Boilers and Burner Safety Controls
26 Questions
1 Views

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to lesson

Podcast

Play an AI-generated podcast conversation about this lesson

Questions and Answers

What is the main function of the Low Combustion Air Pressure Fuel Cut-Off Switch?

  • To prevent burner operation in case of insufficient combustion air (correct)
  • To control the temperature inside the boiler
  • To regulate the fuel flow to the burner
  • To start the burner operation
  • How is the Low Combustion Air Pressure Fuel Cut-Off Switch triggered to shut the SSOVs?

  • By decreasing the windbox air pressure
  • By interrupting or completing the burner limit control circuit (correct)
  • By increasing the airflow purge switch
  • By turning off the fuel valve
  • What happens if the forced draft fan is not in operation according to the text?

  • The low combustion air pressure switch opens, causing the flame safeguard controller to shut the SSOVs (correct)
  • The fuel valve supervisory switch activates
  • The low-fire start switch turns on
  • The burner operation continues normally
  • What is the function of the High Airflow Purge Switch?

    <p>To prevent burner startup sequence if unsafe conditions exist</p> Signup and view all the answers

    What role does the flexible diaphragm play in the low combustion air pressure switch?

    <p>It interacts with a switch that interrupts or completes the burner limit control circuit</p> Signup and view all the answers

    Why does the low combustion air pressure switch have one side of the housing open to atmosphere and the other connected to the windbox?

    <p>To ensure adequate air pressure for safe combustion</p> Signup and view all the answers

    What happens if the windbox pressure drops below the safe minimum?

    <p>The burner shuts down.</p> Signup and view all the answers

    What is the importance of the low-fire start switch?

    <p>To prevent ignition if air and fuel are not in low-fire positions.</p> Signup and view all the answers

    What is required by the CSA B149.3 Code for any appliance over 300 kW input?

    <p>Proven low-fire start.</p> Signup and view all the answers

    How does a high-airflow purge switch contribute to safety?

    <p>Ensures air changes in combustion zone before ignition.</p> Signup and view all the answers

    What proof of airflow is required during a purge according to the text?

    <p>Variable frequency drive (VFD) contact closures.</p> Signup and view all the answers

    Why is it important to have limit switches on combustion air dampers?

    <p>To ensure the purge timer starts at high-fire position.</p> Signup and view all the answers

    What does a differential pressure switch connected to the forced draft fan do at maximum airflow?

    <p>Closes to initiate purge timer.</p> Signup and view all the answers

    In what scenario does the text mention a risk of a furnace explosion?

    <p>If excessive fuel flow occurs during main ignition.</p> Signup and view all the answers

    'Proof of airflow' mentioned in the text serves to ensure what aspect of burner operation?

    <p>'Proper purging before ignition.'</p> Signup and view all the answers

    'High-low start switch' mentioned in the text is primarily responsible for what function in boiler systems?

    <p>'Ensuring safe lighting at low-fire.'</p> Signup and view all the answers

    What happens if the fan in a burner becomes mechanically uncoupled according to the text?

    <p>The airflow decreases</p> Signup and view all the answers

    Why is it important to keep combustion air openings unobstructed?

    <p>To ensure proper burner operation</p> Signup and view all the answers

    What is the minimum mesh size for screens placed on combustion air openings?

    <p>1/4 inch</p> Signup and view all the answers

    Why must the combustion air inlet from outdoors not be located lower than 300 mm above the outside grade level?

    <p>To avoid snow blocking the opening</p> Signup and view all the answers

    Which type of damper can be used to shut off the combustion air when the boiler is off according to the text?

    <p>Fully automatic damper</p> Signup and view all the answers

    What is the percentage of ventilation air openings required in relation to combustion air openings as per CSA B149.1?

    <p>10%</p> Signup and view all the answers

    What happens if natural draft burners experience extreme air starvation according to the text?

    <p>They spill combustion products into the building interior</p> Signup and view all the answers

    Why should care be taken to ensure no water lines are run in the path of cold fresh air?

    <p>To avoid freezing of water lines</p> Signup and view all the answers

    What type of switch must be installed when combustion air is supplied by mechanical means?

    <p>Airflow-sensing switch</p> Signup and view all the answers

    Why should heavy oil lines be protected from cold air according to the text?

    <p>To avoid freezing</p> Signup and view all the answers