Document Details

Uploaded by PatriIllumination
Full Transcript
ough 53 (trade sizes 11â„2 through 2) (3) 1500 mm (5 ft) for metric designators 63 (trade size 21â„2) and larger Exception No. 3: Lengths not exceeding 1.8 m (6 ft) from a luminaire terminal connection for tap connections to luminaires as permitted in 410.117(C). Exception No. 4: Lengths not excee...
ough 53 (trade sizes 11â„2 through 2) (3) 1500 mm (5 ft) for metric designators 63 (trade size 21â„2) and larger Exception No. 3: Lengths not exceeding 1.8 m (6 ft) from a luminaire terminal connection for tap connections to luminaires as permitted in 410.117(C). Exception No. 4: Lengths not exceeding 1.8 m (6 ft) from the last point where the raceway is securely fastened for connections within an accessible ceiling to a luminaire(s) or other equipment. For the purposes of the exceptions, listed FMC fittings shall be permitted as a means of securement and support. ENHANCED CONTENT Collapse Listing of cable ties for securement and support of FMC is necessary because the standard requires markings that identify critical performance characteristics. These characteristics can affect their suitability for the conditions of use, including minimum and maximum operating temperatures and resistance to ultraviolet light for outdoor installations. Exception No. 2. An example of the phrase “where flexibility is necessary after installation†is an installation of FMC to a motor mounted on an adjustable or sliding frame, where the frame is required to be movable for drive belt maintenance. The length that the exception addresses is the length from the last point where the FMC is securely fastened. Exception No. 4. Securing a raceway can be different from supporting the raceway. Specifying that the listed FMC fitting provides the securement also required by this section clarifies that the listed fitting provides both securement and support of the FMC. Supports. Horizontal runs of FMC supported by openings through framing members at intervals not greater than 1.4 m (41â„2 ft) and securely fastened within 300 mm (12 in.) of termination points shall be permitted. 348.42 Couplings and Connectors. Angle connectors shall not be concealed. 348.56 Splices and Taps. Splices and taps shall be made in accordance with 300.15. 348.60 Grounding and Bonding. ENHANCED CONTENT Collapse An additional EGC is always required where FMC is used for flexibility. Examples of such installations include using FMC to minimize the transmission of equipment vibration such as motors or to provide flexibility for floodlights, spotlights, or other equipment that require adjustment after installation. According to ANSI/UL 1, Standard for Flexible Metal Conduit, FMC longer than 6 feet has not been judged to be suitable for grounding purposes. If the length of the total ground-fault return path exceeds 6 feet or the circuit overcurrent protection exceeds 20 amperes, a separate EGC must be installed with the circuit conductors according to 250.118(5). In the following exhibit, the top section shows an acceptable application of FMC, where the total length of any ground return path is limited to 6 feet. The bottom figure shows an application that is unacceptable because the grounding return path for Luminaire 2 exceeds the permitted maximum of 6 feet to the box. Where FMC is used in hazardous (classified) locations, a bonding jumper is required. Section 250.102(E) permits the routing of equipment bonding jumpers on the outside of the raceway in lengths that are no longer than 6 feet and bonded at each end. Fixed Installation. FMC shall be permitted to be used as an equipment grounding conductor when installed in accordance with 250.118(A)(5) where flexibility is not required after installation. Flexible Installation. An equipment grounding conductor shall be installed where flexibility is necessary to minimize the transmission of vibration from equipment or to provide flexibility for equipment that requires movement after installation. Equipment Grounding Conductors. Where required or installed, equipment grounding conductors shall be installed in accordance with 250.134. Equipment Bonding Jumpers. Where required or installed, equipment bonding jumpers shall be installed in accordance with 250.102. Article 350 Liquidtight Flexible Metal Conduit (LFMC) Part I. General 350.1 Scope. This article covers the use, installation, and construction specifications for liquidtight flexible metal conduit (LFMC) and associated fittings. ENHANCED CONTENT Collapse LFMC is intended for use in wet locations or where exposed to oil or coolants, at a maximum temperature of 140°F. LFMC is not intended for use where exposed to gasoline or similar light petroleum solvents unless so marked on the product. If properly marked for the application, LFMC is permitted for direct burial in the earth. LFMC is on the permitted list of wiring methods for services (see 230.43), provided the length does not exceed 6 feet and an equipment bonding jumper is installed in accordance with 250.102. LFMC may be installed in unlimited lengths, provided it meets the other requirements of Article 350 and a separate equipment grounding conductor (EGC) is installed with the circuit conductors. 