Fibrous Glass Duct Construction Standards
54 Questions
1 Views

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to Lesson

Podcast

Play an AI-generated podcast conversation about this lesson

Questions and Answers

What is the highest permissible continuous operating temperature within a fibrous glass duct?

  • 225°F
  • 200°F
  • 275°F
  • 250°F (correct)

In the absence of staple flaps to temporarily secure seams and joints on fibrous glass ducts, which alternative method is recommended prior to applying the final closure system?

  • Cross tabs made of closure tape (correct)
  • Hot seal tape
  • Pressure seal tape
  • Overlapping tabs of duct board

What is the minimum length requirement for sheet metal screws used to penetrate fibrous glass duct board?

  • No less than 1.25 inches long
  • 0.5 inch (12.7 mm) longer than the board thickness (correct)
  • 1 inch longer than the board thickness
  • 7/8 inches longer than the board thickness

When employing cross tabs on fibrous glass duct seams and joints lacking staple flaps, what is the minimum recommended length for each cross tab?

<p>8 inches (B)</p> Signup and view all the answers

A duct constructed of 1-inch thick fibrous glass duct board that is 60 inches wide shall be supported by hangers a maximum of how many feet on center?

<p>4 (C)</p> Signup and view all the answers

What is the maximum permissible spacing between hangers supporting fibrous glass ductwork that measures 48 inches or greater in width?

<p>4 feet (B)</p> Signup and view all the answers

What gauge of sheet metal is required to support 20" x 12" diffuser connections in fibrous glass ductwork with a bearing plate?

<p>22 (A)</p> Signup and view all the answers

Under what maximum width condition can 22-gauge, 2" x 1.5" hangers be used in place of standard 3-inch duct hangers for fibrous duct board?

<p>24 inches (C)</p> Signup and view all the answers

What is the minimum width requirement for all heat seal tapes used in the construction of fibrous glass duct systems?

<p>3 inches (B)</p> Signup and view all the answers

A 30" x 30" fibrous glass duct shall be supported by hangers a maximum of how many feet on center?

<p>2 (C)</p> Signup and view all the answers

Which closure system is deemed unsuitable for rigid fibrous glass duct systems due to non-compliance with UL 181 or UL 181A standards?

<p>Pressure-sensitive aluminum foil tapes (D)</p> Signup and view all the answers

It is recommended that fibrous glass duct systems (when used in air conditioning systems) not exceed what pressure in inches W.G.?

<p>1 (A)</p> Signup and view all the answers

A 48" x 48" duct constructed of 1-inch thick duct board shall be supported by hangers at a maximum interval of how many feet on center?

<p>2 (B)</p> Signup and view all the answers

What is the minimum size hanger wire gauge recommended for fibrous glass duct?

<p>16 (D)</p> Signup and view all the answers

For what application is fibrous glass duct suitable?

<p>Conveying air at 40°F to 250°F (A)</p> Signup and view all the answers

What size and type of screws are required for Z-framing around the opening of a flange, spaced 6 inches on center?

<p>#10 x 1.25 inch sheet metal (A)</p> Signup and view all the answers

A fibrous glass duct measures 36 inches by 64 inches. What is the maximum allowable spacing, in feet, for supporting this straight duct?

<p>8 (B)</p> Signup and view all the answers

For a 1-inch water gauge utilizing Type 475 board with an inside duct dimension of 22 inches, what tie rod reinforcement spacing is required?

<p>Not required (A)</p> Signup and view all the answers

When staple flaps aren't used to join seams and joints, cross tabs must be equally spaced on each side of the joint and on what maximum centers?

<p>2 (A)</p> Signup and view all the answers

A straight piece of fibrous glass duct with a three-inch-wide channel measures 36 inches high and 60 inches wide inside. What is the maximum allowable hanger spacing for this ductwork in feet?

<p>6 (C)</p> Signup and view all the answers

What is the minimum number of pieces required to construct a 45-degree fibrous glass duct elbow?

<p>2 (D)</p> Signup and view all the answers

Cross tabs holding seams and joints in place before closure are made from closure tape lengths of at least how many inches?

