HPC Infrastructure and Air Conditioning System

SuccessfulSatire avatar
SuccessfulSatire
·
·
Download

Start Quiz

Study Flashcards

15 Questions

What is the required network bandwidth that must be considered for the archiving system and post-processing/product-generation systems?

The required network bandwidth must be considered in connection to the archiving system, to any required post-processing/product-generation systems, and to the BMKG website.

What is the purpose of the multiple uninterrupted power supplies (UPSs)?

The multiple uninterrupted power supplies (UPSs) will protect the computing environment and provide at least 15 minutes of ample time for the facility's generators to come online.

What are the requirements for the cable system in the Data Center?

The Data Center Cabling System must have a cable system above and below that is structured and protected. Data cables and electrical wiring must be separated and isolated so that they do not cause extensive interference.

What standard must the Power Panel systems be in accordance with?

The Power Panel systems must be in accordance with the standard BS / IEC / EN 60439.

What is the standard that the strip data cable and power supply should follow regarding distance and anti-lightning grounding lines?

The strip data cable and power supply should have the distance and anti-lightning grounding lines according to standard ANSI / TIA-469-B.

What are the key components of the civil infrastructure that the bidder must provide for the HPC system?

The bidder must provide electric power redundancy/backup (UPS) with 15 minutes backup time, temperature control, security, power and cooling distribution, and availability of raised floor.

Describe the air conditioning system requirements for the server rooms in Jakarta and Bali.

The air conditioning system must include cooling equipment, air filter media, air temperature and humidity controls, plumbing systems, and air circulation arrangements that cover the whole room and equipment within an area of 600 m2 for Jakarta Headquarters and 60 m2 for BMKG Regional Center III - Bali.

What is the required temperature and humidity range for the server rooms?

The server room temperature must be kept constant at 22 ℃ (+/- 2), and the moisture must be kept constant at 55% (+/- 10).

Describe the electrical system requirements for the Data Center, including the main electrical panel, PLC, and automatic switchover in case of power supply failure.

The electrical system includes the main electrical panel and PLC (Program Logic Control), which must be resistant to high current waves and spikes to prevent damage to the server devices and other Data Center infrastructure. It must also have an automatic system switchover when there is a failure of the power supply source.

What are the additional power-related requirements for the Data Center, besides the UPS equipment?

Besides UPS equipment, the Data Center must have enough reserve and backup batteries system and electrical connector block (PDU / Power Distribution Unit) adjusted by the number of server racks and cabinets.

Describe the requirements for the Access Control and Security system in the data center.

The Access Control and Security system should be state-of-the-art, including entry and exit logs, video security, overall emergency procedures for the data center, a contact list for emergencies, fire prevention systems, and other necessary facilities.

What are the specifications for the Server Cabinet and Raised Floor Systems in the data center?

The Server Cabinet should use a 42U to 48U rack. The Raised Floor Systems should use the space under the floor to maintain air pressure stabilization, be rust-free, and clean.

Explain the requirements for the Data Center Cabling System regarding cable separation and isolation.

The Data Center Cabling System must have a structured and protected cable system above and below. Data cables and electrical wiring must be separated and isolated so that they do not cause extensive interference.

What is the purpose of providing multiple uninterrupted power supplies (UPSs) in the data center, and what is the minimum required runtime?

The multiple uninterrupted power supplies (UPSs) are intended to protect the computing environment. They must provide at least 15 minutes of runtime to allow sufficient time for the facility's generators to come online.

What are the requirements for the network infrastructure in the data center regarding operational bandwidth and support for model runs?

The network infrastructure must accommodate the operational bandwidth required to transmit the observational data needed for all model runs. Bidders are expected to provide internal Ethernet speed and bandwidth sufficient to support the operational requirements of the platform and its entire environment.

This quiz covers the civil infrastructure requirements for HPC, including electric power backup, temperature control, security, and cooling distribution. It also discusses the components of an air conditioning system for HPC rooms such as cooling equipment, air filters, temperature/humidity controls, and air circulation arrangements.