sprinklers to be installed under fixed obstructions?

<p>Obstructions over 4 ft (1.2 m) wide. (A)</p> Signup and view all the answers

Where soffits are used for the installation of sidewall sprinklers, what action is required if the soffits exceed 8 in. (200 mm) in width or projection from the wall?

<p>Install pendent sprinklers under the soffit. (A)</p> Signup and view all the answers

When installing residential sprinklers at the peak below a sloped ceiling or roof surface, how should they be positioned?

<p>With the deflector horizontal. (B)</p> Signup and view all the answers

For CMSA sprinklers, what is the maximum area of coverage allowed?

<p>130 ft² (12.1 m²) (B)</p> Signup and view all the answers

For ESFR sprinklers, under what circumstance is a deviation permitted for sprinkler spacing?

<p>To eliminate obstructions created by structural elements. (A)</p> Signup and view all the answers

For in-rack sprinkler systems, what is the maximum floor area that can be protected by a single system?

<p>40,000 ft² (3720 m²) (A)</p> Signup and view all the answers

What is a key condition that must be met when moving an ESFR sprinkler along the branch line to avoid obstructions?

<p>Adjacent branch lines maintain the same pattern. (D)</p> Signup and view all the answers

If a vertical change in ceiling elevation within the area of coverage of an extended coverage sprinkler creates a distance of more than 36 in. (900 mm) between the upper ceiling and the sprinkler deflector, how should the change in elevation be treated?

<p>As a wall for the purpose of sprinkler spacing. (D)</p> Signup and view all the answers

According to standard obstruction rules, what is the maximum that a sprinkler can be above the bottom of an obstruction if the sprinkler is 4 feet to 4 feet 6 inches away from the side of the obstruction?

<p>5 in. (125 mm) (B)</p> Signup and view all the answers

For extended coverage sidewall spray sprinklers, what is the acceptable range for the distance between the deflector and the ceiling?

<p>Not more than 6 in. (150 mm) nor less than 4 in. (100 mm) (C)</p> Signup and view all the answers

Where vertical shafts have combustible surfaces, at what minimum frequency must at least one sprinkler be installed?

<p>At every other floor level (D)</p> Signup and view all the answers

Flashcards

Extended Coverage Sprinkler Protection Area

The area of coverage for extended coverage sprinklers must meet listing requirements.

Extended Coverage Sprinkler Spacing

The maximum distance between extended coverage sprinklers depends on the construction type.

Extended Coverage Deflector Position

The deflector must be between 1 and 12 inches below the ceiling if unobstructed

Extended Coverage Performance Objective

Arrange sprinklers to minimize obstructions or add more sprinklers for adequate hazard coverage.

Signup and view all the flashcards

Extended Coverage Clearance to Storage

Maintain 18 inches or more between the deflector and the top of the storage.

Signup and view all the flashcards

Extended Coverage Ceiling Pockets

Sprinklers are generally needed in ceiling pockets. Unless specific exemptions apply.

Signup and view all the flashcards

Extended Coverage Sidewall Protection Area

The area of coverage for extended coverage sidewall sprinklers must meet listing requirements.

Signup and view all the flashcards

Extended Coverage Sidewall Spacing

The maximum distance between sprinklers depends on the construction type and is based on the centerline distance between sprinklers.8.9.3.1

Signup and view all the flashcards

Extended Coverage Sidewall Deflector Position

Sidewall sprinkler deflectors should be located between 4 and 6 inches from ceilings.8.9.4.1.1.1

Signup and view all the flashcards

Extended Sidewall Coverage Performance Objective

Arrange sprinklers to minimize obstructions or add more sprinklers for adequate hazard coverage.

Signup and view all the flashcards

Extended Coverage Sidewall Obstructions

The water discharge must not be interrupted in a horizontal plane more than 18 in below the sprinkler deflector.8.9.5.3.1

Signup and view all the flashcards

Residential Sprinkler Coverage

Areas of coverage shall align with the manufacturer's listing for residential sprinklers.8.10.2.1

Signup and view all the flashcards

Residential Sprinkler Spacing

Maximum distances between sprinklers is is dictated by thr manufacturer's listing.8.10.3.1

Signup and view all the flashcards

Residential Sprinkler Deflector Position

Pendent and upright sprinklers should have deflectors positioned 1-4 inches from the ceiling.

Signup and view all the flashcards

Residential Sprinkler Obstructions

Sprinklers should be arranged to minimize obstructions to discharge.8.10.6.1.1

Signup and view all the flashcards

Residential Sprinklers - Minimum Distance.

