What is the maximum allowable area for a single detection zone in a building if it is less than an open plan area?

  • 3000 m²
  • 5000 m²
  • 1500 m²
  • 2000 m² (correct)
  • Which equipment must be used in explosive hazardous atmospheres?

  • Common wiring systems
  • Explosion Proof and Intrinsically Safe equipment (correct)
  • Fire-rated enclosures
  • Standard electrical devices
  • What is a requirement for detectors placed in HVAC plenums?

  • They should be low voltage
  • They must accommodate high humidity
  • They should be selected based on airflow patterns and fire type (correct)
  • They can substitute open area detectors
  • How far can search distance for an addressable system be if the building has sprinklers?

    <p>100 m</p> Signup and view all the answers

    Which statement is correct regarding the division of detection zones?

    <p>Detection zones should be clearly defined for emergency procedures</p> Signup and view all the answers

    What is the requirement for automatic fire detectors in enclosed structures like stairwells?

    <p>They must be treated as separate detection zones</p> Signup and view all the answers

    What is the purpose of indication of detection zone status on a control panel?

    <p>To inform operational status and provide alerts</p> Signup and view all the answers

    What is a notable feature of the detectors used in environmental air ducts or plenums?

    <p>They are designed to work in varying temperature conditions</p> Signup and view all the answers

    What does a phased evacuation system prioritize during an emergency?

    <p>Evacuating higher risk areas first in a controlled sequence</p> Signup and view all the answers

    Which component of the fire detection system helps mitigate unwanted alarms?

    <p>Alarm Verification Feature</p> Signup and view all the answers

    What role does an annunciator play in a fire alarm system?

    <p>Displays status information about the alarm circuits</p> Signup and view all the answers

    What is the primary function of a voice alarm system during a fire emergency?

    <p>To provide voice instructions and evacuation signals</p> Signup and view all the answers

    What defines a zone in a fire detection system?

    <p>A part of the building with one or more fire detectors, identified by a unique alphanumeric</p> Signup and view all the answers

    Which feature allows for multiple stages of alarm warning within a given zone?

    <p>Staged Alarm</p> Signup and view all the answers

    What is the purpose of a standby supply in a fire alarm system?

    <p>To ensure power continuity during main supply failure</p> Signup and view all the answers

    How does an alarm repeater system function within fire detection systems?

    <p>It retransmits alarm information received from alarm processing equipment</p> Signup and view all the answers

    What triggers the off-normal signal in steam-operated equipment?

    <p>Pressure falling below 110% of the minimum operating pressure</p> Signup and view all the answers

    Which of the following statements about the control valve supervisory system is true?

    <p>Two distinct signals are required for valve position changes.</p> Signup and view all the answers

    What should not occur with the position-supervising device of a control valve?

    <p>All of the above</p> Signup and view all the answers

    Which of the following is a common reason for false fire alarms?

    <p>Incorrect selection of the type of detector</p> Signup and view all the answers

    How should smoke detectors be classified in a smoke control system?

    <p>Based on their installation location in the smoke compartments</p> Signup and view all the answers

    Which aspect is NOT a requirement of smoke detectors used for smoke control?

    <p>Reliance on manual triggering mechanisms</p> Signup and view all the answers

    What indicates that a control valve is in an 'off-normal' position?

    <p>The first two revolutions of the hand wheel are utilized</p> Signup and view all the answers

    What is a key requirement for maintaining fire detection systems?

    <p>Regularly checking and ensuring proper maintenance</p> Signup and view all the answers

    What is required when in-duct smoke detectors are installed in locations over 3 m above the floor where their alarms are not visible?

    <p>Remote alarm or supervisory indicators must be provided.</p> Signup and view all the answers

    Which statement about ionization smoke detectors is correct?

    <p>Their alarm threshold can vary based on ambient conditions.</p> Signup and view all the answers

    What is a key feature of photoelectric type smoke detectors?

    <p>They use light beam propagation affected by smoke particles.</p> Signup and view all the answers

    Which feature is necessary for remote alarm or supervisory indicators connected to smoke detectors?

    <p>They must be installed in an accessible location.</p> Signup and view all the answers

    According to the requirements, which type of smoke detector uses an alpha emitter?

    <p>Ionization type smoke detectors.</p> Signup and view all the answers

    What happens to the electrical conductance when smoke particles enter the ionization area of a smoke detector?

