Safety Regulations for Utility Vaults and Access
47 Questions
0 Views

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to Lesson

Podcast

Play an AI-generated podcast conversation about this lesson

Questions and Answers

What is the minimum requirement for the strength of manhole covers?

  • They must be able to withstand the load specified in Rule 323A.E. (correct)
  • They must be able to support the weight of a person.
  • They must be able to withstand the load specified in Table 110-1.
  • They must be able to withstand the load specified in Rule 110A2.
  • Where should personnel access openings in vaults be located to ensure safety?

  • Directly over cable for easy access.
  • In a location where they do not directly open into equipment or cable. (correct)
  • In a location where they are easily accessible from the outside.
  • Directly over equipment for easy access.
  • What type of openings in vaults are allowed to be located over equipment?

  • Ventilation openings.
  • Openings for cable entry.
  • Personnel access openings.
  • Openings for equipment installation and maintenance. (correct)
  • Openings for emergency exits.
  • What is the requirement for access doors to utility tunnels and vaults when they are accessible to the public?

    <p>They must be locked unless authorized personnel are present. (C)</p> Signup and view all the answers

    What is the purpose of the EXCEPTION mentioned regarding the locking mechanism of access doors?

    <p>To ensure that the door can be opened from the inside even when locked from the outside. (D)</p> Signup and view all the answers

    What is the minimum clearance required for energized parts and controls near ventilation openings in an aboveground vault?

    <p>The same clearance as specified in Rule 110A2. (D)</p> Signup and view all the answers

    What is the minimum requirement for fixed ladders?

    <p>They must be corrosion-resistant. (C)</p> Signup and view all the answers

    What should be considered regarding ventilation openings in an aboveground vault when it comes to energized parts and controls?

    <p>They should be equipped with louvers or baffles to prevent object penetration. (B)</p> Signup and view all the answers

    Under what conditions can communication cables be buried alongside supply cables at the same depth?

    <p>All of the above, provided all parties involved agree and applicable rules are met. (D)</p> Signup and view all the answers

    What is the maximum operating voltage to ground for grounded supply systems?

    <p>22,000 V (D)</p> Signup and view all the answers

    What type of construction is mandatory for ungrounded supply cables operating above 300 V?

    <p>Effectively grounded concentric shield construction (C)</p> Signup and view all the answers

    What is the purpose of a ground-fault indication system for ungrounded supply circuits operating above 300 V?

    <p>To detect and signal a ground fault within the circuit. (B)</p> Signup and view all the answers

    Which of the following requirements applies to communication cables and communication service wire having metallic conductors or components?

    <p>They must have a continuous metallic shield under the outer jacket. (A)</p> Signup and view all the answers

    What is the maximum allowable operating voltage phase-to-phase for ungrounded supply systems?

    <p>5,300 V (C)</p> Signup and view all the answers

    What type of protective devices are required for communication systems in the event of contact with supply conductors?

    <p>Communications-protective devices adequate for the expected voltage and currents (A)</p> Signup and view all the answers

    What is the maximum allowable radial resistivity of a semiconducting jacket for a cable?

    <p>100   m (C)</p> Signup and view all the answers

    How is the radial resistivity of a cable jacket calculated?

    <p>By measuring the resistance between the concentric neutral and a surrounding conducting medium, multiplying by the surface area and dividing by the thickness. (A)</p> Signup and view all the answers

    Which of the following is NOT a requirement for a multi-grounded supply system operating above 300 V to ground with an insulating jacket?

    <p>The concentric conductor must be grounded at each service. (A)</p> Signup and view all the answers

    Under what exception can the grounding interval for a grounded neutral supply cable with an insulating jacket be increased?

    <p>When adherence would require opening a duct and/or removing the protective jacket of the buried cable only for the purpose of installing a ground connection. (D)</p> Signup and view all the answers

    What is the minimum number of grounding electrodes required for a grounded neutral supply cable with an insulating jacket in a random buried section?

    <p>8 (D)</p> Signup and view all the answers

    Where may an insulating jacketed grounded neutral supply cable meeting the rules of 354D3 be installed?

    <p>Only in nonmetallic ducts (B)</p> Signup and view all the answers

    Which parties must agree to the burying of supply cables and conductors with non-metallic water and sewer lines?

    <p>The electric utility and the owner of the property (C)</p> Signup and view all the answers

    Why is it important for the concentric neutral conductor of a multi-grounded supply system with an insulating jacket to be adequate for expected fault currents?

    <p>To ensure that the fault current is diverted to ground safely. (D)</p> Signup and view all the answers

    What type of material should be used for cable identification?