Minimum spacing is 8ft unless the listing of the sprinkler requires greater distance.8.10.3.3

Signup and view all the flashcards

Residential Deflector Orientation

Align deflectors parallel to ceilings, roofs, or the incline of stairs.8.10.4.7.1

Signup and view all the flashcards

Sidewall Deflector Orientation

Align deflectors parallel to ceilings, roofs.8.9.4.2.1

Signup and view all the flashcards

Sidewall/ light fixture offset

Clearance depends on distance. 8.10.7.1.3

Signup and view all the flashcards

Sidewall Obstruction

Locate sprinklers to minimize obstructions.8.10.7.1.1

Signup and view all the flashcards

Residential Sidewall Sprinkler Spacing

Sidewall sprinklers should be no closer than 8 feet from light fixtures.

Signup and view all the flashcards

CMSA sprinklers protection area of coverage

Areas of coverage determined by listing.8.11.2.1

Signup and view all the flashcards

CMSA sprinkler distance

Not to exceed 12ft, or 10ft under obstructed combustible.8.11.3.1

Signup and view all the flashcards

CMSA distance below ceilings unrestricted

Between 6 in and 8 in.8.11.4.1.1

Signup and view all the flashcards

CMSA sprinkler obstructions to discharge

Arrange sprinklers to minimize obstructions or add sprinklers.

Signup and view all the flashcards

CMSA clearance to storage

More than 36in (900mm) required.8.11.6

Signup and view all the flashcards

ESFR Spacing deviations

Deviations permitted up to 1ft (300mm) if coverage doesn't exceed 110 ft2 (10.2 m2).8.12.2.2.3

Signup and view all the flashcards

ESFR Sprinkler max distance

Storage height > 25 ft (7.6 m) and ceiling height > 30 ft (9.1 m) distance limited not more than 10ft (3.0 m) between sprinklers

Signup and view all the flashcards

ESFR deflector position

Between 6 in(150 mm) and max ceiling distance.

Signup and view all the flashcards

ESFR Deviations along the Branch Line

1ft (300 mm) from its allowable spacing, provided coverage for that sprinkler does not exceed 110 ft2 (10.2 m2).8.12.3.1

Signup and view all the flashcards

ESFR to avoid obstructions with discharge

Comply with Table 8.12.5.1.1.8.12.5.1.1

Signup and view all the flashcards

ESFR clearance to storage

Shall be 36 in. (900 mm) or greater.8.12.6

Signup and view all the flashcards

Area protected system size

Protected area not to exceed 40,000 ft2.8.13.1

Signup and view all the flashcards

Sprinklers in top of shaft

Install one sprinkler at the top of shafts.8.15.2.1

Signup and view all the flashcards

Combustible Shafts Sprinklers

Install one sprinkler at each alternate level when surfaces are combustible

Signup and view all the flashcards

Accessible Shaft Protection

One sprinkler near the bottom when accessible shafts have noncombustible surface.8.15.2.3

Signup and view all the flashcards

Stairs Protection construction

Requires protection for stairs and landings.8.15.3.1

Signup and view all the flashcards

Install vertical opening

Install draft stops should meed specified requirement.8.15.4

Signup and view all the flashcards

Spray sprinklers install protection rooms

Install sidewall spray sprinklers at the bottom of each elevator hoistway ≤ 2ft above the pit floor.8.15.5.1

Signup and view all the flashcards

Protection required areas situations

Shall be protected by sprinklers except in concealed spaces.8.15.1.1

Signup and view all the flashcards

Study Notes

Extended Coverage Upright and Pendent Spray Sprinklers

  • All requirements of Section 8.5 apply unless modified in Section 8.8.

Protection Areas

  • The protection area must be no less than that prescribed by the listing.
  • Listing dimensions are even-numbered square protection areas as shown in Table 8.8.2.1.2.
  • For extended coverage extra hazard or high-piled storage, spacing can follow 8.5.2 and 8.5.3.
    • Maximum spacing is 14 ft (4.3 m) and maximum area is 196 ft2 (18.2 m2) per sprinkler.
    • Alternatively, maximum spacing is 15 ft (4.6 m) and maximum area is 144 ft2 (13.5 m2) per sprinkler.
  • The maximum allowable area of coverage conforms to Table 8.8.2.1.2.
  • The maximum area of coverage must not exceed 400 ft2 (37 m2).

Sprinkler Spacing

  • Maximum distance between sprinklers is based on the centerline distance on the branch line or adjacent branch lines.
  • Maximum distance is measured along the slope of the ceiling.
  • Maximum distance complies with Table 8.8.2.1.2.
  • Distance from sprinklers to walls must not exceed one-half of the allowable distance between sprinklers per Table 8.8.2.1.2, measured perpendicular to the wall.
  • For angled or irregular walls, the maximum horizontal distance between a sprinkler and any point of floor area must not exceed 0.75 times the allowable distance between sprinklers.
  • Sprinklers should be located a minimum of 4 in. (100 mm) from a wall unless listed for less.
  • Sprinklers must be spaced not less than 8 ft (2.4 m) on center unless specific conditions are met.
    • Baffles protect actuating elements.
    • Baffles are solid, rigid, and stay in place.
    • Baffles are not less than 8 in. (200 mm) long and 6 in. (150 mm) high.
    • Tops of baffles extend 2-3 in. (50-75 mm) above upright sprinkler deflectors.
    • Bottoms of baffles extend to at least the level of pendent sprinkler deflectors.