<p>4 (C)</p> Signup and view all the answers

A contractor is installing a 12-inch wide flanged electric heater in a 12-inch by 18-inch fibrous glass duct. Given the need for sheet metal to safely mount the heater, what is the MOST appropriate quantity and gauge of sheet metal required?

<p>10 square feet of 22-gauge sheet metal (B)</p> Signup and view all the answers

For a 24-inch by 24-inch fibrous glass duct, utilizing 3-inch-wide channel for hanger support, what is the MAXIMUM permissible spacing, in feet, between hangers to ensure structural integrity and compliance with standard practices?

<p>8 (C)</p> Signup and view all the answers

When installing volume dampers in fibrous glass duct, what is the MOST critical requirement to prevent damage and maintain the duct's integrity?

<p>20-gauge galvanized steel to prevent cutting into the duct board (A)</p> Signup and view all the answers

According to UL181 A standards, listed enclosures MUST utilize specific materials for secure sealing. Which of the following sealing methods is NOT typically approved under these standards?

<p>Heat-activated aluminum scrim tapes (C)</p> Signup and view all the answers

What is the MINIMUM acceptable width, in inches, for pressure-sensitive tape used in sealing fibrous glass ductwork to ensure adequate adhesion and prevent air leakage?

<p>3 (D)</p> Signup and view all the answers

When incorporating sheet metal sleeves inside ductboard for electric heater applications, how far, in inches, MUST the sleeves extend beyond each side of the heater to provide adequate heat protection and prevent damage to the ductboard?

<p>12 (A)</p> Signup and view all the answers

When securing ductboard with screws, what is the MAXIMUM permissible length, in inches, by which the screws can exceed the thickness of the ductboard to prevent compromising the duct's integrity?

<p>0.25 (A)</p> Signup and view all the answers

Under what conditions is fibrous glass duct board MOST appropriately used, considering its limitations in withstanding pressure and exposure to certain substances?

<p>Return air ductwork only (C)</p> Signup and view all the answers

What type of lock is commonly used for straight duct and fittings?

<p>Pittsburgh lock (A)</p> Signup and view all the answers

What is the maximum distance screws can be spaced apart on duct access panels?

<p>6 inches (B)</p> Signup and view all the answers

For rectangular ducts with flexible liners and an interior width of 6 inches, what is the requirement regarding mechanical fasteners?

<p>Require mechanical fasteners in addition to adhesive (B)</p> Signup and view all the answers

What is the requirement for devices installed inside lined ducts or fittings?

<p>Must not damage the liner or cause erosion of the liner. (C)</p> Signup and view all the answers

According to regulations, what entity sets the standards for belt guards?

<p>OSHA (B)</p> Signup and view all the answers

What component is represented by the drawing resembling a branching duct?

<p>Wye junction (D)</p> Signup and view all the answers

What type of steel sheet is required for ducts and connectors unless otherwise specified?

<p>G-60 coated galvanized steel (C)</p> Signup and view all the answers

The Type L-2 longitudinal duct seam is suitable for use up to what static pressure?

<p>3 inch water gage (A)</p> Signup and view all the answers

What is the operating pressure range required for one-inch wg.?

<p>Over ½-inch up to 1-inch wg. (D)</p> Signup and view all the answers

How often should longitudinal standing seams be fastened on ducts?

<p>4-inch intervals (B)</p> Signup and view all the answers

What material is acceptable for reinforcement for flat sides of oval duct?

<p>Of a size equal to or greater and spaced at intervals specified for flat oval duct (C)</p> Signup and view all the answers

What is the minimum gage requirement for duct access panels?

<p>22 gage (A)</p> Signup and view all the answers

What is the maximum allowable sag between supports for flexible duct?

<p>½ (C)</p> Signup and view all the answers

Class C transverse joints are applicable for a static pressure construction class up to what level?

<p>3 (B)</p> Signup and view all the answers

For ducts using adhesive, what interior width allows skipping mechanical fasteners?

<p>6 inches or less (A)</p> Signup and view all the answers

What type of lock system is best suited for straight duct and fittings?

<p>Pittsburgh lock systems (D)</p> Signup and view all the answers

Which of the following is a factor to consider when determining duct dimensions?

<p>Available space and airflow requirements (A)</p> Signup and view all the answers

What is a primary purpose of applying adhesive to ductwork?