    <p>Corrosion-resistant (C)</p> Signup and view all the answers

    Where should supply cables be racked in relation to communication cables when they must be on the same wall?

    <p>Below communication cables (A)</p> Signup and view all the answers

    What is the requirement regarding cable movement during installation?

    <p>Cable movement should be allowed, ensuring no stress concentration (A)</p> Signup and view all the answers

    In a joint-use manhole, what is required for installing supply and communication facilities?

    <p>Agreement from all involved parties (D)</p> Signup and view all the answers

    Where does the text recommend special protection be considered for cables?

    <p>At the cable entrance to the duct (A)</p> Signup and view all the answers

    What is the purpose of permanently identifying cables?

    <p>To facilitate identification and maintenance (D)</p> Signup and view all the answers

    What is the minimum clearance required for supply and communications facilities?

    <p>As specified in Table 341-1 (C)</p> Signup and view all the answers

    How should cables in a joint-use manhole or vault be identified?

    <p>By using tags with the utility name and cable type (C)</p> Signup and view all the answers

    What is the minimum vertical dimension required for a manhole, excluding those with openings within 300mm of the adjacent interior side wall?

    <p>1.83 m (A)</p> Signup and view all the answers

    What is the minimum horizontal dimension of a manhole's clear working space?

    <p>900 mm (D)</p> Signup and view all the answers

    What is the purpose of increasing live loads by 30% in manhole design?

    <p>To account for the impact of heavy vehicles and equipment. (B)</p> Signup and view all the answers

    What is the minimum design live load for structures that are not subjected to vehicular loading?

    <p>14.5 kPa (D)</p> Signup and view all the answers

    What is the main consideration in determining the design loads for manholes and vaults?

    <p>The maximum combination of vertical and lateral loads that will be imposed on the structure. (D)</p> Signup and view all the answers

    What type of vehicles are used to determine the live load in roadway areas?

    <p>Tractor-semitrailer trucks. (C)</p> Signup and view all the answers

    What is the design consideration for pulling iron facilities installed in manholes?

    <p>They should be designed to withstand twice the expected load. (B)</p> Signup and view all the answers

    How are manholes designed to withstand hydraulic, frost, or other uplift forces?

    <p>By ensuring the manhole's weight is sufficient or by restraining it to withstand the forces. (B)</p> Signup and view all the answers

    What is the primary concern regarding the effect of ground currents on communication circuits near supply stations?

    <p>Interference with data transmission due to electromagnetic induction. (C)</p> Signup and view all the answers

    What is the minimum voltage threshold for a supply facility to require a bare or semiconducting jacketed grounded conductor?

    <p>300 V (A)</p> Signup and view all the answers

    What are the acceptable configurations for a grounded conductor in a supply facility?

    <p>All of the above are acceptable configurations. (D)</p> Signup and view all the answers

    When can the contact with earth of the grounded conductor be omitted for a buried cable?

    <p>When the cable passes through a short section of conduit, such as under a roadway. (A)</p> Signup and view all the answers

    What material requirement is specified for the bare conductors in contact with the earth?

    <p>They must be made of a material that is corrosion-resistant. (A)</p> Signup and view all the answers

    What is the primary reason for the recommendation against using bare concentric copper neutral conductors in many geographic areas?

    <p>They are susceptible to corrosion in the presence of moisture and soil chemicals. (B)</p> Signup and view all the answers

    What is the rationale behind the recommendation for the conductor covered by a semiconducting jacket to be compatible with the jacketing compound?

    <p>To prevent the jacket from degrading and compromising the conductor's integrity. (C)</p> Signup and view all the answers

    What is the importance of evaluating the effect of ground currents on communication circuits before cable placement?

    <p>To avoid interference with communication signals caused by electromagnetic induction from ground currents. (B)</p> Signup and view all the answers

    Flashcards

    Strength requirements for manholes

    Manholes must sustain all expected loads, including dead, live, equipment, impact, and environmental loads.

    Dead load

    The permanent static load that a structure must support, such as the weight of the structure itself.

    Live load

    The variable load that may change over time, such as vehicles passing over a structure.

    Impact load

    An increase in live load by 30% to account for sudden forces, like a truck hitting a bump.

    Signup and view all the flashcards

    Lateral loading

    Forces acting on the structure horizontally, which can affect its stability.

    Signup and view all the flashcards

    Frost uplift

    A condition where frost can push structures upward, requiring designs to withstand this force.

    Signup and view all the flashcards

    Clear working space dimensions

    Manholes must have a clear working space of at least 900 mm (3 ft) wide and 1.83 m (6 ft) high.