Deflector Position

  • Unobstructed Construction: Deflector must be a minimum of 1 in. (25 mm) and a maximum of 12 in. (300 mm) from the ceiling.
    • This requirement does not apply to ceiling-type sprinklers or where sprinklers are listed for other ceiling construction/distances.
    • This requirement does not apply for light and ordinary hazard occupancies with noncombustible or limited-combustible ceilings.
    • Where a vertical change in ceiling elevation creates a distance of more than 36 in. (900 mm) between the upper ceiling and the sprinkler deflector, a vertical plane extending down from the ceiling at the change in elevation is considered a wall for spacing.
    • Where the distance between the upper ceiling and deflector is less than or equal to 36 in. (900 mm), the sprinklers can be spaced as if the ceiling were flat, following obstruction rules.
  • Obstructed Construction: Deflector should be located in accordance with one of the following:
    • Within 1-6 in. (25-150 mm) below noncombustible structural members and a maximum of 22 in. (550 mm) below the ceiling/roof deck.
    • At or above the bottom of noncombustible structural member to a maximum of 22 in. (550 mm) below the noncombustible ceiling/roof deck, following 8.8.5.1.2.
    • In each bay of combustible or noncombustible obstructed construction, with deflectors 1-12 in. (25-300 mm) below the ceiling.
    • Installed per their listing for use under other ceiling construction features or distances.
  • Peaked Roofs and Ceilings: Sprinklers near the peak must have deflectors located no more than 3 ft (900 mm) vertically down from the peak, per Figures 8.6.4.1.3.1(a) and 8.6.4.1.3.1(b).
  • Deflector Orientation: Deflectors must be aligned parallel to ceilings or roofs.
    • Roofs and ceilings with a pitch not exceeding 2 in 12 (16.7%) are considered horizontal.

Obstructions to Sprinkler Discharge

  • Sprinklers must be located to minimize obstructions or additional sprinklers must ensure adequate coverage.
  • Sprinklers should be arranged to comply with one of the arrangements:
    • 8.5.5.2, Table 8.8.5.1.2, and Figure 8.8.5.1.2(a).
    • Spaced on opposite sides of obstructions not exceeding 4 ft (1.2 m) in width, with the distance from the centerline of the obstruction to the sprinklers not exceeding one-half the allowable distance between sprinklers.
    • For obstructions against the wall and not over 30 in. (750 mm) wide, protect per Figure 8.8.5.1.2(b).
    • For obstructions against the wall and not over 24 in. (600 mm) wide, protect per Figure 8.8.5.1.2(c), measuring the distance from the sprinkler to the wall behind the obstruction.

Obstructions to Sprinkler Discharge Pattern Development

  • General: For continuous or noncontinuous obstructions less than or equal to 18 in. (450 mm) below the deflector that prevent pattern development, comply with 8.8.5.2.
    • Solid continuous obstructions must meet 8.8.5.1.2.
    • Unless other requirements are met, position sprinklers away from obstructions a minimum of four times the obstruction's maximum dimension, with a maximum clear distance of 36 in. (900 mm) for horizontal obstructions and no limit for vertical obstructions.
    • Spacing on opposite sides of obstructions is allowed if the distance from the centerline of the obstruction to the sprinklers does not exceed half the allowable distance between sprinklers.
    • One-half the distance between the obstructions is permitted where obstructions consist of wood bar joists 20 in. (500 mm) or greater apart, provided that the top and bottom chords of the wood bar joist are not greater than 4 in. (100 mm) (nominal) in width and bar members do not exceed 1 in. (25 mm) in width.
    • Installation is permitted on the centerline of a truss or bar joist or directly above a beam, provided the truss chord or beam dimension is not more than 8 in. (200 mm) and the sprinkler deflector is located at least 6 in. (150 mm) above the structural member and where the sprinkler is positioned at a distance four times greater than the maximum dimension of the web members away from the web members.
    • 8.8.5.2.1.3 does not apply to sprinkler system piping less than 3 in. (80 mm) in diameter or to obstructions per 8.8.5.1.2.
    • Placement is permitted without regard to ceiling fan blades less than 60 in. (1.5 m) in diameter, if the fan has at least 50% open plan view.
  • Suspended or Floor-Mounted Vertical Obstructions: Distance from sprinklers to privacy curtains, partitions, and room dividers in light hazard occupancies must comply with Table 8.8.5.2.2 and Figure 8.8.5.2.2.
    • Privacy curtains are not considered obstructions in light hazard occupancies if supported by fabric mesh on ceiling track with openings equal to/greater than 70%, and the mesh extends at least 22 in. (550 mm) down from the ceiling.