350.2 Reconditioned Equipment. LFMC shall not be reconditioned. 350.6 Listing Requirements. LFMC and associated fittings shall be listed. Part II. Installation 350.10 Uses Permitted. LFMC shall be permitted to be used in exposed or concealed locations as follows: (1) Where conditions of installation, operation, or maintenance require flexibility or protection from machine oils, liquids, vapors, or solids. In hazardous (classified) locations where specifically permitted by Chapter 5. For direct burial where listed and marked for the purpose. Conductors or cables rated at a temperature higher than the listed temperature rating of LFMC shall be permitted to be installed in LFMC, provided the conductors or cables are not operated at a temperature higher than the listed temperature rating of the LFMC. 350.12 Uses Not Permitted. LFMC shall not be used where subject to physical damage. 350.20 Size. (A) Minimum. LFMC smaller than metric designator 16 (trade size 1â„2) shall not be used. Exception: LFMC of metric designator 12 (trade size 3â„8) shall be permitted as covered in 348.20(A). (B) Maximum. The maximum size of LFMC shall be metric designator 103 (trade size 4). Informational Note: See 300.1(C) for the metric designators and trade sizes. These are for identification purposes only and do not relate to actual dimensions. 350.22 Number of Conductors or Cables. (A) Metric Designators 16 through 103 (Trade Sizes 1â„2 through 4). The number of conductors shall not exceed that permitted by the percentage fill specified in Table 1, Chapter 9. Cables shall be permitted to be installed where such use is not prohibited by the respective cable articles. The number of cables shall not exceed the allowable percentage fill specified in Table 1, Chapter 9. Metric Designator 12 (Trade Size 3â„8). The number of conductors shall not exceed that permitted in Table 348.22, “Fittings Outside Conduit†columns. ENHANCED CONTENT Collapse Table 4, Dimensions and Percent Area of Conduit and Tubing, of Chapter 9 provides the usable area within the selected conduit or tubing, and Table 5, Dimensions of Insulated Conductors and Fixture Wires, provides the required area for each conductor. Examples using these tables to calculate a conduit or tubing size are provided below. To select the proper trade size of LFMC, see the appropriate sub-table within Table 4 of Chapter 9: Article 350 — Liquidtight Flexible Metal Conduit (LFMC). If the conductors are of the same wire size, Tables C.8 and C.8(A) for LFMC in Informative Annex C can be used instead of performing the calculations. The exception to 350.20(A) permits the use of trade size â…œ LFMC under the limited conditions specified for flexible metal conduit (FMC) in 348.20(A). See also Table 348.22 for the number of conductors permitted in trade size â…œ LFMC. 350.24 Bends. How Made. Bends in conduit shall be so made that the conduit will not be damaged and the internal diameter of the conduit will not be effectively reduced. Bends shall be permitted to be made manually without auxiliary equipment. The radius of the curve to the centerline of any bend shall not be less than required in Table 2, Chapter 9 using the column “Other Bends.†Number in One Run. The total degrees of bends in a conduit run shall not exceed 360 degrees between pull points. 350.28 Trimming. All cut ends of conduit shall be trimmed inside and outside to remove rough edges. ENHANCED CONTENT Collapse Proper trimming of the cut ends of LFMC is necessary to allow for the proper installation of the steel grounding ferrule, which is required to maintain ground continuity of the steel sheath. 