    Signup and view all the flashcards

    Pulling iron load capacity

    Facilities for pulling iron should withstand twice the expected load applied during use.

    Signup and view all the flashcards

    Manhole Cover Requirements

    Covers must be heavy or designed to prevent removal without tools.

    Signup and view all the flashcards

    Cover Design Standards

    Covers must not fall into manholes or touch cables/equipment.

    Signup and view all the flashcards

    Strength of Covers

    Covers must support applicable loads as per Rule 323A.

    Signup and view all the flashcards

    Vault Access Openings

    Access openings should ensure safe passage and not align over equipment.

    Signup and view all the flashcards

    Utility Tunnel Security

    Public access doors must be locked unless authorized personnel are present.

    Signup and view all the flashcards

    Safety Signage

    Prominent signs must be posted near exposed live parts.

    Signup and view all the flashcards

    Exit Door Requirements

    Doors should allow exiting from inside even when locked outside.

    Signup and view all the flashcards

    Ventilation Opening Clearance

    Energized parts must have a safety clearance from ventilation openings.

    Signup and view all the flashcards

    Buried cable requirements

    Supply and communication cables may be buried together if agreed and rules are met.

    Signup and view all the flashcards

    Exception for fiber-optic cables

    Dielectric fiber-optic cables can be buried with supply cables without separation under specific agreements.

    Signup and view all the flashcards

    Voltage limits for grounded systems

    Grounded supply systems should not exceed 22,000 V to ground.

    Signup and view all the flashcards

    Ungrounded system voltage

    Ungrounded systems must not exceed 5,300 V phase-to-phase.

    Signup and view all the flashcards

    Concentric shield cables

    Ungrounded supply cables over 300 V must be effectively grounded concentric shield type.

    Signup and view all the flashcards

    Ground-fault indication system

    Ungrounded circuits over 300 V must have a ground-fault indication system.

    Signup and view all the flashcards

    Metallic shield requirement

    Communication cables with metallic parts must have a continuous metallic shield.

    Signup and view all the flashcards

    Bonding interval for cables

    Bonding between supply conductors and cable shields should not exceed 300 m (1000 ft).

    Signup and view all the flashcards

    Effect of Ground Currents

    Evaluate communication circuits near supply stations to prevent interference from large ground currents.

    Signup and view all the flashcards

    Grounded Conductor Requirement

    Supply facilities above 300 V must have a grounded conductor continuously in contact with earth.

    Signup and view all the flashcards

    Types of Grounded Electrode

    Grounded conductors can be a sheath, insulation shield, or multiple concentric conductors.

    Signup and view all the flashcards

    Separate Conductor Proximity

    A separate conductor in contact with earth should be close to the cable for grounding.

    Signup and view all the flashcards

    Exception for Conduit

    When a cable passes through a conduit, grounding can be omitted if continuous through conduit.

    Signup and view all the flashcards

    Corrosion-Resistant Material

    Bare conductors contacting earth must be made of corrosion-resistant materials.

    Signup and view all the flashcards

    Semiconducting Jacket Compatibility

    Conductors under semiconducting jackets must be compatible with the jacketing compound.

    Signup and view all the flashcards

    Bare Copper Neutral Conductors

    Experience shows bare concentric copper neutrals can corrode severely in many areas.

    Signup and view all the flashcards

    Cable movement requirements

    Cables must allow movement without stress concentration and stay supported during operation.

    Signup and view all the flashcards

    Clearance requirements

    Adequate space must be provided as per Rule 323B for cable installation.

    Signup and view all the flashcards

    Joint-use installations

    Installing cables in a shared manhole requires agreement from all utilities involved.

    Signup and view all the flashcards

    Cable racking

    Supply and communication cables should be racked separately; if not, supply cables go below.

    Signup and view all the flashcards

    Access without interference

    Facilities must be installed to allow access without moving other cables.

    Signup and view all the flashcards

    Cable identification

    Cables must be permanently marked at access points for identification.

    Signup and view all the flashcards

    Corrosion-resistant tags

    Tags for cable identification should resist corrosion and be readable in low light.

    Signup and view all the flashcards

    Utility identification tags

    Cables in joint-use areas should be marked with utility names and cable types.

    Signup and view all the flashcards

    Radial resistivity

    The measurement of resistance in the semiconducting jacket material of cables, ideally not exceeding 100 Ω·m.

    Signup and view all the flashcards

    Grounding requirement

    Each phase conductor above 300 V must have an effectively grounded copper concentric conductor meeting safety codes.