    <p>It decreases due to particle attachment.</p> Signup and view all the answers

    In smoke detection systems, what is the primary function of a supervisory indicator?

    <p>To clearly indicate the functionality and association with air-handling units.</p> Signup and view all the answers

    What must be considered when installing smoke detectors per the requirements?

    <p>Installation should follow specific tables outlining requirements.</p> Signup and view all the answers

    What is the recommended spacing per smoke detector for an installation with an air change interval of 2 minutes?

    <p>23.23 feet</p> Signup and view all the answers

    Which factor is NOT considered when determining the location and spacing of smoke detectors?

    <p>Temperature of the smoke</p> Signup and view all the answers

    As per the guidelines, how frequently should air changes occur to allow a spacing of 58.06 feet per smoke detector?

    <p>5 minutes</p> Signup and view all the answers

    What is the minimum number of air changes per hour needed to achieve a spacing of 69.68 feet per smoke detector?

    <p>10</p> Signup and view all the answers

    In which scenario should smoke detectors be installed closer to the hazard than stated in the guidelines?

    <p>When protecting against specific hazards</p> Signup and view all the answers

    At what air change interval does spacing remain constant at 83.61 feet per smoke detector?

    <p>9 minutes</p> Signup and view all the answers

    What ceiling feature is least likely to affect smoke detector installation and spacing?

    <p>Ceiling color</p> Signup and view all the answers

    How does the configuration of material in the area impact smoke detector placement?

    <p>It can affect smoke movement and detector effectiveness</p> Signup and view all the answers

    Study Notes

    Fire Detection System Overview

    • A topographic diagram outlines protected buildings, electric circuits, and visual alarm signals linked to fire systems.
    • Phased evacuation ensures a controlled sequence in evacuating different premises, prioritizing areas at highest risk.

    Alarm Systems

    • Staged alarm systems provide multiple warning levels within a designated zone before triggering a full alarm.
    • Standby supply refers to automatic electrical power systems that activate during a main power failure.
    • Voice alarm systems offer manual or automatic voice instructions and evacuation alerts during emergencies, such as fires.

    Zones and Detectors

    • Protected buildings are divided into zones, each identified by a unique alphanumeric code, containing fire detectors.
    • Alarm repeater systems automatically retransmit alarm information from the processing equipment.
    • Alarm verification features help reduce false alarms, requiring smoke detectors to confirm alarm conditions over time.

    Environmental Considerations

    • Smoke detectors in HVAC plenums must meet requirements for temperature, airflow, and humidity.
    • In explosive atmospheres, all fire detection devices must be "Explosion Proof" and "Intrinsically Safe".

    Detection Zones

    • Buildings should have multiple detection zones to facilitate quick recognition and minimize search times.
    • Each detection zone must not exceed 2000 m²; open spaces can extend to 10,000 m².
    • Automatic fire detectors in enclosed spaces (like stairwells) are treated as separate detection zones.

    Control Valve Supervision

    • Two distinct signals indicate control valve status changes: one for off-normal and another for restoration to normal.
    • Detecting any movement from the normal valve position is crucial for system integrity.

    Common Issues with Fire Detection Systems

    • Frequent false alarms often lead to system disregard, primarily caused by improper detector selection, faulty installation, and inadequate maintenance.

    Smoke Control Systems

    • Smoke detectors serve to manage smoke spread by controlling fans, dampers, and doors.
    • Specific classifications exist for smoke detectors based on their installation: area detectors, duct detectors, and video image smoke detectors.
    • Remote alarm indicators must be accessible and clearly marked when detectors are out of immediate view.

    Smoke Detection Types

    • Ionization smoke detectors use alpha emitters to detect reduced air conductivity due to smoke presence.
    • Photoelectric smoke detectors measure lighting interruptions caused by smoke particles.

    Installation Guidelines

    • Smoke detector installation should consider anticipated smoke flows, ceiling configurations, ambient conditions, and proximity to specific hazards.
    • Specific guidelines for detector spacing based on air movement are provided, ensuring optimal coverage per air change rate within a given area.

    Studying That Suits You

    Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

    Quiz Team

    Related Documents

    Description

    This quiz covers important aspects of fire safety, including topographic diagrams of protected buildings and phased evacuation systems. Understand the mechanisms behind visual alarm signals and their role in enhancing safety during emergencies. Test your knowledge on how evacuation procedures can be effectively managed.