quiz image

Boiler Components and Equipment

WiseMood avatar
WiseMood
·
·
Download

Start Quiz

Study Flashcards

78 Questions

What type of air preheater is mentioned in the text?

Steam Coil Air Preheater

Which document provides information on Safety Valves?

MV Vol 5 Part 4 Sec 1

What is the purpose of a Sootblower?

To clean soot from the boiler

Which system is responsible for circulating water in the boiler?

Boiler Circulation Pump System

What type of fans are mentioned in the text?

All of the above

What is the purpose of the Steam Coil Airheater?

To heat air before it enters the boiler

Which document provides information on Sootblowers?

MV Vol 16 Part 5 Sec

What is the purpose of the Combustion and Flue Gas System?

To mix air and gas in the boiler

Which system is responsible for starting up the boiler?

High Pressure Startup and Warmup System

What type of system is the Scanner Air System?

Scanner Air System

What is the primary consideration for soot-blower selection in a boiler?

Boiler configuration and probable dirtying characteristics of the oil ash

Which of the following is not a boiler auxiliary equipment?

Feed-water pumps

What is the primary function of air heaters in a boiler?

To heat the air and gas flows

What is the purpose of soot-blowers in a boiler?

To clean the boiler surfaces

What is the primary consideration for air-heater sizing in a boiler?

Air and gas flows and temperatures

Which of the following is a boiler auxiliary equipment?

Pumps within the boiler circuit

What is the primary function of pumps within the boiler circuit?

To circulate boiler water

Why is it important to consider the boiler configuration and oil ash characteristics in soot-blower selection?

To determine the appropriate soot-blower type and size

What is the recommended duration for supplying station air to high-pressure nozzles after soot blowing?

5 minutes

When should off-load high-pressure water washing be conducted?

Only when required to reduce gas side pressure drop to within acceptable operating limits

What is the recommended increase in gas side pressure differential that warrants high-pressure water washing?

50% over the design value

Why should high-pressure water washing of the heating elements be done only when necessary?

To prevent damage to the heating elements due to high pressure and subsequent surface oxidation

When can the air preheater be water washed?

After the boiler has been shut down and the preheater has been vacuumed clean of ash and debris

What is the recommended timeframe for completing the washing, drying, and inspection process of the air preheater?

24 – 48 hours

Why is it important to vacuum clean the air preheater before water washing?

To remove loose particles and ash

What is a safety precaution that should be taken when inspecting the air preheater?

DO NOT ENTER THE AIRHEATER while the rotor is turning or without proper permits

What is the percentage of steam generation at the point where the warmkeeping system line valve control is set to 60?

35%

At what percentage of steam generation is the warmkeeping system control typically engaged?

20%

What is the primary function of the circulation line management system in a boiler?

To circulate water through the boiler

In which boiler operating mode is the warmkeeping system typically engaged?

Standby mode

What is the purpose of the line valve control in the warmkeeping system?

To control the warmkeeping system

At what point does the steam generation percentage reach 70%?

When the warmkeeping system line valve control is set to 60

What is the primary consideration for managing circulation line valves in a boiler?

Water circulation rate

In which boiler operating mode is the warmkeeping system typically disengaged?

Startup mode

What is the primary purpose of the remote demand feature in the boiler system?

To ensure a delta setpoint between HHV and actual values

What happens to the flow rate when no burner is in service?

It zeros to prevent unnecessary fuel consumption

What is the effect of restricting the valve demand on the boiler system?

It limits the number of burners in service

What is the primary purpose of the delta setpoint in the boiler system?

To ensure a consistent fuel-to-air ratio

What happens when the HHV setpoint is not met?

The fuel-to-air ratio is adjusted

What is the purpose of the controller in the boiler system?

To manage the number of burners in service

What is the effect of having multiple burners in service on the valve demand?

It increases the valve demand

What is the primary purpose of the return flow feature in the boiler system?

To prevent low-pressure nuisance trips

What is the primary function of the ID & FD fan blade pitch control?

To regulate combustion air flow

What is the purpose of the SH & RH spraywater control valves?

To control steam temperature

What is the function of the redundant pressure transmitters in the FAN CONTROL system?

To provide backup pressure measurement

What is the purpose of the furnace pressure control mimic (ID FAN CONTROL)?

To maintain furnace pressure

What type of system is used to control combustion air and flue gas in the boiler?

Auctioneered median-select system

What is the purpose of the windbox air dampers?

To regulate combustion air flow

What is the function of the gas recirculation dampers?

To recirculate gas for emission control

What is the purpose of the startup system control valves?

To control startup system operation

According to NFPA-85-2015, what is the minimum ignition energy required for a Class 1 Igniter?

10% of full load burner fuel input

What is the primary characteristic of a Class 2 Igniter?

Operates under low load or certain adverse operating conditions

What is the typical capacity range of a Class 3 Igniter?

4% to 10% of full load burner fuel input

What is a Class 3 Special Igniter capable of?

