Podcast
Questions and Answers
Study Notes
NEC and Wiring
- Article 725 of the NEC covers wiring for burglary systems.
- Non-power-limited circuits can operate with voltages up to 600 V.
- Tables 12A and 12B outline limitations for power-limited circuits.
- Part III of Article 760 contains power-limited wiring requirements.
- Power-limited circuits typically operate at less than 100 VA.
Fire Alarm Circuit Requirements
- Power-limited equipment circuit limitations are verified by testing laboratories.
- Underground power-limited copper fire alarm circuits must comply with Articles 800 and 300.
- Fire alarm cables cannot be laid directly on top of suspended ceiling tiles.
- Circuit integrity cable should not be spliced with standard connectors.
- Power-limited circuits may use Chapter 3 or power-limited wiring methods.
Circuit Specifications
- Class 2 conductors are permitted in the same cable as power-limited circuit conductors.
- FPLP is the suitable cable type for two hours of fire exposure.
- Fire alarm circuits must maintain functionality for partial evacuation.
- Abandoned fire alarm cables can remain if tagged for future use.
Equipment and Installation Guidelines
- Non-power-limited circuits may utilize THHN wire in EMT.
- Fire alarm circuit conductors above ceilings cannot use ceiling support wires.
- Fire alarm cables must not be strapped to other conduits.
- Control relays and modules need to be listed for fire alarm use.
Firestopping and Penetrations
- Firestopping materials classification is essential; a minimum F rating of 120 is required for two-hour rated firewalls.
- NEC 300.21 mandates firestopping for electrical penetrations.
- Intumescent materials expand when heated; ablative materials cool as they burn.
- Wet locations are identified for the inside of conduits under concrete slabs.
Detection and Suppression Systems
- UL Fire Resistance Directory assists in determining assembly ratings.
- Automatic sprinkler systems, kitchen hoods, and dry chemical suppression systems usually work with fire alarms.
- Phase I recall smoke detectors must be installed within 21 feet of elevator car centerlines.
Control Units and Integration
- Fire alarm control units must connect to buildings' suppression systems; they need to be monitored for alarms and troubles.
- Maximum delay for a waterflow switch is 90 seconds.
- Control modules must be installed within 3 feet of components controlling emergency functions.
HVAC System Requirements
- NFPA 90A necessitates duct detectors for HVAC systems exceeding 2000 cfm capacity.
- Detection on the return side in multi-story systems is required for HVAC systems over 15000 cfm.
Regulatory Compliance
- The AHJ selects the designated elevator recall level for fire alarm systems.
- NFPA mandates specifications for fire alarm control outputs based on the number of elevator systems.
Studying That Suits You
Use AI to generate personalized quizzes and flashcards to suit your learning preferences.
Description
Test your knowledge with these flashcards covering key concepts from Lessons 5 and 6 of fire alarm systems. Focus on important articles from the NEC and the specifications for power-limited circuits. Perfect for anyone looking to deepen their understanding of fire alarm installations.