Obstructions Preventing Sprinkler Discharge from Reaching Hazard

  • For continuous or noncontinuous obstructions interrupting water discharge more than 18 in. (450 mm) below the deflector in a way that limits distribution to the hazard, comply with 8.8.5.3.
  • Installation is required under fixed obstructions over 4 ft (1.2 m) wide.
  • Not required under non-fixed obstructions.
  • Sprinklers under open gratings shall be of the intermediate level/rack storage type or shielded.
  • Deflectors of sprinklers installed under fixed obstructions must be positioned no more than 12 in. (300 mm) below the bottom of the obstruction.
  • Sprinklers installed under round ducts shall be of the intermediate level/rack storage type or shielded.

Clearance to Storage

  • Clearance between the deflector and the top of storage must be 18 in. (450 mm) or greater.
  • Other standards specifying greater clearance minimums must be followed.

Ceiling Pockets

  • Sprinklers are required in all ceiling pockets unless specific conditions are met.
  • Sprinklers are not required in ceiling pockets if:
    • The total volume of the unprotected ceiling pocket does not exceed 1000 ft3 (28 m3).
    • The depth of the unprotected ceiling pocket does not exceed 36 in. (900 mm).
    • The entire floor under the unprotected ceiling pocket is protected by sprinklers at the lower ceiling elevation.
    • The total size of all unprotected ceiling pockets in the same compartment within 10 ft (3 m) of each other does not exceed 1000 ft3 (28 m3).
    • The unprotected ceiling pocket has noncombustible or limited-combustible finishes.
    • Quick-response sprinklers are utilized throughout the compartment.
  • Sprinklers are not required in skylights and similar pockets in accordance with 8.5.7.

Extended Coverage Sidewall Spray Sprinklers

  • All requirements of Section 8.5 apply unless modified in Section 8.9.

Protection Areas

  • Area of coverage must not be less than that prescribed by the listing.
  • Listing dimensions are in 2 ft (600 mm) increments up to 28 ft (8.5 m).
  • The maximum allowable protection area is in accordance with Table 8.9.2.2.1, and must not exceed 400 ft2 (37.2 m2).

Sprinkler Spacing

  • Maximum distance allowed is based on the centerline distance between sprinklers on the branch line along the wall.
  • Spacing must align with the maximum spacing provisions of Table 8.9.2.2.1 when installed along the length of a single wall.
  • Sidewall sprinklers cannot be installed back-to-back without separation by a continuous lintel, soffit, or baffle.
  • Installation is permitted on opposing or adjacent walls, provided no sprinkler is located within another's maximum protection area.
  • The distance from sprinklers to the end walls must not exceed one-half of the allowable distance permitted between them as indicated in Table 8.9.2.2.1.
  • Sprinklers are to be located a minimum of 4 in. (100 mm) from an end wall, measuring the distance perpendicular to the wall.
  • Sprinklers should not be located within another's maximum protection area unless required by 8.9.4.1.4.1 or separated by baffles.
    • Baffles protect actuating elements.
    • Baffles are solid, rigid, and stay in place.
    • Baffles are not less than 8 in. (200 mm) long and 6 in. (150 mm) high.
    • Tops of baffles extend 2-3 in. (50-75 mm) above deflectors.
    • Bottoms of baffles extend to at least the level of the deflectors.

Deflector Position from Ceilings and Walls

  • Ceilings: Unless the requirements of 8.9.4.1.1.2 are met, deflectors must be 4-6 in. (100-150 mm) from ceilings.
    • Horizontal sidewall sprinklers are permitted in a zone 6-12 in. (150-300 mm) or 12-18 in. (300-450 mm) below noncombustible or limited-combustible ceilings where listed for such use.
  • Walls: Deflectors must be 4-6 in. (100-150 mm) from the walls on which they are mounted unless 8.9.4.1.2.2 is met
    • Horizontal sidewall sprinklers are allowed with deflectors less than 4 in. (100 mm) from the wall.
  • Lintels and Soffits: Additional sprinklers are not necessary below soffits less than or equal to 8 in. (200 mm) in width or projection from the wall if 8.9.4.1.3.1 is met.
    • Installation under a soffit is permitted when both the minimum distance from the sprinkler deflector to the bottom of the soffit and the maximum distance from the sprinkler deflector to the high ceiling are maintained.
  • Soffits and Cabinets in Residential Areas/Occupancies: Sprinklers and soffits should be installed according to 8.9.4.1.4.1, 8.9.4.1.4.2, or 8.9.4.1.4.3.
    • Pendent sprinklers must be installed under soffits exceeding 8 in. (200 mm) in width or projection.
    • Sidewall sprinklers are permitted in the face of a soffit directly over cabinets, without additional sprinklers, where the soffit does not project horizontally more than 12 in. (300 mm) from the wall.
    • Wall installation is permitted above cabinets (if the sprinklers are more than 3 ft (900 mm) above the top, and the cabinets are no greater than 12 in. (300 mm) from the wall).
  • Deflector Orientation: Deflectors must be aligned parallel to ceilings or roofs.
    • Installation is required at the high point of a sloped ceiling (exceeding 2 in 12), positioned to discharge downward along the slope.
    • Sidewall sprinklers listed for other ceiling configurations can be installed per their listing requirements.