    Signup and view all the flashcards

    Fault current

    The magnitude and duration of abnormal current that can occur during a fault condition in electrical systems.

    Signup and view all the flashcards

    Concentric neutral

    A grounded copper conductor that surrounds the phase conductors, providing safety and stability.

    Signup and view all the flashcards

    Grounding electrodes

    Conductors placed in the ground to safely disperse electrical faults, with at least eight required per 1.6 km.

    Signup and view all the flashcards

    Nonmetallic duct installation

    Grounded neutral supply cables can be laid randomly with communication cables in nonmetallic ducts.

    Signup and view all the flashcards

    Communication cables

    Cables used for transmitting information, which can run alongside supply cables in certain installations.

    Signup and view all the flashcards

    Installation depth agreement

    Supply cables and non-metallic lines may be buried at the same depth if all parties agree.

    Signup and view all the flashcards

    Study Notes

    Safety Rules for the Installation and Maintenance of Underground Electric Supply and Communication Lines

    • Purpose: Part 3 of the code ensures the safety of personnel during installation, operation, and maintenance of underground electrical and communication cables.
    • Scope: Covers underground supply and communication cables, associated structures, and extending systems into buildings also includes electrical power systems employed by utilities. Excludes installations in electric supply stations.
    • Application of rules: General requirements outlined in Rule 13. While "duct" and "conduit" are often used interchangeably, they have distinct meanings in this part of the code. "Duct" is a single enclosed raceway for conductors or cables; "conduit" is a structure that contains multiple ducts. A "conduit system" is an integrated whole formed by combining ducts, conduits, manholes, handholes, and/or vaults.

    General Requirements Applying to Underground Lines

    • Referenced sections: Introduction, Definitions, References, and Grounding Methods of the Code apply to Part 3.
    • Installation and maintenance: Personnel responsible for underground facilities need to be able to locate their equipment. Adequate notice should be given well ahead of time to owners or operators of other proximate facilities that may be affected. Emergency installations of supply and communication cables can be on-grade if guarded or otherwise located to prevent pedestrian/vehicular interference and properly marked. Cables operating above 600 V must follow Rule 230C or 350B.
    • Accessibility: All parts needing examination or adjustment during operation must have adequate working spaces, working facilities, and clearances.
    • Inspection and tests: Lines and equipment must comply with safety rules when placed in service. Inspections must be done at intervals deemed necessary by experience. Testing of lines and equipment is required when considered necessary. Records of any identified issues must be maintained until the conditions or defects are corrected.

    Grounding of Circuits and Equipment

    • Methods: Grounding methods are detailed elsewhere in Section 9.
    • Conductive parts: Cable sheaths, shields, equipment frames, conductive poles, and conductive handhole/duct covers, must be effectively grounded.
    • Exceptions: Rules do not apply to parts located 8 ft or more above ground or those that are isolated or guarded.
    • Neutrals: Primary, secondary, service, and common neutrals exposed to personnel, shall be effectively grounded (exception for circuits with ground-fault detection and impedance current-limiting devices.)
    • Other conductors: Intentionally grounded conductors (other than neutrals) are to be effectively grounded if exposed to personnel contact.
    • Surge arresters: All surge arresters shall be effectively grounded.
    • Earth in circuits: Supply circuits should not use the ground as the sole conductor.

    Communications Protective Requirements

    • Requirements: When communication equipment is accessible to unqualified personnel, one or more protection measures (per Rule 315B). must be employed: Lightning, contact with supply conductors exceeding 300 V, or transient rise in ground potential exceeding 300 V.
    • Protection means: Insulation, surge arresters, additional devices like auxiliary arresters, drainage coils or isolating devices as necessary, depending on the expected voltage.

    Underground Conduit Systems

    • Location: Conduit systems should follow the least disturbance possible, avoiding direct placement over or under other subsurface structures; bends should have large radii to reduce damage risk to cables.
    • Natural hazards: Avoid using unstable or corrosive soils, which require conduit design to limit movement or corrosion risk.
    • Highways/Streets: Should be placed in the shoulder if possible.
    • Bridges/Tunnels: Located to minimize traffic damage impact, and to enable safe access for inspection and maintenance.
    • Railroads: Minimum 36 inches below the top of the rails or a specified greater depth if unusual conditions exist.

    Excavation and Backfill

    • Trench: Should be relatively smooth undisturbed earth, or tamped or clean tamped backfill for rock excavations.
    • Backfill: Should be free of materials capable of damaging conduit system. Adequate compaction to control settling is necessary.