Directly igniting the main burner fuel

What is the primary function of an igniter in a combustion system?

To provide sufficient ignition energy under any burner light-off or operating conditions

According to NFPA-85-2015, what is the purpose of an igniter in a combustion system?

To provide sufficient ignition energy to raise any credible combination of burner inputs

What is the tilt range of the nozzles in the Twin Fireball burner arrangement?

+/- 30°

How many Main WB Assemblies are vertically stacked in the Twin Fireball burner arrangement?

Eight (8)

What is the function of the Auto Tilt System in the FGR Elevations?

+/- 30° CC-OFA thru UFA tilt control

What type of system is the Spinner Vane Stabilized Oil Elevation?

HEA system

How many NG Elevations are there in the Twin Fireball burner arrangement?

Three (3)

What type of Ignitor & Flame Scanner system is used in the NG Elevations?

Twin Ignitor system

What is the primary function of the High Energy Arc (HEA) Retractable Ignitor?

To light off the main fuel directly without a separate pilot ignitor

What is the stroke length of the pneumatic cylinder in the HEA Retractable Ignitor?

8 inches

What is the purpose of the solenoid in the HEA Retractable Ignitor?

To retract the ignitor on loss of power

What is the typical insertion length of the HEA Rod Assembly into the wet spray?

7 inches

What is the purpose of the advance and retract limit switches in the HEA Retractable Ignitor?

To limit the advance and retract motion of the ignitor

What is the typical application of the High Energy Arc (HEA) Retractable Ignitor?

Lightoff of oil guns

What is the primary function of the NFPA Class 1 Ignitor?

To support ignition under any burner light-off or operating conditions

What is the firing rate of the NG Pipe Ignitor?

24 MBTU/Hr

What is the purpose of the Compartment Ignitor Proven Vote?

To prove both ignitors in the compartment are in service via IFM Flame Rod

What is the heat input required for the main gas operation?

10% Compartment Heat Input

What is the purpose of the Air Inlet in the Yanbu LIMELIGHTTM 3” NG Pipe Ignitors?

To provide combustion air to the burner

What is the primary function of the Ignitor Assembly?

To provide ignition energy to the burner

What is the purpose of the Twin 3-inch NG Pipe 12 MBTU/Hr Ignitors?

To provide ignition energy to the burner

What is the total fuel heat input of the NG Compartment?

6,087 MBTU/Hr

What is the purpose of the Main Gas Operation?

To require 3 of 4 Compartment Ignitor Votes at Elevation

What is the percentage of Compartment Heat Input required for the Main Gas Operation?

10% Compartment Heat Input

Study Notes

Boiler Auxiliaries

  • Boiler auxiliaries include air preheaters, soot blowers, safety valves, fans, and boiler circulation pumps.
  • These components are essential to the operation of the boiler and represent a significant portion of the overall steam-generator investment.

Air Preheaters

  • Air preheaters are sized based on air and gas flows and temperatures, as well as allowable static pressure losses.
  • Steam coil air preheaters require a manual for operation.
  • Air preheaters can be water washed, but only when necessary, with the air preheater out of service, and after the boiler has been shut down and vacuumed clean.

Soot Blowers

  • Soot blowers are selected based on the boiler configuration and probable dirtying characteristics of the oil ash.
  • Soot blower systems include half retract and full retract soot blowers.

Fans

  • Fans are used in the boiler auxiliary system, including forced draft air fans and gas recirculation fans.

Safety Valves

  • Safety valves are used in the boiler system, including electromatic relief valves.

Boiler Circulation Pumps

  • Boiler circulation pumps are used to circulate water within the boiler circuit.

Operation and Maintenance

  • Station air must be supplied to the high-pressure nozzles for 5 minutes after soot blowing.
  • High-pressure water washing should be conducted only when required to reduce the gas side pressure drop to within acceptable operating limits.
  • Off-load high-pressure water washing should be conducted only when required.
  • The air preheater should be inspected through the observation ports during and after washing.

References

  • Multiple manuals and P&ID diagrams are referenced for specific equipment and systems.

Boiler Controls Training

  • Warmkeeping System Line Valve Control prevents low pressure nuisance trips and zeros flow if no burner is in service.
  • Remote demand comes in with delta setpoint to actual, restricted by the number of burners in service.

Controlled Equipment - Unit

  • ID & FD FAN BLADE PITCH CONTROL is part of the CLC controlled equipment.
  • FUEL CONTROL VALVES, BOILER FEEDWATER DEMAND, SH & RH SPRAYWATER CONTROL VALVES, STARTUP SYSTEM CONTROL VALVES, WINDBOX AIR DAMPERS, WINDBOX TILTS, GAS RECIRCULATION DAMPERS, and STEAM COIL CONTROL VALVES are also part of the CLC controlled equipment.

Fan Control

  • Redundant pressure transmitters are used in fan control.