350.30 Securing and Supporting. LFMC shall be securely fastened in place and supported in accordance with 350.30(A) and (B). Securely Fastened. LFMC shall be securely fastened in place by an approved means within 300 mm (12 in.) of each box, cabinet, conduit body, or other conduit termination and shall be supported and secured at intervals not to exceed 1.4 m (41â„2 ft). Where used, cable ties shall be listed and be identified for securement and support. Exception No. 1: Where LFMC is fished between access points through concealed spaces in finished buildings or structures and supporting is impractical. Exception No. 2: Where flexibility is necessary after installation, lengths from the last point where the raceway is securely fastened shall not exceed the following: (1) 900 mm (3 ft) for metric designators 16 through 35 (trade sizes 1â„2 through 11â„4) (2) 1200 mm (4 ft) for metric designators 41 through 53 (trade sizes 11â„2 through 2) (3) 1500 mm (5 ft) for metric designators 63 (trade size 21â„2) and larger Exception No. 3: Lengths not exceeding 1.8 m (6 ft) from a luminaire terminal connection for tap conductors to luminaires, as permitted in 410.117(C). Exception No. 4: Lengths not exceeding 1.8 m (6 ft) from the last point where the raceway is securely fastened for connections within an accessible ceiling to luminaire(s) or other equipment. For the purposes of the exceptions, listed LFMC fittings shall be permitted as a means of securement and support. ENHANCED CONTENT Collapse Listing of cable ties for securement and support of LFMC is necessary because the standard requires markings that identify critical performance characteristics. These characteristics can affect their suitability for the conditions of use, including minimum and maximum operating temperatures, and resistance to ultraviolet light for outdoor installations. Exception No. 4. Securing LFMC can be different from supporting it. The listed fittings are now recognized to provide the securement as well as the support required by this section. Supports. Horizontal runs of LFMC supported by openings through framing members at intervals not greater than 1.4 m (41â„2 ft) and securely fastened within 300 mm (12 in.) of termination points shall be permitted. 350.42 Couplings and Connectors. Only fittings listed for use with LFMC shall be used. Angle connectors shall not be concealed. Straight LFMC fittings shall be permitted for direct burial where marked. 350.56 Splices and Taps. Splices and taps shall be made in accordance with 300.15. 350.60 Grounding and Bonding. Fixed Installation. LFMC shall be permitted to be used as an equipment grounding conductor when installed in accordance with 250.118(A)(6) where flexibility is not required after installation. Flexible Installation. An equipment grounding conductor shall be installed where flexibility is necessary to minimize the transmission of vibration from equipment or to provide flexibility for equipment that requires movement after installation. Equipment Grounding Conductor. Where required or installed, equipment grounding conductors shall be installed in accordance with 250.134. Equipment Bonding Jumpers. Where required or installed, equipment bonding jumpers shall be installed in accordance with 250.102. Informational Note: See 501.30(B)(2), 502.30(B)(2), 503.30(B)(2), 505.30(B)(2), and 506.30(B)(2) for types of equipment grounding conductors. Part III. Construction Specifications 350.120 Marking. LFMC shall be marked according to 110.21. The trade size and other information required by the listing shall also be marked on the conduit. Conduit suitable for direct burial shall be so marked. Article 352 Rigid Polyvinyl Chloride Conduit (PVC) Part I. General 352.1 Scope. This article covers the use, installation, and construction specifications for rigid polyvinyl chloride conduit (PVC) and associated fittings. ENHANCED CONTENT Collapse The UL Guide Information for Electrical Equipment describes rigid PVC conduit, Type PVC, for use in accordance with Article 352. Schedule 40 is suitable for locations not subject to physical damage for underground, aboveground, indoor, and outdoor locations. Schedule 80 is suitable for locations where the conduit will be subject to damage. Types A and EB are intended for underground installations. 