NC H3-1 Exam Sample - Section 17 Quiz
33 Questions
100 Views

NC H3-1 Exam Sample - Section 17 Quiz

Created by
@ExceedingSodalite

Questions and Answers

What is the heating load for the walls only if the indoor temperature is to be maintained at 60°F?

867,240 btu/hr

What is flash gas?

Answer 4

What load estimating procedure should you use for this building according to code?

  • ACCA Manual-J
  • ASHRAE/ACCA Standard 183 (correct)
  • ASHRAE CLTD method
  • ACCA Manual-N
  • How many cfm of total exhaust air will be required for a 10-foot long single island canopy hood?

    <p>5000 cfm</p> Signup and view all the answers

    How many cubic feet of air is needed for combustion air based on the standard method in a room with a 100,000 btu/hr furnace and two 45,000 btu/hr water heaters?

    <p>9500 ft^3</p> Signup and view all the answers

    How many vibration isolators should be installed in each line when experiencing horizontal and vertical vibration?

    <p>Two in each line</p> Signup and view all the answers

    Which of the following options are allowed according to NC Admin Code Title 21, Chapter 50 regarding subcontracting labor?

    <p>Use a temporary labor service that withholds taxes</p> Signup and view all the answers

    The pressure drop for return air grills in residential duct systems is _____?

    <p>0.03</p> Signup and view all the answers

    What is the heat gain on a residential structure's west-facing wall in Charlotte, NC, with specific construction details?

    <p>465 btu/hr</p> Signup and view all the answers

    An externally equalized thermostatic expansion valve should always be used when the pressure drop across the evaporator coil exceeds ________?

    <p>1010 btu/hr</p> Signup and view all the answers

    How many cubic feet of natural gas can a branch line carry in a 20-foot-long EHD18 if the longest length is 90 feet?

    <p>28 cubic feet</p> Signup and view all the answers

    What is the smallest size 2" louver with 45° blades that can bring in 600 cfm of combustion air?

    <p>32&quot; x 28&quot;</p> Signup and view all the answers

    How many British thermal units does it take to melt 2000 pounds of ice in a 24-hour period?

    <p>288,000 btu</p> Signup and view all the answers

    The term system operating point refers to the ________?

    <p>Duct/blower performance</p> Signup and view all the answers

    What is the winter infiltration rate in cfm for a 4000-square foot, two-story single-family home of average construction?

    <p>222 cfm</p> Signup and view all the answers

    What is the cooling cfm required for a light commercial building with a sensible cooling load of 655,900 btu/hr?

    <p>29,813 cfm</p> Signup and view all the answers

    What is an acceptable slope for a converging transition in a commercial duct system?

    <p>1:4</p> Signup and view all the answers

    Assuming the duct system has 425 feet of equivalent length, what is the design friction rate for a residential air handling unit delivering 1200 cfm at a pressure drop of 0.40?

    <p>0.09</p> Signup and view all the answers

    What is the least expensive form of protection accepted by code for a clearance of 6-inches to combustible materials for a single-wall pipe?

    <p>1/2&quot; insulation board over 1-inch glass fiber or mineral wool batts</p> Signup and view all the answers

    When installing plastic gas piping outside and underground, where shall the tracer wire terminate?

    <p>Above grade at each end</p> Signup and view all the answers

    Under what condition can UL listed and labeled Class I flexible air duct pass through a fire-resistance-rated assembly?

    <p>Never</p> Signup and view all the answers

    What is the installation requirement for the liner near an electric resistance duct heater?

    <p>Interrupt liner 6&quot; before and 6&quot; after the heater</p> Signup and view all the answers

    When installing sediment traps (drip legs) in gas piping, the length of the sediment trap shall be _________?

    <p>Any length</p> Signup and view all the answers

    When installing refrigerant suction lines larger than 1 3/8", the insulation on the suction line must be at least ________?

    <p>1.5&quot; thick</p> Signup and view all the answers

    What is the minimum amount of outside air per minute required for a 3000 square foot seating area in a coffee shop per code?

    <p>1200 cfm</p> Signup and view all the answers

    What is the heat loss from a residential structure with an R-19 insulated crawlspace and a floor area of 2600 square feet on a design winter day?

    <p>1363 btu/hr</p> Signup and view all the answers

    What is the critical temperature of R-410A refrigerant?

    <p>72.1'C</p> Signup and view all the answers

    What is the roughness index for fiberglass duct board constructed with good workmanship?

    <p>0.0003</p> Signup and view all the answers

    What must be the velocity of air in an 18" round duct carrying 2400 cfm?

    <p>1400 cfm</p> Signup and view all the answers

    What is the minimum pipe insulation required for pipes carrying fluids above 105'F and below 55'F?

    <p>R-3.0</p> Signup and view all the answers

    What is the approximate pressure drop across a wet 1200 cfm residential evaporator coil?