Obstructions to Sprinkler Discharge

  • Sprinklers must be located to minimize obstructions to discharge or additional sprinklers must be provided.
  • Installation must not be closer than 8 ft (2.4 m) from light fixtures or similar obstructions.
  • Distance between light fixtures (or obstructions) located more than 8 ft (2.4 m) from the sprinkler must conform to Table 8.9.5.1.3 and Figure 8.9.5.1.3.
  • Continuous obstructions: (projecting from the same wall as the sidewall sprinkler) must follow one of these arrangements:
    • Compliance with Table 8.9.5.1.4 and Figure 8.9.5.1.4(a).
    • Spacing on opposite sides of obstructions less than 4 ft (1.2 m) wide is permitted, if the distance from the centerline of the obstruction to the sprinklers does not exceed one-half the allowable distance between sprinklers.
    • Protection per Figure 8.9.5.1.4(b) is allowed for obstructions located against the wall and not over 30 in. (750 mm) wide.
    • Protection per Figure 8.9.5.1.4(c) is allowed for obstructions against the wall and not over 24 in. (600 mm) wide. The measurement is from the sprinkler to the wall behind the obstruction.
  • Isolated Obstructions: Isolated obstructions projecting from the same wall as the sidewall sprinkler should be located a minimum of 6 in. (150 mm) from the sidewall sprinkler.
  • Obstructions on the opposite wall: Obstructions up to 2 ft (600 mm) deep and 2 ft (600 mm) wide are permitted.

Obstructions to Sprinkler Discharge Pattern Development

  • General: Continuous or noncontinuous obstructions less than or equal to 18 in. (450 mm) below the deflector that prevent the pattern from developing must comply with this section.
    • Solid continuous obstructions must meet the requirements of 8.9.5.1.2 and 8.9.5.1.3.
    • Unless other requirements are met, position sprinklers away from obstructions a minimum of four times the obstruction's dimension.
      • The clear distance to horizontal obstructions must be 36 in. (900 mm).
      • No maximum clear distance to vertical obstructions.
    • 8.9.5.2.1.3 and 8.9.5.2.1.4 do not apply where sprinklers are positioned with respect to obstructions in accordance with 8.9.5.1.2 and 8.9.5.1.3.
    • 8.9.5.2.1.3 does not apply to sprinkler system piping less than 3 in. (80 mm) in diameter.
    • Sprinkler placement is permitted without regard to ceiling fan blades less than 60 in. (1.5 m) in diameter if the fan's plan view is at least 50% open.
  • Suspended or Floor-Mounted Vertical Obstructions: Distance from sprinklers to privacy curtains, freestanding partitions, etc., in light hazard occupancies must comply with Table 8.9.5.2.2 and Figure 8.9.5.2.2.
    • Privacy curtains in light hazard occupancies are not considered obstructions if supported by fabric mesh on a ceiling track, with openings ≥ 70%, and mesh extends ≥ 22 in. (550 mm) from ceiling.

Obstructions Preventing Sprinkler Discharge from Reaching Hazard

  • For continuous or noncontinuous obstructions interrupting water discharge more than 18 in. (450 mm) below the deflector in a manner that limits distribution, comply with this section.
  • Installation is required under fixed obstructions over 4 ft (1.2 m) wide.
  • Not required under non-fixed obstructions.