352.6 Listing Requirements. PVC conduit, factory elbows, and associated fittings shall be listed. Part II. Installation 352.10 Uses Permitted. The use of PVC conduit shall be permitted in accordance with 352.10(A) through (K). Informational Note: Extreme cold may cause some nonmetallic conduits to become brittle and, therefore, more susceptible to damage from physical contact. (A) Concealed. PVC conduit shall be permitted in walls, floors, and ceilings. Encased in Concrete. PVC conduit shall be permitted to be encased in concrete. Corrosive Influences. PVC conduit shall be permitted in locations subject to severe corrosive influences as covered in 300.6 and where subject to chemicals for which the materials are specifically approved. Cinders. PVC conduit shall be permitted in cinder fill. Wet Locations. PVC conduit shall be permitted in portions of dairies, laundries, canneries, or other wet locations, and in locations where walls are frequently washed, the entire conduit system, including boxes and fittings used therewith, shall be installed and equipped so as to prevent water from entering the conduit. All supports, bolts, straps, screws, and so forth, shall be of corrosion-resistant materials or be protected against corrosion by approved corrosion-resistant materials. Dry and Damp Locations. PVC conduit shall be permitted for use in dry and damp locations not prohibited by 352.12. Exposed. PVC conduit shall be permitted for exposed work. Underground Installations. For underground installations, PVC shall be permitted for direct burial and underground encased in concrete. See 300.5 and 305.15. ENHANCED CONTENT Collapse Schedule 40 and Schedule 80 PVC are both permitted for underground installations, such as under driveways, provided that the required burial depth is met. See also Table 300.5(A) for burial depth minimum cover requirements for 1000 V ac or less underground installations. For burial depth minimum cover requirements for over 1000 V ac underground installations, see Table 305.15(A). Support of Conduit Bodies. PVC conduit shall be permitted to support nonmetallic conduit bodies not larger than the largest trade size of an entering raceway. These conduit bodies shall not support luminaires or other equipment and shall not contain devices other than splicing devices as permitted by 110.14(B) and 314.16(C)(2). Insulation Temperature Limitations. Conductors or cables rated at a temperature higher than the listed temperature rating of PVC conduit shall be permitted to be installed in PVC conduit, provided the conductors or cables are not operated at a temperature higher than the listed temperature rating of the PVC conduit. ENHANCED CONTENT Collapse Conductors marked with a rated temperature higher than that of the raceway can be used if the conductors are to be operated within the raceway temperature rating. One application is the use of 105°C-rated medium-voltage cables, Type MV, where the cable ampacity at the 105°C rating is reduced to the cable ampacity at 75°C or 90°C to match the listed operating temperature rating of the PVC conduit (75°C or 90°C). Physical Damage. Where subject to physical damage, Schedule 80 PVC conduit, Schedule 80 PVC elbows, and listed fittings for PVC conduit shall be used. Informational Note: All listed PVC conduit fittings are suitable for connection to both Schedule 40 and Schedule 80 PVC conduit. 352.12 Uses Not Permitted. PVC conduit shall not be used under the conditions specified in 352.12(A) through (E). Hazardous (Classified) Locations. In any hazardous (classified) location, except as permitted by other articles of this Code. Support of Luminaires. For the support of luminaires or other equipment not described in 352.10(I). Physical Damage. Where subject to physical damage, except as permitted in 352.10(K). Ambient Temperatures. Where subject to ambient temperatures in excess of 50°C (122°F) unless listed otherwise. Theaters and Similar Locations. In theaters and similar locations, except as provided in 518.4 and 520.5. ENHANCED CONTENT Collapse In addition to the conditions in 352.12(A) through (E), PVC conduits are not permitted to be installed in ducts, plenums, and other air-handling spaces. For limitations of the use of materials in ducts, plenums, and other air-handling spaces, which could contribute smoke and products of combustion during a fire 300.22. 352.20 Size. (A) Minimum. PVC conduit smaller than metric designator 16 (trade size 1â„2) shall not be used. Maximum. PVC conduit larger than metric designator 155 (trade size 6) shall not be used. Informational Note: See 300.1(C) for the trade sizes and metric designators that are for identification purposes only and do not relate to actual dimensions. 