Stand Pipe Systems Flashcards

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to Lesson

Podcast

Play an AI-generated podcast conversation about this lesson
Download our mobile app to listen on the go
Get App

Questions and Answers

What is the purpose of a standpipe system?

A standpipe system is intended to eliminate the need for excessively long runs of hose for manual firefighting.

What is a Class 1 standpipe?

Intended for fire department use only, equipped with a 2 1/2 in. (65 mm) angle valve for hose attachment.

What NFPA standard covers standpipes?

NFPA 14

What is a Class 2 standpipe?

<p>The Class II system is usually equipped with 1 1/2 in. (65 mm) hose in varying lengths, used by building occupants until the fire department arrives.</p> Signup and view all the answers

How long can the hose be in Class 2 standpipes?

<p>50-150 feet</p> Signup and view all the answers

How many GPM's and at which PSI do Class 2 standpipes discharge at?

<p>50 GPM at 65 PSI</p> Signup and view all the answers

What is a Class 3 standpipe?

<p>A combination of Class I and Class II, usually equipped with a 2 1/2 in. (65 mm) angle valve for fire department use and a 1 1/2 in. (40 mm) hose rack assembly for industrial fire brigade use.</p> Signup and view all the answers

How is a standpipe system tested?

<p>A hydrostatic test is performed by pressurizing the piping to 200 PSI for 2 hours to check for leaks.</p> Signup and view all the answers

How are dry systems tested?

<p>An air pressure leakage test at 40 PSI for 24 hours must be conducted.</p> Signup and view all the answers

What are the minimum qualifications that need to be met during a flow test at the most hydraulically demanding riser for a Class 1 standpipe?

<p>Flowing 500 GPM at 100 PSI at the most hydraulically demanding riser.</p> Signup and view all the answers

What is the minimum GPM and PSI for every additional riser in a building with a Class 1 standpipe?

<p>250 GPM at 100 PSI for each additional riser.</p> Signup and view all the answers

What should be the minimum total GPM of all Class 1 standpipes flowing simultaneously in a building that is not completely sprinklered?

<p>1250 GPM</p> Signup and view all the answers

What should be the minimum total GPM of all Class 1 standpipes flowing simultaneously in a building that is protected throughout with an automatic sprinkler system?

<p>1000 GPM</p> Signup and view all the answers

What NFPA standard covers sprinkler systems?

<p>NFPA 13</p> Signup and view all the answers

How many different classes of standpipes are there?

<p>3</p> Signup and view all the answers

How many different types of standpipes are there?

<p>4 types (1 wet and 3 dry)</p> Signup and view all the answers

Describe the 'wet type' of standpipe system.

<p>Standpipe system having a supply valve open and water pressure maintained at all times to the outlet valves.</p> Signup and view all the answers

Describe the 1st 'dry' type of standpipe.

<p>Normally empty, the system is charged automatically when an electrical switch or other device located at each outlet is activated.</p> Signup and view all the answers

Describe the 2nd 'dry' type of standpipe.

<p>Normally empty; the system is charged with air pressure. Water enters the system when an outlet valve is opened.</p> Signup and view all the answers

Describe the 3rd 'dry' type of standpipe.

<p>Normally empty; the system has no permanent water supply. Water is supplied by fire department pumper.</p> Signup and view all the answers

On the 3rd type of dry standpipe, how do some systems help reduce filling time by the engine?

<p>Primed system - a dry type (no permanent water supply), but kept full of water to reduce filling time by a pumper.</p> Signup and view all the answers

How far apart should Class 3 standpipes be spaced out in a building?

<p>All portions of each floor are to be within 30' of a nozzle attached to no more than 100' of fire hose.</p> Signup and view all the answers

How far apart should Class 2 standpipes be spaced out in a building?

<p>All portions of each floor are to be within 20' of a nozzle attached to no more than 75' of fire hose.</p> Signup and view all the answers

What is the minimum water supply for a Class 1 standpipe?

<p>500 GPM for 30 min., maintain 65 PSI at the topmost outlet with 500 GPM flowing.</p> Signup and view all the answers

What is the minimum water supply for a Class 2 standpipe?

<p>100 GPM for 30 min., maintain 65 PSI at the topmost outlet with 100 GPM flowing.</p> Signup and view all the answers

What is the minimum water supply for a Class 3 standpipe?

<p>Same as Class 1</p> Signup and view all the answers

What is an FDC and how many are required for Class 1 and 3 standpipes?

<p>FDC - Fire Department Connection; one or more Siamese connections are required.</p> Signup and view all the answers

How often should a standpipe be tested and maintained?

<p>Outside agencies usually test and maintain systems, with frequency requirements set by state and local governments.</p> Signup and view all the answers

Flashcards are hidden until you start studying

Study Notes

Standpipe Systems Overview

  • Standpipe systems facilitate firefighting by reducing long hose runs.
  • NFPA 14 governs the standards for standpipe systems.

Classifications of Standpipes

  • Class I: For fire department use; equipped with a 2 1⁄2 in. angle valve.
  • Class II: Suited for occupants; features 1 1⁄2 in. hose, lengths between 50-150 feet; discharges at 50 GPM and 65 PSI.
  • Class III: A combination of Class I and II; has both a 2 1⁄2 in. valve and a 1 1⁄2 in. hose rack.

Testing and Maintenance

  • Standpipe systems undergo hydrostatic testing at 200 PSI for 2 hours to detect leaks.
  • Dry systems require an air pressure leak test at 40 PSI for 24 hours; a pressure drop of 1.5 PSI indicates leakage.
  • Frequency of testing is determined by state and local regulations.

Flow and Water Supply Requirements

  • Class I flow test must verify 500 GPM at 100 PSI from the most hydraulically demanding riser.
  • Each additional Class I riser requires 250 GPM at 100 PSI.
  • Total minimum supply for non-sprinklered Class I buildings is 1250 GPM; for sprinklered buildings, it's 1000 GPM.
  • Class II minimum supply is 100 GPM for 30 minutes at 65 PSI.

Types of Standpipe Systems

  • Wet Type: Constant water supply and pressure maintained at outlet valves.
  • Dry Types:
    • First type activates water flow upon valve use.
    • Second type uses air pressure; water enters on valve opening.
    • Third type has no water supply; relies on fire department delivery.

Installation and Spacing Requirements

  • Class III standpipes must ensure every floor section is within 30 feet of a nozzle with up to 100 feet of hose.
  • Class II requires a maximum of 20 feet from nozzles attached to 75 feet of hose.

Fire Department Connection (FDC)

  • FDCs consist of one or more Siamese connections, required for Class I and III systems.

Studying That Suits You

Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

Quiz Team

More Like This

Use Quizgecko on...
Browser
Browser