<p>To create an airtight seal (A)</p> Signup and view all the answers

Which of the following best describes a low-pressure duct system?

<p>Operates with pressures at or below 2 inches W.G. (A)</p> Signup and view all the answers

Which of the following is a common type of seam used in ductwork?

<p>A 'snap lock' seam (B)</p> Signup and view all the answers

What does the term 'W.G.' typically stand for in the context of duct pressure?

<p>Water Gauge (A)</p> Signup and view all the answers

Which of the following should be considered during duct installation?

<p>Proper support and sealing (A)</p> Signup and view all the answers

What is the purpose of using joint reinforcement in ductwork?

<p>To increase the strength of the ductwork (B)</p> Signup and view all the answers

Why is proper sealing important for ductwork?

<p>Prevents air leaks. (C)</p> Signup and view all the answers

Flashcards

Max temp in fibrous glass duct?

250°F

Missing staple flaps?

Crosstabs

Screw length penetrating duct board?

0.5 inch (12.7 mm) longer than the board thickness

Minimum cross tab length (inches)?

8

Signup and view all the flashcards

Max hanger spacing for >48 inch duct?

6 feet

Signup and view all the flashcards

Max width (in) for 22-gage hangers?

36

Signup and view all the flashcards

Minimum width of heat seal tapes (inches)?

3

Signup and view all the flashcards

Unsuitable closure System?

Pressure-sensitive aluminum foil tapes

Signup and view all the flashcards

Sheet Metal Needed for Heater

Around 10 square feet of 22 gage sheet metal.

Signup and view all the flashcards

Fibrous Glass Duct Hanger Spacing

A maximum spacing of 6 feet.

Signup and view all the flashcards

Volume Dampers in Fibrous Glass Duct

20-gage galvanized steel used to prevent cutting into the duct board.

Signup and view all the flashcards

UL181 A Listed Enclosures

Heat activated aluminum scrim tapes.

Signup and view all the flashcards

Pressure Sensitive Tape Width

A minimum of 3 inches.

Signup and view all the flashcards

Sheet Metal Sleeves for Ductboard Heaters

6 inches beyond each side.

Signup and view all the flashcards

Screw Length for Ductboard

No more than .25 inches longer.

Signup and view all the flashcards

Fibrous Glass Duct Board Use

Supply air ductwork subject to 2-inch WG static pressure.

Signup and view all the flashcards

Z-framing screw spec.

#10 x 1.25 inch galvanized screws, spaced 6 inches on center.

Signup and view all the flashcards

Max spacing: 36" x 64" duct

6 feet

Signup and view all the flashcards

Tie rod reinforcement?

Not required

Signup and view all the flashcards

Max spacing: 44" x 56" duct

4 feet

Signup and view all the flashcards

Cross tab spacing

6 inch maximum centers

Signup and view all the flashcards

Max hanger spacing

10 feet

Signup and view all the flashcards

Min pieces: 45° elbow

2

Signup and view all the flashcards

Cross tab tape length

4 inches

Signup and view all the flashcards

Fibrous Glass Duct Support Spacing (60" wide)

For a 60-inch wide duct constructed of 1-inch thick fibrous glass duct board, hangers should be placed a maximum of 6 feet on center.

Signup and view all the flashcards

Diffuser Connection Support

20" x 12" diffuser connections in fibrous glass ductwork require a bearing plate made of 18-gage sheet metal for support.

Signup and view all the flashcards

Fibrous Glass Duct Support Spacing (30"x30")

For a 30" x 30" fibrous glass duct, hangers should be placed a maximum of 6 feet on center.

Signup and view all the flashcards

Max Pressure for Fibrous Glass Duct

Fibrous glass duct systems in air conditioning systems are recommended not to exceed 2 inches W.G. (Water Gauge).

Signup and view all the flashcards

Fibrous Glass Duct Support Spacing (48"x48")

A 48" x 48" duct made of 1-inch thick duct board needs hangers every 6 feet.

Signup and view all the flashcards

Minimum Hanger Wire Gage

The smallest hanger wire for fibrous glass duct is 18 gage.

