Fire Protection Code Regulations

InvigoratingNash avatar
InvigoratingNash
·
·
Download

Start Quiz

Study Flashcards

10 Questions

Match the room type with the required fire-resistance rating or provision:

Incinerator rooms = 2 hours and automatic sprinkler system Laundry rooms over 100 square feet = 1 hour or provide automatic fire-extinguishing system Group I-3 cells equipped with padded surfaces = 1 hour Waste and linen collection rooms over 100 square feet = 1 hour or provide automatic fire-extinguishing system

Match the location classification with the required fire-resistance rating or provision:

Paint shops not classified as Group H in occupancies other than Group F = 2 hours; or 1 hour and provide automatic fire-extinguishing system Laboratories and vocational shops not classified as Group H in a Group E or I-2 occupancy = 1 hour or provide automatic fire-extinguishing system Stationary storage battery systems in Group B, F, M, S, and U occupancies = 1 hour Stationary storage battery systems in Group A, E, I, and R occupancies = 2 hours

Match the occupancy type with the required fire-resistance rating or provision for waste and linen collection rooms:

Group I-2 waste and linen collection rooms = 1 hour Waste and linen collection rooms over 100 square feet = 1 hour or provide automatic fire-extinguishing system

Match the room type with the required fire-resistance rating or provision for waste and linen collection rooms:

Incinerator rooms = 2 hours and automatic sprinkler system Group I-3 cells equipped with padded surfaces = 1 hour

Match the electrolyte capacity with the required fire-resistance rating or provision for stationary storage battery systems:

Liquid electrolyte capacity of more than 50 gallons = 1 hour in Group B, F, M, S, and U occupancies Lithium-ion capacity of 1,000 pounds used for facility standby power, emergency power or uninterruptible power systems = 2 hours in Group A, E, I, and R occupancies

Which type of separation is required between individual occupancies according to Section 508.4.4.1?

Fire barriers

What is the purpose of the provisions in Section 509 regarding horizontal building separation allowance?

To permit special conditions exempt from the code requirements

In a Group S-2 parking garage, how should adjacent occupancies be separated according to Section 508.4.4.1?

Horizontal assemblies

Which occupancies are permitted below the horizontal assembly protected by an automatic sprinkler system?

Group A assembly spaces

What is the purpose of special provisions in Section 509.1 regarding allowable heights and areas of buildings?

To allow exemptions or modifications based on occupancy and construction type

Test your knowledge of fire protection code regulations regarding the separation of incidental accessory occupancies in buildings without a fire barrier. Questions cover construction requirements for walls in such scenarios.