Residential Sprinklers

  • Listings: Areas of coverage must align with the manufacturer’s listing.
    • Residential sprinklers cannot be used on ceilings with slopes > 8 in 12 or heights > 24 ft unless specifically listed.
  • Distances Between Sprinklers:
    • Maximum distances are consistent with the manufacturer's listing.
    • The distance between the sprinkler and the wall is not to exceed half the maximum allowable distance between sprinklers as per the manufacturer’s listing.
    • Minimum distance within a compartment is 8 ft (2.4 m), unless the sprinkler's listing requires more, or unless separated by baffles.
      • Baffles must protect the actuating elements and be solid/rigid.
      • Dimensions: not less than 8 in. (200 mm) long and 6 in. (150 mm) high.
      • Top of baffles: 2-3 in. (50-75 mm) above upright deflectors.
      • Bottom of baffles: level with pendent deflectors.
    • Sidewall sprinklers are permitted on opposing or adjacent walls if not within another's maximum protection area, or separated by the specified baffles.
    • Slope measurement is per Figure 8.10.3.5(a) and Figure 8.10.3.5(b).
    • For sloped ceilings, maintain the minimum listed spacing (but not less than 8 ft (2.4 m)), measured in the plan view (Figure 8.10.3.6(a) and Figure 8.10.3.6(b)), or separate sprinklers with listed baffles.
  • Deflector Position from Ceilings and Walls:
    • Pendent/upright sprinklers: deflectors 1-4 in. (25-100 mm) from the ceiling, unless the listing allows more.
    • Sidewall sprinklers: deflectors 4-6 in. (100-150 mm) from the ceiling, unless the listing allows more.
    • Sidewall sprinklers: soffits exceeding 8 in. (200 mm) in width or projection require additional sprinklers below the soffit.
    • Horizontal sidewall sprinklers: no more than 6 in. (150 mm) from the wall, unless listed for more.
    • End wall distance: no more than half the allowable distance between sprinklers per the listing.
    • Minimum Distance from Walls: 4 in. (100 mm) , measured perpendicular to the wall.
  • Deflector Orientation (Residential Upright/Pendent Spray):
    • Deflectors should be parallel to ceilings, roofs, or the incline of stairs.
    • Installation required with the deflector horizontal at the peak below a sloped ceiling or roof surface.
    • Roofs and ceilings with a pitch ≤ 2 in 12 (16.7%) are considered horizontal.
  • Compliance with this standard requires adherence to obstruction rules of 8.10.6 or 8.10.7, appropriate for the sprinkler's orientation (upright, pendent, or sidewall) and the manufacturer’s installation instructions.
  • Obstructions to Sprinkler Discharge (Residential Upright and Pendent Spray Sprinklers)
    • Performance Objective: Sprinklers are located to minimize obstructions, or additional sprinklers are provided.
    • Arrangement: comply with the following:
      • 8.5.5.2, Table 8.10.6.1.2, and Figure 8.10.6.1.2(a).
      • Spaced on opposite sides of obstructions not exceeding 4 ft (1.2 m) in width, with the distance from the centerline of the obstruction to the sprinklers not exceeding one-half the allowable distance between sprinklers.
      • For obstructions against the wall and not over 30 in. (750 mm) in width, protection is per Figure 8.10.6.1.2(b).
      • Per Figure 8.10.6.1.2(c) for obstructions against the wall and not over 24 in. (600 mm) in width. Measurement is from the sprinkler to the wall behind the obstruction.
    • Obstructions to Sprinkler Discharge Pattern Development.
      • General. For continuous or noncontinuous obstructions less than or equal to 18 in. (450 mm) below the deflector preventing full pattern development, comply with 8.10.6.2.
      • Solid continuous obstructions must meet the applicable requirements of 8.10.6.1.2.
      • Unless more specific requirements are met: position sprinklers away from obstructions at a minimum distance of four times the maximum dimension of the obstruction.
        • Maximum clearance to horizontal obstructions is 36 in. (900 mm).
      • Spacing on opposite sides is allowed, if the distance from the centerline to the sprinklers does not exceed half the allowable distance.
      • Half the distance between obstructions is permitted where obstructions consist of open trusses 20 in. (500 mm) or greater apart [24 in. (600 mm) on center], provided that all truss members are not greater than 4 in. (100 mm) (nominal) in width and web members do not exceed 1 in. (25 mm) in width.
      • Installation is permitted on the centerline of a truss/bar joist or directly above a beam, provided the truss chord or beam is not more than 8 in. and the sprinkler deflector is at least 6 in. above, and the sprinkler is positioned at a distance four times greater than the maximum dimension of the web members away from the web members.