Signup and view all the flashcards

Fibrous Glass Duct Temperature Range

Fibrous glass duct can be used for conveying air between 40°F to 250°F.

Signup and view all the flashcards

Heater Support Dimensions

A 12" heater requires a 22 gage metal sleeve extending 6" past each end, resulting in 24" width x 60" length.

Signup and view all the flashcards

Flat drive slip T-1 use

24 gage duct wall 20 inches wide with a ½-inch water gage static pressure

Signup and view all the flashcards

Max spacing: duct access panel screws

6 inches

Signup and view all the flashcards

Devices inside lined ducts

Must not damage the liner or cause erosion of the liner

Signup and view all the flashcards

Steel sheet coating standard

G-60

Signup and view all the flashcards

Longitudinal duct seam Type L-2

3 inch

Signup and view all the flashcards

Duct seam fastening intervals

4

Signup and view all the flashcards

Duct access panel gage

At least equal to the duct gage

Signup and view all the flashcards

Duct width without mechanical fasteners

6

Signup and view all the flashcards

Pittsburgh lock

A lock commonly used for straight duct and fittings.

Signup and view all the flashcards

Ducts w/ Flexible Liners (6-inch width)

Requires mechanical fasteners in addition to adhesive.

Signup and view all the flashcards

Belt Guard Regulations

Belt guards must adhere to these safety regulations.

Signup and view all the flashcards

Volume damper

A component used to adjust airflow within a duct system.

Signup and view all the flashcards

1-inch wg. Operating Pressure

Over ½-inch up to 1-inch wg.

Signup and view all the flashcards

Oval Duct Reinforcement

Reinforcement should match or exceed the specifications for flat oval duct.

Signup and view all the flashcards

Max Sag: Flexible Duct

The maximum allowable sag between flexible duct supports.

Signup and view all the flashcards

Class C Transverse Joints

Applicable for static pressure construction up to 1 wg.

Signup and view all the flashcards

SMACNA Duct Standards

SMACNA standards cover metal and flexible duct construction.

Signup and view all the flashcards

Using SMACNA Tables

Find data for duct construction in tables organized by gauge and reinforcement type.

Signup and view all the flashcards

Weight Per Foot (WPF)

Use a weight per foot (WPF) factor to estimate the weight of duct sections.

Signup and view all the flashcards

Volume Damper Material

Galvanized steel is often used for volume dampers to prevent cutting into duct board.

Signup and view all the flashcards

UL181 A Enclosures

Heat-activated aluminum scrim tapes are examples of UL181 A listed enclosures.

Signup and view all the flashcards

Unsuitable Tape

Pressure-sensitive aluminum foil tapes are not a suitable closure system.

Signup and view all the flashcards

Fibrous Glass Duct Use

Fibrous glass duct board should be used for supply air ductwork with up to 2-inch WG static pressure.

Signup and view all the flashcards

60" Duct Hanger Spacing

For a 60-inch wide duct constructed of 1-inch thick fibrous glass duct board, hangers should be placed a maximum of 6 feet on center.

Signup and view all the flashcards

Study Notes

  • Fibrous Glass Duct Construction Standards based on SMACNA, 7th and 8th Editions.

Temperature

  • The maximum temperature inside a fibrous glass duct with continuous operation is 250°F.

Closure Systems

  • Pressure seal tape should be used when staple flaps are not present to hold seams and joints in place before applying the closure system.
  • A closure system that does not comply with UL 181 or UL 181A is not suitable for rigid fibrous glass duct systems.
  • Mastic-pressured glycol tape is not suitable for use with rigid fibrous glass duct systems and does not comply with UL 181 or UL 181A.

Sheet Metal Screws

  • All sheet metal screws penetrating duct board shall be 0.5 inch (12.7 mm) longer than the board thickness.

Cross Tabs

  • When staple flaps are not present, cross tabs are to be equally spaced on each side of the joint and made from 8 inch minimum lengths of closure tape.
  • For seams and joints without staple flaps, cross tabs made from 8-inch minimum lengths of closure tape should be used.
  • The cross tabs should be spaced equally on each side of the joint and on 12-inch centers with at least one cross tab per duct side.
  • When staple flaps are not used to join seams and joints, cross tabs must be equally spaced on each side of the joint and on 12 inch maximum centers.
  • When staple flaps are not used to join seams and joints there must be at least one cross tab per duct side
  • Cross tabs used to hold seams and joints in place prior to the application of a closure system must be made from lengths of closure tape at least 8 inches long.