    <p>0.26 IWC</p> Signup and view all the answers

    What is the manual-D default for excessive length of wire helix flexible duct?

    <p>0% to 4%</p> Signup and view all the answers

    When running PVC pipe underground for use as part of a domestic kitchen exhaust system, no more than _______ inches of PVC duct is allowed to extend above the concrete floor surface.

    <p>1 inch</p> Signup and view all the answers

    Study Notes

    Access Path to Attic Appliances

    • Minimum width for continuous solid flooring along access paths to attic appliances is 24 inches according to the 2018 NC Mechanical Code.

    Smoke Detectors Installation

    • Smoke detectors must be installed according to NFPA 72 when required by code.

    Latent Load Calculation

    • For 200 machine tool operators, the latent load is 125,000 BTU/hr, calculated as 625 BTU/hr per person.

    Heat Loss for an Industrial Assembly

    • A building in Asheville, NC with specific insulation and temperature conditions has a heat loss of 19,980 BTU/hr.

    Duct Specifications for Commercial Use

    • A 24" round spiral duct in a high-class restaurant can handle approximately 4,600 CFM at a maximum velocity of 1500 feet per minute.

    CSST Gas Piping System

    • For a new gas appliance requiring 45,000 BTU/hr, the minimum CSST size to run with a total length of 80 feet previously established is EHD 23.

    Solar Heat Gain in Residential Load

    • Minimum solar heat gain coefficient for glass in climate zone 3 of North Carolina is 0.30.

    PVC Pipe Venting Regulations

    • A maximum of 1 inch of PVC duct can extend above the concrete floor surface when used for a domestic kitchen exhaust system.

    Equivalent Round Duct Size

    • For a rectangular duct measuring 40" x 34" with insulation, the equivalent round duct size is 35.9".

    Gas Piping Considerations

    • Sediment traps in gas piping systems must be located after the shutoff valve, as close as possible to the inlet of the equipment.

    Duct System Design Friction Rate

    • For a residential system delivering 1000 CFM at 0.30 static pressure and 475 feet of equivalent duct length, the design friction rate is 0.063 FR/100'.

    Combustion Air Requirements

    • A 45,000 BTU/hr hot water heater and a 60,000 BTU/hr furnace require 5,250 cubic feet of combustion air when using indoor air.

    Equivalent Length in Duct Fittings

    • A 1R fitting has 70 feet more equivalent length compared to a 1Q fitting in a residential duct system.

    Heat Gain from Block Walls

    • A block wall in Raleigh, NC with specific attributes gains approximately 692 BTU/hr in the summer.

    Electric Heaters with Heat Pumps

    • The lowest temperature setting for outdoor thermostats controlling electric heaters in heat pumps is 35°F.

    Appeal of Code Decisions

    • A disagreement with local authority decisions can be appealed to the NC Department of Insurance within 5 days.

    Pressure Drop Across Diffusers

    • The average total pressure drop across a round commercial diffuser with a neck velocity of 700 feet per minute is 0.75 IWC.

    Pressure Drop in Evaporator Coils

    • A wet residential evaporator coil has a pressure drop of approximately 0.46 IWC when 1750 CFM of air passes through.

    Maximum Face Velocity in Return Air Grills

    • The maximum allowable face velocity for return air grills in North Carolina is 450 feet per minute.

    Copper Tubing Support Regulations

    • The maximum distance between supports for 1/2" semi-rigid copper tubing used as a gas line is 4 feet.

    Duct Heater Installation

    • The maximum distance a duct heater can be from the air handling unit is 4 feet.

    Fire Damper Insulation Requirements

    • Insulation must be interrupted by at least 6 inches upstream and downstream of fire dampers installed in duct systems.

    Minimum Vapor Compression Efficiency

    • The minimum vapor compression efficiency for a 120,000 BTU/hr unit at 17°F outdoor temperature has been set at 2.25.

    Licensing for Ductless Units

    • Installing an 18,000 BTU/hr ductless unit in a light-commercial building requires an H2 license classification in North Carolina.

    Total Sensible Load from Pump Motors

    • Ten 20-horsepower pump motors in a pump house produce a total sensible load of 585,000 BTU/hr.

    Cooling Factor Calculation

    • The cooling factor for a residential HVAC system with a heating load of 34,500 BTU/hr and cooling load of 31,350 BTU/hr is 0.036.

    clearance for Gas Venting

    • When venting a gas line through an insulated attic, a 1-inch clearance must be maintained with insulation shields.

    Permit Validity

    • Permits for regulated work in North Carolina are valid for six months, after which they expire.

    Heat Loss Calculation for Commercial Walls

    • A wall constructed of 8" block with specific finishes in Asheville, NC has a heat loss of approximately 2403 BTU/hr on a design winter day.

    Access Requirements for Equipment

    • Permanent means of access is required for servicing equipment located 16 feet above grade, even if hidden by a parapet.