      • Requirements of 8.10.6.2.1.3 do not apply to sprinkler system piping less than 3 in. (80 mm) in diameter.
      • Placement without regard to ceiling fan blades is permitted, if the fan has at least 50% open plan view.
    • Suspended or Floor-Mounted Vertical Obstructions: Distance from sprinklers to privacy curtains, freestanding partitions, room dividers, etc., is in accordance with Table 8.10.6.2.2 and Figure 8.10.6.2.2.
    • Obstructions Preventing Sprinkler Discharge from Reaching Hazard.
      • Comply with 8.10.6.3 for obstructions that interrupt water discharge more than 18 in. (450 mm) below the sprinkler deflector, limiting distribution.
      • Installation under fixed obstructions over 4 ft (1.2 m) wide, such as stairs and landings, is required.
      • Not required under non-fixed obstructions.
      • Sprinklers under open gratings must be shielded.
  • Obstructions to Sprinkler Discharge (Residential Sidewall Spray Sprinklers)
    • Performance Objective: Sprinklers are located to minimize obstructions, or additional sprinklers are provided.
    • Installation: no closer than 8 ft (2.4 m) from light fixtures or similar obstructions.
    • Distance between light fixtures/obstructions > 8 ft (2.4 m) from the sprinkler should conform to Table 8.10.7.1.3 and Figure 8.10.7.1.3.
    • For obstructions projecting from the same wall, comply with one of the following:
      • Table 8.10.7.1.4 and Figure 8.10.7.1.4(a).
      • Spaced on opposite sides of obstructions less than 4 ft (1.2 m) in width, where the distance from the centerline of the obstruction to the sprinklers does not exceed one-half the allowable distance between sprinklers.
      • Obstructions against the wall and not over 30 in. (750 mm) wide are protected per Figure 8.10.7.1.4(b).
      • Obstructions against the wall and no more than 24 in. (600 mm) wide should be protected in accordance with Figure 8.10.7.1.4(c). Maximum distance between the sprinkler and the wall is to the wall behind the obstruction, not to its face.
    • Soffits and Cabinets: Installation should be in accordance with 8.10.7.1.5.1, 8.10.7.1.5.2, or 8.10.7.1.5.3.
      • For soffits > 8 in. (200 mm) wide or projecting, install pendent sprinklers underneath.
      • Sidewall sprinklers are permitted in the face of a soffit over cabinets, without additional sprinklers, if the soffit projects horizontally ≤ 12 in. (300 mm) from the wall.
      • Sidewall sprinklers more than 3 ft (900 mm) above cabinets which are no greater than 12 in. (300 mm) from the wall can be installed on the wall above cabinets.
    • On the wall opposite from the sidewall sprinkler, obstructions up to 2 ft (600 mm) deep and 2 ft (600 mm) wide are permitted.
    • Obstructions to Sprinkler Discharge Pattern Development.
      • Continuous/noncontinuous obstructions ≤ 18 in. (450 mm) below the deflector that prevent full pattern development should comply with this section.
      • Solid continuous obstructions must meet the requirements of 8.10.7.1.2 and 8.10.7.1.3.
      • Unless the following requirements are met, position sprinklers away from obstructions a minimum distance of four times the maximum dimension of the obstruction.
        • Clear distance to horizontal obstructions should be ≤ 36 in. (900 mm).
        • 8.10.7.2.1.3 and 8.10.7.2.1.4 do not apply where sprinklers are positioned with respect to obstructions per 8.10.7.1.2 and 8.10.7.1.3.
        • 8.10.7.2.1.3 does not apply to sprinkler system piping less than 3 in. (80 mm) in diameter.
        • Sprinkler placement is permitted without regard to ceiling fan blades if the fan's plan view is at least 50% open.
    • Suspended/Floor-Mounted Vertical Obstructions: The distance from sprinklers to privacy curtains, freestanding partitions, and similar obstructions should be in accordance with Table 8.10.7.2.2 and Figure 8.10.7.2.2.
    • Obstructions Preventing Sprinkler Discharge from Reaching Hazard.
      • For obstructions interrupting water discharge > 18 in. (450 mm) below the deflector, that limit distribution, comply with this section.
      • The installation is required under fixed obstructions over 4 ft (1.2 m) wide, such as ducts, stairs, and landings.
      • Not required under non-fixed obstructions.
      • Sprinklers installed under open gratings must be shielded.
      • The deflector must be positioned per its listed distance below ceilings for sprinklers installed under fixed obstructions.
      • Sprinklers installed under round ducts must be shielded.
  • Ceiling Pockets:
    • Sprinklers are required in all ceiling pockets unless specific requirements are met:
      • Total volume ≤ 100 ft3 (2.8 m3).
      • Depth ≤ 12 in. (300 mm).
      • The entire floor protected by sprinklers at the lower elevation.
      • Interior finish is noncombustible or limited-combustible.

