II-C-09 Facilities Management Procedures 04/15/2019 - II
13 Questions
1 Views

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to lesson

Podcast

Play an AI-generated podcast conversation about this lesson

Questions and Answers

What is the primary function of the Air Cleaning Device (ACD)?

  • To control the humidity levels in the facility.
  • To filter and clean the apparatus bay of gases. (correct)
  • To detect gas levels in the apparatus bay.
  • To provide ventilation to the apparatus bay.
  • What does a RED LIGHT indicate on the ACD Light Indicator?

  • The ACD is currently undergoing maintenance.
  • The system filter requires changing. (correct)
  • The system filter is functioning at optimal capacity.
  • System is active and functioning normally.
  • When does the General Exhaust Fan (GEF) switch to HIGH speed?

  • When it is activated manually.
  • Immediately upon power restoration.
  • When the GEF reaches the maximum operational temperature.
  • When the apparatus bay doors are opened and then closed. (correct)
  • What level of CO will trigger the yellow alarm light?

    <p>10 ppm</p> Signup and view all the answers

    What action should be taken if the GEF motor fan is not functioning?

    <p>Conduct a ‘paper test’ against the grill.</p> Signup and view all the answers

    What should be done if the CVC view panel flashes red?

    <p>Submit a service request</p> Signup and view all the answers

    What does a continuous beeping sound from the electrical UPS indicate?

    <p>The battery is low</p> Signup and view all the answers

    What is the maximum carbon monoxide (CO) level that can activate the alarm in the Central Ventilation Control (CVC) Box?

    <p>25 ppm</p> Signup and view all the answers

    How long does the GEF operate at HIGH speed after activation?

    <p>20 minutes</p> Signup and view all the answers

    What action is not required when CO levels reach 10 ppm?

    <p>Take immediate action to evacuate</p> Signup and view all the answers

    What does a green light indicate on the system?

    <p>The system is active</p> Signup and view all the answers

    What should be done if neither the GREEN nor RED LIGHTS are visible on the ACD?

    <p>Submit a Facilities Service Request for ACD Repair.</p> Signup and view all the answers

    Which gases are detected by the nitrogen dioxide (NO2) and carbon monoxide (CO) gas sensors?

    <p>Both nitrogen dioxide and carbon monoxide.</p> Signup and view all the answers

    Study Notes

    Air Cleaning Device (ACD)

    • Features a 3-stage filtering system: pre-filter, primary filter, and gas/odor filter.
    • Effectively cleans the apparatus bay of gases within 20 minutes of activation.

    ACD Light Indicators

    • GREEN LIGHT: Indicates the system is active (ON position).
    • RED LIGHT: Signals that the system filter needs changing; the CVC view panel will also flash RED.
    • If neither light is illuminated, the Station OIC must submit an electronic Facilities Service Request.

    General Exhaust Fan (GEF)

    • Operates primarily in LOW speed, only switching to HIGH speed upon detecting registered gas levels.
    • When apparatus bay doors are opened and closed, or gas levels exceed set limits, GEF operates in HIGH speed for a minimum of 20 minutes.
    • To check fan operation, perform a 'paper test'; if paper does not stick to the grill, submit a Facilities Service Request for GEF Repair.

    Gas Sensors

    • Nitrogen Dioxide (NO2) and Carbon Monoxide (CO) gas sensors monitor air quality within the apparatus bay.

    Central Ventilation Control (CVC) Box

    • OFF Position: System is inactive.
    • ALARM B (Red Box Light): Activates at CO levels of 25 ppm and/or NO2 levels of 2 ppm; no immediate action required as the system clears gases in 20 minutes.
    • ALARM A (Yellow Box Light): Activates at CO levels of 10 ppm and/or NO2 levels of 0.7 ppm; serves as a precaution, with the system also clearing gases.

    CVC View Panel

    • A flashing RED screen indicates a dirty filter requiring service: "Fan 1 Filter Full."
    • Immediate submission of a Facilities Service Request is necessary upon encountering a flashing red light.

    Electrical UPS/Battery Back-Up

    • Continuous beeping indicates a low battery; the system should not be turned off.
    • The Station OIC is responsible for submitting a Facilities Service Request for battery servicing.

    Studying That Suits You

    Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

    Quiz Team

    Description

    Test your knowledge on the Air Cleaning Device (ACD) used in apparatus bays. This quiz covers the 3-stage filtering system, including pre-filters, primary filters, and gas/odor filters. Learn about the ACD light indicators and their meanings.

    More Like This

    Use Quizgecko on...
    Browser
    Browser