Combustion Air and Flue Gas Overview

  • Combustion air and flue gas overview is a crucial part of boiler controls training.

Combustion Air and Flue Gas Train A

  • Specific training is provided for combustion air and flue gas Train A.

Furnace Pressure Control Mimic (ID FAN CONTROL)

  • Furnace pressure control mimic is used in ID FAN CONTROL.

Furnace Pressure / ID FAN CONTROL

  • Furnace pressure control is crucial for ID FAN CONTROL.

NFPA 85 - Furnace Pressure Control Functional Requirements

  • Block A shows the requirements for three furnace pressure transmitters arranged in an auctioneered median-select system, each on a separate pressure sensing tap, as per NFPA 85.

NFPA 85 Igniter Types

  • Class 1 Igniter: Provides sufficient ignition energy (over 10% of full load burner input) to ignite fuel input under any burner light-off or operating conditions.
  • Class 2 Igniter: Provides ignition energy (4-10% of full load burner fuel input) under prescribed light-off conditions and supports ignition under low load or adverse operating conditions.
  • Class 3 Igniter: A small igniter that ignites fuel input to the burner under prescribed light-off conditions, with a capacity not exceeding 4% of the full load burner fuel input.
  • Class 3 Special Igniter: A high energy electrical igniter capable of directly igniting the main burner fuel.

High Energy Arc (HEA) Retractable Ignitor

  • Defined as a Class 3 Special Ignitor per NFPA 85.
  • Capable of directly igniting the main burner fuel without a separate pilot ignitor.
  • Standard GE practice for light-off of oil guns since the 1980s.
  • Features an 8” stroke pneumatic cylinder, solenoid (retracts on loss of power), and advance and retract limit switches.

HEA Rod Assembly

  • Comprises a guide tube and an HEA spark rod (Champion).
  • The HEA spark rod is part of the HEA rod assembly.

HEA Insertion Target

  • The HEA insertion target has an 8” stroke and inserts 7” into the spray.

Yanbu III Key Features

  • Twin Fireball - Eight (8) Main WB Assemblies – Vertically Stacked Nozzles with +/- 30° Tilt Range.
  • Future NG Elevation - Top End Air.
  • 4 Spinner Vane Stabilized Oil Elevations / HEA & Flame Scanner.
  • 3 NG Elevations / Twin Ignitor & Flame Scanner.
  • Auto Tilt System +/- 30° CC-OFA thru UFA.
  • CC-OFA +/- 20° Yaw.
  • Top / BTM End Air.
  • UFA Elevation.
  • FGR Elevations +/- 30° Manual Tilt.

Corner Firing - Twin Fireball / One Burner - Control

  • Features a corner firing arrangement.

Gas Firing System

  • Yanbu firing system orientation is used for gas firing.
  • Air flow control and distribution are crucial for proper air distribution.

Ignitor Assembly

  • Components of the LimelightTM NG Pipe Ignitor include Spark Wiring, DFI Wiring Connection, Air Inlet, Dust Cap, Camlock Coupling, and ¼” NPT Gas Pressure Tap.

Gas Supply and Pressure

  • NG Supply Pressure should be set to 2.8 psig for 12 BTU/hr.
  • Air Pressure should be set to 3 in wc dp with lower furnace static pressure.
  • NG Pressure can be adjusted via Valve Train Manual Globe Valve.
  • Air Pressure can be adjusted via Butterfly Valve.

Scanner Cooling Air/Ignitor Air

  • A pressure control damper is used to maintain a constant differential pressure between the Scanner Cooling/Ignitor Air Header and the Furnace.
  • The ignition system may also be sized to provide sufficient heat input for warming of the unit.

NG Compartment – Pipe Ignitor

  • NFPA Class 1 Ignitor is used to ignite the fuel input through the burner and to support ignition under any burner light-off or operating conditions.
  • The ignitor provides sufficient ignition energy, typically in excess of 10% of full load burner input, at its associated burner to raise any credible combination of burner inputs of both fuel and air above the minimum ignition temperature.

NG Pipe Ignitor – 2 x 12 MBTU/Hr

  • Class I Ignitor provides 10% Heat Input.
  • NG Total Fuel Heat Input is 6,087 MBTU/Hr BMCR.
  • Ignitor Firing Rate is 24 MBTU/Hr.
  • Compartment Ignitor Proven Vote requires proving both ignitors in the compartment are in-service via IFM Flame Rod.
  • Main Gas Operation requires 3 of 4 Compartment Ignitor Votes at Elevation - per Furnace Cell.

This quiz covers various components and equipment used in boilers, including air preheaters, soot blowers, safety valves, fans, and boiler circulation pumps. Test your knowledge of these essential systems.

Make Your Own Quizzes and Flashcards

Convert your notes into interactive study material.

Get started for free

More Quizzes Like This

Boiler Safety
11 questions

Boiler Safety

WholesomeMaroon avatar
WholesomeMaroon
Use Quizgecko on...
Browser
Browser