CMSA Sprinklers

  • General: All requirements of Section 8.5 apply, except as modified in Section 8.11.
    • Installation should align with Section 8.5 and the manufacturer’s instructions, instead of the rules in Section 8.11.
  • Protection Areas per Sprinkler:
    • Determination of Protection Area of Coverage: In accordance with 8.5.2.1.
    • Maximum Protection Area of Coverage:
      • Value should align with Table 8.11.2.2.1.
      • Does not exceed 130 ft2 (12.1 m2).
    • Minimum Protection Area of Coverage: No less than 80 ft2 (7.4 m2).
  • Sprinkler Spacing:
    • Maximum Distance Between Sprinklers:
      • Under unobstructed and obstructed noncombustible construction and unobstructed combustible construction, the distance is no more than 12 ft (3.7 m) between sprinklers.
      • Under obstructed combustible construction, the maximum distance is 10 ft (3 m).
    • Maximum Distance from Walls: No more than one-half of the allowable distance per Table 8.11.2.2.1.
    • Minimum Distance from Walls: 4 in. (100 mm).
    • Minimum Distance Between Sprinklers: 8 ft (2.4 m) on center.
  • Deflector Position:
    • Distance Below Ceilings:
      • Unobstructed Construction: Deflector is a minimum of 6 in. (150 mm) and a maximum of 8 in. (200 mm) from the ceiling.
      • Obstructed Construction: the deflector should be:
        • Between 6 in. (150 mm) and 12 in. (300 mm) from the ceiling, or
        • 1 in. to 6 in. (25 mm to 150 mm) below wood joist, to a maximum distance of 22 in. (550 mm) below the ceiling/roof or deck. Under open wood joist construction, a minimum operating pressure of 50 psi (3.4 bar) is needed for a K-11.2 (160) sprinkler, or 22 psi (1.5 bar) for a K-16.8 (240) sprinkler, based on 16.2.2.4, 16.3.2.4, and 17.2.2.3., or
        • For concrete tee construction with stems spaced less than 7 ft 6 in. (2.3 m) but more than 3 ft (900 mm) on centers, regardless of the depth of the tee, located at or above a horizontal plane 1 in. (25 mm) below the bottom of the stems of the tees and complying with Table 8.11.5.1.2.
    • Deflector Orientation: Aligned parallel to ceilings or roofs.
  • Obstructions to Sprinkler Discharge:
    • Performance Objective: Locate sprinklers to minimize obstructions. Alternative sprinklers must ensure adequate coverage.
    • Arrangement: comply with 8.5.5.2, Table 8.11.5.1.2, and Figure 8.11.5.1.2.
    • These requirements do not apply where sprinklers are on opposite sides of the obstruction.
    • Obstructions to Sprinkler Discharge Pattern Development.
      • General: Continuous or noncontinuous obstructions less than or equal to 36 in. (900 mm) below the deflector should follow 8.11.5.2
      • Rules: Solid continuous obstructions must meet of 8.11.5.1.2 or 8.11.5.1.3.
      • Position sprinklers so they are located at least a distance three times greater than the maximum dimension of the obstruction from the sprinkler for obstructions 8 in. (200 mm) or less in width.
    • Branch Lines: Position upright sprinklers with respect to branch lines as follows:
      • Upright sprinklers are permitted on branch lines ≤ 4 in. (100 mm) nominal in diameter.
      • Horizontally offset ≥ 12 in. (300 mm) from the pipe or elevated using a riser nipple to position the deflector ≥ 12 in. (300 mm) from the centerline of piping > 4 in. (100 mm) nominal in diameter.
    • Obstructions Preventing Sprinkler Discharge from Reaching Hazard
      • For obstructions below the sprinkler deflector that interfere with water distribution to the protected hazard, comply with 8.11.5.3
      • position sprinklers in relation to:
        • Fluorescent lighting fixtures.
        • Ducts.
        • Obstructions > 24 in. (600 mm) wide and below the sprinklers should have the minimum horizontal distances based on Table 8.11.5.3.2 and Figure 8.11.5.3.2.
    • Sprinklers installed under open gratings shielded.
    • Position obstructions centered between adjacent sprinklers when more than 24 inches below sprinkler deflectors.
      • Obstruction Width: Limited to 24 in. (600 mm). For obstructions > 24 in. (600 mm) wide, install more lines of sprinklers below the obstruction.
      • Extension: The obstruction should also not extend more than 12 in. (300 mm) to either side of the midpoint between sprinklers. Lines of sprinklers are required where there are extensions > 12 in. Ensure that there is 18 in. (450 mm) clearance is maintained between the top of storage and the bottom of the obstruction.
    • Special Case: For obstructions parallel to or directly below a branch line:
      • Sprinkler location: At least 36 in. (900 mm) above the top of the obstruction.
      • The obstruction's maximum width is 12 in. (300 mm).
      • Maximum extension from sides: 6 in. (150 mm) to either side of the centerline of the branch line.
  • Clearance to Storage: The required minimum clearance between the deflector and the top of the storage is 36 in. (900 mm) or greater.

Early Suppression Fast-Response Sprinklers

  • General: All Section 8.5 requirements, except as modified in Section 8.12.
  • Protection Areas per Sprinkler:
    • Determination of Protection Area of Coverage: Should align with 8.5.2.1.