    Conduit, Ducts and Joints

    • Materials: Corrosion resistant for the intended environment. Duct material or conduit construction must ensure a failure in one duct won't harm others.
    • Impact loading: Conduit design should withstand external surface loading; impact load reduction of one-third is permissible with at least 3 feet of cover.
    • Surface of conduits: Shall be free of sharp edges or burrs to prevent damage to cables.

    Cable in Underground Structures

    • General requirements: Applies Rule 33 to supply cables in structures. On systems using above 2 kV to ground, the design of cables or conductors in nonmetallic conduits must account for an effectively grounded shielding or sheath .
    • Installation: Limit the bending of supply cables during handling and installation, using manufacturers' recommendations as a guide. Make sure ducts are clean before pulling cables or other materials to eliminate the potential of damage to the cable. Cable lubricants must not harm the cable or conduit system. For slopes/vertical runs, the likelihood of cables moving downwards should be mitigated. Supply cables should not be in the same conduit as communication cables unless both are operated and maintained by the same utility.
    • Supports (in manholes/vaults): Conduit supports must meet the local environmental compatibility (ex: fire hydrants). Horizontal supply conductors need support above floor. Clear working spaces are required in accordance with Rule 323B.
    • Identifications: All cables should use some type of physical marking to identify who owns which cable and how it is intended to be used.

    Supply Cable Terminations

    • Design: Cable terminations must meet Rule 333 requirements.
    • Riser terminations: Installation should maintain the required clearances (specified in other parts of the code).
    • Moisture: Cable terminations need to be resistant to moisture damage.
    • Clearances: Required clearances must be maintained, especially where different electrical potentials exist. Insulated barriers are needed where minimal clearances are present.

    Equipment

    • General: Equipment design must consider local climate (e.g. water standing in a manhole/vault) and mechanical stressing of equipment. Pad-mounted equipment, pedestals or enclosures should be located at least 1.2 meters (4 feet)from any hydrant; if this isn't possible, a minimum 900 mm (3 ft) is acceptable with agreement.
    • Installation: Equipment must withstand expected thermal, chemical mechanical, and environmental conditions.
    • Safety signs: Remotely operated/controlled switches are required to be labeled.
    • Working spaces: Work areas should be designated to provide appropriate space for personnel and to avoid hazards (e.g. standing beneath energized equipment).
    • Grounding: Enclosures/cases made from conductive materials must be effectively grounded.
    • Identification: Transformers, as well as other equipment that operates in multiple locations, need tags or diagrams for clarity.

    Installation in Tunnels

    • General Requirements: Installations in tunnels must meet applicable code requirements; non-qualified people cannot work unless the space is compliant with Part 2 of code or with other standards.
    • Controlled Environment: Tunnel interiors must meet safety criteria, including provisions for ventilation, detecting hazardous atmospheres, fire prevention, explosion resistance, and measures to handle the high temperatures/pressures within the space.

    Work Rules for the Operation of Electric Supply and Communications Lines and Equipment

    • Purpose and Scope: The code will outline work rules for the installation, operation, and maintenance of electrical supply and communication systems.
    • Referenced sections: The code incorporates information from the Introduction, Definitions, References, and Grounding methods section.

    Supply and Communications Systems—Rules for Employers

    • Employer Requirements: Employers must train employees on all rules and safety precautions for communications and electric supply equipment in their assigned work areas. Employees must be properly trained for the tasks they perform, must be properly equipped, and must comply with all safety guidelines for tasks in their specific environment.

    Additional Rules for Communications Employees

    • Approaches to energized conductors/parts: Employees must maintain a minimum approach distance to energized parts, as stipulated in Table 431-1. Workers cannot approach energized lines or parts unless the line is de-energized and grounded (per Rule 444D), or the approach is protected/insulated, or the line is isolated, or part-to-part are insulated from each other.

    Additional Rules for Supply Employees

    • Work on energized lines/equipment: Multiple requirements outlined for worker safety when working around energized equipment, including insulation/isolation and safeguarding equipment, procedures for safely de-energizing and testing equipment before work, and handling tools, and materials.

    Studying That Suits You

    Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

    Quiz Team

    Related Documents

    Description

    This quiz covers essential safety regulations for utility vaults, including requirements for access openings, ladders, and ventilation. It also addresses specific guidelines for manhole covers and the safe installation of communication and supply cables. Test your knowledge on these important safety standards and ensure compliance with regulations.

    More Like This

    Utility Marketing Concepts
    12 questions
    Economics: Utility and Demand Concepts
    12 questions
    Utility and Consumer Satisfaction
    20 questions
    Economics Chapter 2: Utility and Choice
    27 questions
    Use Quizgecko on...
    Browser
    Browser