352.22 Number of Conductors. The number of conductors shall not exceed that permitted by the percentage fill specified in Table 1, Chapter 9. Cables shall be permitted to be installed where such use is not prohibited by the respective cable articles. The number of cables shall not exceed the allowable percentage fill specified in Table 1, Chapter 9. ENHANCED CONTENT Collapse Table 4, Dimensions and Percent Area of Conduit and Tubing, of Chapter 9 provides the usable area within the selected conduit or tubing, and Table 5, Dimensions of Insulated Conductors and Fixture Wires, provides the required area for each conductor. Examples using these tables to calculate a conduit or tubing size are provided below. To select the proper trade size of PVC conduit, see the appropriate sub-table for Article 352, Rigid PVC Conduit (PVC), in Table 4 of Chapter 9. If the conductors are of the same wire size and insulation type, Tables C.10 and C.10(A) through Tables C.13 and C.13(A) of Informative Annex C can be used instead of performing the calculations, provided the appropriate table for the given type of PVC conduit is used. 352.24 Bends. ENHANCED CONTENT Collapse Pulling conductors in underground conduit can damage nonmetallic elbows. Metal elbows are often used to ensure the raceway’s integrity. Metal elbows in runs of PVC conduit that are buried at least 18 inches are not required to be bonded to the system grounded conductor or the grounding electrode conductor (GEC). See also 250.80, Exception, for more information on metal elbows in service raceways and enclosures. For common raceway field bend measurements see Table 2 of Chapter 9. How Made. Bends shall be so made that the conduit will not be damaged and the internal diameter of the conduit will not be effectively reduced. Field bends shall be made only with identified bending equipment. The radius of the curve to the centerline of such bends shall not be less than shown in Table 2, Chapter 9. Number in One Run. The total degrees of bends in a conduit run shall not exceed 360 degrees between pull points. 352.28 Trimming. All cut ends shall be trimmed inside and outside to remove rough edges. 352.30 Securing and Supporting. PVC conduit shall be instalâ led as a complete system as provided in 300.18 and shall be fastened so that movement from thermal expansion or contraction is permitted. PVC conduit shall be securely fastened and supported in accordance with 352.30(A) and (B). Securely Fastened. PVC conduit shall be securely fastened within 900 mm (3 ft) of each outlet box, junction box, device box, conduit body, or other conduit termination. Conduit listed for securing at other than 900 mm (3 ft) shall be permitted to be installed in accordance with the listing. Supports. PVC conduit shall be supported as required in Table 352.30(B). Conduit listed for support at spacings other than as shown in Table 352.30(B) shall be permitted to be installed in accordance with the listing. Horizontal runs of PVC conduit supported by openings through framing members at intervals not exceeding those in Table 352.30(B) and securely fastened within 900 mm (3 ft) of termination points shall be permitted. Table 352.30(B) Support of Rigid Polyvinyl Chloride Conduit (PVC) Conduit Size Maximum Spacing Between Supports Metric Designator Trade Size mm or m ft 16–27 1â„ 2 –1 900 mm 3 35–53 11â„4–2 1.5 m 5 63–78 21â„2–3 1.8 m 6 91–129 31â„2–5 2.1 m 7 155 6 2.5 m 8 352.44 Expansion Fittings. Thermal Expansion and Contraction. Expansion fittings for PVC conduit shall be provided to compensate for thermal expansion and contraction where the length change, in accordance with Table 352.44(A), is expected to be 6 mm (1â„4 in.) or greater in a straight run between securely mounted items such as boxes, cabinets, elbows, or other conduit terminations. Table 352.44(A) Expansion Characteristics of PVC Rigid Nonmetallic Conduit Coefficient of Thermal Expansion = 6.084 × 10–5 mm/mm/°C (3.38 × 10–5 in./in./°F) Temperature Change (°C) Length Change of PVC Conduit (mm/m) Temperature Change (°F) Length Change of PVC Conduit (in./100 ft) Temperature Change (°F) Length Change of PVC Conduit (in./100 ft) 5 0.30 5 0.20 105 4.26 10 0.61 10 0.41 110 4.46 15 0.91 15 0.61 115 4.66 20 1.22 20 0.81 120 4.87 25 1.52 25 1.01 125 5.07 30 1.83 30 1.22 130 5.27 35 2.13 35 1.42 135 5.48 40 2.43 40 1.62 140 5.68 45 2.74 45 1.83 145 5.88 50 3.04 50 2.03 150 6.08 55 3.35 55 2.23 155 6.29 60 3.65 60 2.43 160 6.49 65 3.95 65 2.64 165 6.69 70 4.26 70 2.84 170 6.90 75 4.56 75 3.04 175 7.10 80 4.87 80 3.24 180 7.30 85 5.17 85 3.45 185 7.50 90 5.48 90 3.65 190 7.71 95 5.78 95 3.85 195 7.91 100 6.08 100 4.06 200 8.11 ENHANCED CONTENT Collapse Because PVC conduit exhibits a considerable change in length during a change in temperature, expansion fittings are required for specific temperature variations. According to Table 352.44(A), a 100-foot run of PVC conduit will change 4.06 inches in length if the temperature change is 100°F. The allowable range of expansion for many PVC conduit expansion couplings is ge