Hangers

  • For fibrous duct board, 22 gage, 2" x 1.5" hangers may substitute for 3 inches duct hangers with widths not over 48 inches.
  • The maximum hanger spacing for duct 48 inches or greater is 4 feet.
  • Fibrous glass duct 24 inches by 24 inches using 3-inch-wide channel requires hanger spacing at no more than 6 feet maximum.
  • The fibrous glass duct is 36 inches by 64 inches and the maximum allowable spacing for the straight duct is 4 feet.
  • The fibrous glass duct measures 44 inches by 56 inches and the maximum allowable spacing for the straight duct is 4 feet.
  • A piece of fibrous glass duct is straight with a three-inch-wide channel, is 36 inches high and 60 inches wide inside and the maximum allowable hanger spacing for this ductwork is 4 feet.
  • A duct constructed of 1-inch thick fibrous glass duct board that is 60 inches wide shall be supported by hangers a maximum of 4 feet on center.
  • A 30" x 30" fibrous glass duct shall be supported by hangers a maximum of 4 feet on center.
  • A 48" x 48" duct constructed of 1-inch thick duct board shall be supported by hangers a maximum of 4 feet on center.

Fastening

  • Z-framing around the opening of a flange on opening requires #10 x 1.25 inch sheet metal screws 6 inches on center.

Tie Rods

  • The water gage is 1 inch given the contractor installing Type 475 Board. The inside duct dimension is 22 and the tie rod reinforcement is not required.
  • If the access door width interferes with reinforcement, install the tie rods 4 inches from each side of the door opening.

Duct Elbows

  • A 45-degree fibrous glass duct elbow requires a minimum of 2 pieces.
  • A 90-degree fibrous glass duct elbow requires a minimum of 3 pieces.

Tape Measurements

  • All heat seal tapes shall be a minimum width of 3 inches.
  • All pressure sensitive tape shall be a minimum width of 2.5 inches.
  • The minimum overhang for a seam without staple flaps when using pressure sensitive tape is 1.25 inch(es).
  • Closure tape should be centered over edge of stapling flap 1 inch(es) minimum overlap.

Heater Installation

  • When installing a flanged or slip-in electric heater in the duct, where the heater is 12 inches wide and being installed in a fibrous glass duct 12 inches by 18 inches, 10 square feet of 22 gage sheet metal will be needed.
  • Sheet metal sleeves used inside ductboard for heater applications shall extend 6 inches beyond each side of the heater.

Ductboard

  • All screws penetrating ductboard shall be no more than 0.5 inches longer than the ductboard.
  • 20" x 12"" diffuser connections in fibrous glass ductwork are to be supported by a bearing plate of 22 gage sheet metal.

Usage

  • Fibrous glass duct board may be used for supply air ductwork subject to 2-inch WG static pressure.
  • It is recommended that fibrous glass duct systems when used in air conditioning systems, not exceed 2 inches W.G.
  • Fibrous glass duct may be used for conveying air at 40°F to 250°F (4.4°C to 121.1°C).

Other Requirements

  • UL181 A requires listed enclosures be any of the following except heat activated aluminum foil tapes.
  • Volume dampers in fibrous glass duct require metal sleeves.
  • The length of duct board (1-inch thick) required to fabricate a duct 40 inches wide x 16 inches high is 10 feet, assuming a flap width of 1-3/8 inches is included.
  • A 44" x 40" fibrous glass duct operating at 1/2-inch WG static pressure may be reinforced with a 22 gage 1.25" x 1.25" tee.
  • The collar of a 20" by 12" diffuser connection shall be supported by a bearing plate inside the duct approximately 3 inches wide.
  • The minimum size hanger wire for fibrous glass duct is 12 gage.

Studying That Suits You

Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

Quiz Team

Description

Fibrous glass duct construction standards based on SMACNA, 7th and 8th Editions. It covers topics such as temperature limitations, closure systems, sheet metal screws, and cross tabs for seams and joints.