    HVAC Equipment Selection Procedures

    • For one and two-family dwellings and townhouses, HVAC equipment should be selected following ACCA manual-S procedures.

    Pipe Insulation Thickness Requirements

    • The minimum thickness of pipe insulation on a 3" chilled water supply pipe located inside a building is 1.5 inches.

    LP Tank Regulations

    • Regulations for LP-tank installations are overseen by the NC Department of Agriculture.

    U-Factor Calculation for Added R-Value

    • The addition of R-30 insulation that modifies a ceiling's U-factor to 0.018 demonstrates how combined R-values affect thermal performance.

    Duct System Design Friction Rate Calculation

    • The design friction rate of a duct system, considering a total equivalent length of 480 feet and static pressure of 0.3 IWC, is determined to be 0.062.

    Kitchen Exhaust Requirements

    • For a 10-foot single island canopied kitchen hood in a commercial setting, a total exhaust air requirement of 5000 CFM is mandated.

    Combustion Air Requirements for Large Appliances

    • A room with a 100,000 BTU/hr furnace and two 45,000 BTU/hr water heaters needs a total of 9,500 cubic feet of air for combustion.

    Vibration Isolators for Compressors

    • When installing vibration isolators in lines affected by horizontal and vertical vibration, two isolators are recommended.### HVAC and Refrigeration Principles
    • An externally equalized thermostatic expansion valve is necessary when the evaporator coil experiences a pressure drop greater than 25% (answer 2).
    • A minimum insulation thickness of 1.5 inches is required for refrigerant suction lines larger than 1 3/8 inches (answer 2).
    • The system operating point pertains to duct and blower performance (answer 4).

    Airflow and Ductwork Calculations

    • A 30" x 10" duct with 1" duct liner requires an airflow velocity of 645 feet per minute to achieve 1000 CFM (answer 2).
    • Excessive wire helix flexible duct should have a maximum length adjustment of 0% to 4% according to Manual-D (answer 1).
    • The velocity of air in an 18" round duct carrying 2400 CFM is calculated to be 1400 CFM (answer 1).

    Load Calculations and Heat Transfer

    • A residential west-facing wall in Charlotte experiences a heat gain of 465 BTU/hr during August at 3 PM under default conditions (answer 4).
    • Heating load for 33,750 square feet of wall area in a warehouse must reach 867,240 BTU/hr to maintain 60°F indoors (answer 4).
    • Heat loss from a 2600-square-foot insulated crawlspace in Charlotte on a design winter day amounts to 1363 BTU/hr (answer 4).

    Air Quality and Ventilation

    • A coffee shop, serving light food without heavy fryers, does not require a Type I hood for ventilation (answer 2).
    • The minimum acceptable outdoor air per minute in a 3000 square feet seating area is 1200 CFM, based on occupant load (answer 1).

    Code Compliance and Standards

    • Under NC code, a non-binding estimate remains a non-contract after acceptance (answer 2).
    • UL-listed and labeled Class I flexible ducts cannot pass through fire-resistant assemblies (answer 3).
    • A minimum of 6-inch sediment traps is allowed for gas piping installations (answer 1).

    Equipment Specifications

    • The maximum outlet air temperature for a furnace in North Carolina is set at 200°F (answer 4).
    • The minimum size for an oil supply line feeding an appliance is 3/8" ID tubing (answer 4).
    • For an electric resistance duct heater with 1" insulation, the liner must be interrupted 6" before and 6" after the heater (answer 3).

    Miscellaneous Topics

    • Combustion air requirements for a basement with an 80,000 BTU/hr furnace and a 65,000 BTU/hr water heater total 7200 cubic feet (answer 3).
    • In NC, two connected appliances should connect to a single Type B vent using the smaller connector higher in the vent (answer 3).
    • The effective pressure drop across a wet 1200 CFM residential evaporator coil is approximately 0.26 IWC (answer 2).

    Testing and Inspections

    • A final inspection for HVAC systems must occur within 10 days after the system is operational (answer 4).
    • When installing plastic gas piping underground, tracer wires must be above grade at both ends (answer 4).

    Practical Applications

    • For a residential installation with a vibrational issue in refrigerant lines, continuing to isolate the lines from the structure can effectively reduce vibrations (answer 1).
    • The typical roughness index for fiberglass duct board with good workmanship is 0.0003 (answer 2).

    Refrigerant and Heat Pump Data

    • The critical temperature for R-410A refrigerant stands at 72.1°C (answer 4).
    • A PTHP heat pump should have a minimum COP of 3.2 for new commercial construction projects (answer 3).

    These notes provide a concise summary of important HVAC and refrigeration concepts and code compliance based on the provided text.

    Studying That Suits You

    Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

    Quiz Team

    Description

    Test your knowledge on residential and light commercial codes based on the NC H3-1 exam sample. This quiz includes questions about minimum requirements and installation guidelines from the 2018 NC mechanical code. Perfect for those preparing for the license exam.