II-C-09 Facilities Management Procedures 04/15/2019 - II
13 Questions
0 Views

II-C-09 Facilities Management Procedures 04/15/2019 - II

Created by
@AuthoritativeProse

Questions and Answers

What is the primary function of the Air Cleaning Device (ACD)?

  • To control the humidity levels in the facility.
  • To filter and clean the apparatus bay of gases. (correct)
  • To detect gas levels in the apparatus bay.
  • To provide ventilation to the apparatus bay.
  • What does a RED LIGHT indicate on the ACD Light Indicator?

  • The ACD is currently undergoing maintenance.
  • The system filter requires changing. (correct)
  • The system filter is functioning at optimal capacity.
  • System is active and functioning normally.
  • When does the General Exhaust Fan (GEF) switch to HIGH speed?

  • When it is activated manually.
  • Immediately upon power restoration.
  • When the GEF reaches the maximum operational temperature.
  • When the apparatus bay doors are opened and then closed. (correct)
  • What level of CO will trigger the yellow alarm light?

    <p>10 ppm</p> Signup and view all the answers

    What action should be taken if the GEF motor fan is not functioning?

    <p>Conduct a ‘paper test’ against the grill.</p> Signup and view all the answers

    What should be done if the CVC view panel flashes red?

    <p>Submit a service request</p> Signup and view all the answers

    What does a continuous beeping sound from the electrical UPS indicate?

    <p>The battery is low</p> Signup and view all the answers

    What is the maximum carbon monoxide (CO) level that can activate the alarm in the Central Ventilation Control (CVC) Box?

    <p>25 ppm</p> Signup and view all the answers

    How long does the GEF operate at HIGH speed after activation?

    <p>20 minutes</p> Signup and view all the answers

    What action is not required when CO levels reach 10 ppm?

    <p>Take immediate action to evacuate</p> Signup and view all the answers

    What does a green light indicate on the system?

    <p>The system is active</p> Signup and view all the answers

    What should be done if neither the GREEN nor RED LIGHTS are visible on the ACD?

    <p>Submit a Facilities Service Request for ACD Repair.</p> Signup and view all the answers

    Which gases are detected by the nitrogen dioxide (NO2) and carbon monoxide (CO) gas sensors?

    <p>Both nitrogen dioxide and carbon monoxide.</p> Signup and view all the answers

    Study Notes

    Air Cleaning Device (ACD)

    • Features a 3-stage filtering system: pre-filter, primary filter, and gas/odor filter.
    • Effectively cleans the apparatus bay of gases within 20 minutes of activation.

    ACD Light Indicators

    • GREEN LIGHT: Indicates the system is active (ON position).
    • RED LIGHT: Signals that the system filter needs changing; the CVC view panel will also flash RED.
    • If neither light is illuminated, the Station OIC must submit an electronic Facilities Service Request.

    General Exhaust Fan (GEF)

    • Operates primarily in LOW speed, only switching to HIGH speed upon detecting registered gas levels.
    • When apparatus bay doors are opened and closed, or gas levels exceed set limits, GEF operates in HIGH speed for a minimum of 20 minutes.
    • To check fan operation, perform a 'paper test'; if paper does not stick to the grill, submit a Facilities Service Request for GEF Repair.

    Gas Sensors

    • Nitrogen Dioxide (NO2) and Carbon Monoxide (CO) gas sensors monitor air quality within the apparatus bay.

    Central Ventilation Control (CVC) Box

    • OFF Position: System is inactive.
    • ALARM B (Red Box Light): Activates at CO levels of 25 ppm and/or NO2 levels of 2 ppm; no immediate action required as the system clears gases in 20 minutes.
    • ALARM A (Yellow Box Light): Activates at CO levels of 10 ppm and/or NO2 levels of 0.7 ppm; serves as a precaution, with the system also clearing gases.

    CVC View Panel

    • A flashing RED screen indicates a dirty filter requiring service: "Fan 1 Filter Full."
    • Immediate submission of a Facilities Service Request is necessary upon encountering a flashing red light.

    Electrical UPS/Battery Back-Up

    • Continuous beeping indicates a low battery; the system should not be turned off.
    • The Station OIC is responsible for submitting a Facilities Service Request for battery servicing.