Refrigeration Systems Controls

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to Lesson

Podcast

Play an AI-generated podcast conversation about this lesson

Questions and Answers

What is the primary function of the inlet vane closed switch?

  • To prevent compressor operation if lube oil pressure is low
  • To indicate when chiller capacity control vanes are closed (correct)
  • To close the compressor motor circuit under certain conditions
  • To monitor water flow levels

What condition triggers the low oil pressure cut-off device?

  • When the condenser pressure is excessively high
  • When lube oil pressure falls below a safe minimum value (correct)
  • When the refrigerant temperature is too high
  • When lube oil pressure is above the maximum limit

What must occur for the condenser high pressure cut-off to be reset?

  • The compressor must be turned off completely
  • The system must maintain a constant flow of refrigerant
  • The temperature of water must be monitored
  • The switch must be manually reset by an operator (correct)

Under what condition does the refrigerant low temperature cut-off activate?

<p>When the refrigerant temperature drops low enough to freeze water (C)</p> Signup and view all the answers

What is a function of the motor demand limiter in centrifugal chillers?

<p>To limit maximum current flow to the compressor drive motor (B)</p> Signup and view all the answers

What role do face dampers play in the cooling process?

<p>They maintain constant air quantity in the duct. (D)</p> Signup and view all the answers

What typically causes a high condenser pressure trip?

<p>Inadequate condenser cooling water or airflow (C)</p> Signup and view all the answers

What effect does a high start temperature of the chilled water loop have on the electrical demand?

<p>It can lead to very high electrical demand if no current flow restrictions are applied. (A)</p> Signup and view all the answers

Which combination of dampers helps regulate cooling capacity in a system?

<p>Bypass damper with face damper connected to the same driver. (C)</p> Signup and view all the answers

How can the motor demand limiter minimize the risk of motor damage?

<p>By gradually increasing the demand limiter settings. (C)</p> Signup and view all the answers

What method involves stopping and starting the compressor based on temperature?

<p>Intermittent operation. (A)</p> Signup and view all the answers

Which of the following describes a condition that allows the centrifugal compressor to start?

<p>When the chiller capacity control vanes are closed (D)</p> Signup and view all the answers

Which method allows for cooling capacity reduction without shutting down the compressor?

<p>Compressor speed control. (B)</p> Signup and view all the answers

In what scenario does the low oil pressure cut-off require a manual reset?

<p>After a low oil pressure condition occurs (B)</p> Signup and view all the answers

What does the operation of inlet vanes in a compressor do?

<p>It restricts the flow of refrigerant, affecting current draw. (A)</p> Signup and view all the answers

What is the primary function of the bypass damper?

<p>To open when the face damper closes. (B)</p> Signup and view all the answers

What is the primary purpose of a soft loading strategy in chillers?

<p>To control the chilled water temperature increase gradually. (C)</p> Signup and view all the answers

What happens when the vibration on a motor or compressor bearing reaches its shutdown set point?

<p>The compressor will automatically stop. (C)</p> Signup and view all the answers

Which of the following is NOT a method to control compressor capacity?

<p>Constant power operation. (D)</p> Signup and view all the answers

What indicator serves to alert the operator of a high liquid level in a suction scrubber?

<p>Float switch alarm. (A)</p> Signup and view all the answers

How do multistepped blowers enhance the refrigeration process?

<p>By improving balance between fan airflow and cooling requirements. (A)</p> Signup and view all the answers

Why is the power consumption of a compressor motor significant?

<p>It is directly proportional to the mass of refrigerant moved. (B)</p> Signup and view all the answers

What does cylinder unloading achieve in refrigeration compressors?

<p>It prevents total compressor shutdown. (D)</p> Signup and view all the answers

Which of the following describes a consequence of fast unloading of a compressor?

<p>It can cause low chilled water temperature trips. (D)</p> Signup and view all the answers

What is the primary reason for the lube oil temperature cut-off switch to prevent the compressor from starting?

<p>To prevent excessive refrigerant dilution of the lube oil (B)</p> Signup and view all the answers

At what lube oil temperature does the inhibit switch prevent the compressor from starting?

<p>Below 35°C (D)</p> Signup and view all the answers

What role does the crankcase heater play in the operation of a compressor?

<p>To heat the lube oil to appropriate levels (D)</p> Signup and view all the answers

Which factor does NOT affect the refrigerating capacity of a system?

<p>The ambient temperature of the room (C)</p> Signup and view all the answers

What may cause the compressor to lose its prime when starting?

<p>Vaporized refrigerant forming bubbles in the lube oil (A)</p> Signup and view all the answers

What components might be used to monitor temperature in a compressor system?

<p>Bimetal or thermistor temperature sensing elements (D)</p> Signup and view all the answers

How does the mass of refrigerant circulated affect the kW rating of a refrigeration system?

<p>It dictates the refrigerating capacity of the system (D)</p> Signup and view all the answers

What function does the lube oil heater serve when the oil temperature is below 60°C?

<p>It raises the oil temperature to prevent damage (D)</p> Signup and view all the answers

What is the primary purpose of using evaporator capacity control?

<p>To manage the amount of vapour produced (A)</p> Signup and view all the answers

How does a sectional evaporator function in relation to cooling load?

<p>Sections are shut off when the cooling load decreases (B)</p> Signup and view all the answers

What is a common issue with relying solely on face dampers for airflow control?

<p>They can lead to unacceptable reductions in ventilation air (D)</p> Signup and view all the answers

What mechanism is typically used to control the operation of a sectional evaporator?

<p>Solenoid valves in the liquid refrigerant line (C)</p> Signup and view all the answers

What component is responsible for adjusting the airflow in an evaporator equipped with dampers?

<p>Positioner (C)</p> Signup and view all the answers

Why is it necessary to control both evaporator and compressor capacity simultaneously?

<p>To maintain optimal efficiency and performance (D)</p> Signup and view all the answers

What is the role of a face damper in an evaporator system?

<p>To vary the amount of air over the evaporator coils (B)</p> Signup and view all the answers

What happens when cooling load decreases in a system using sectional evaporators?

<p>Some sections become inoperative to manage the load (C)</p> Signup and view all the answers

What determines the capacity of an identical refrigeration system?

<p>The efficiency of the compressor (B)</p> Signup and view all the answers

What occurs when a hand-operated expansion valve allows too much refrigerant into the evaporator?

<p>Evaporator icing may occur (A)</p> Signup and view all the answers

Why are thermostatic expansion valves referred to as 'constant superheat' valves?

<p>They regulate superheat for better evaporator efficiency (D)</p> Signup and view all the answers

What is a disadvantage of hot gas bypass capacity control in refrigeration systems?

<p>It can cause increased energy consumption (B)</p> Signup and view all the answers

When does a refrigeration compressor utilize cylinder unloading?

<p>To reduce capacity under low load conditions (B)</p> Signup and view all the answers

Why are face dampers less effective for evaporator capacity control than bypass dampers?

<p>Bypass dampers provide more precise control (B)</p> Signup and view all the answers

What is the primary function of external equalizer piping in thermostatic expansion valves?

<p>To stabilize pressure readings (B)</p> Signup and view all the answers

What is one reason for using low-pressure float valves in certain evaporators?

<p>To control the flow of refrigerant based on liquid levels (D)</p> Signup and view all the answers

Flashcards

Intermittent Operation

A method to control the capacity of a refrigeration compressor where the compressor starts and stops based on temperature needs.

How does intermittent operation work?

The compressor is stopped when the desired low temperature is reached, and then started up again once the temperature increases.

Continuous Operation with Reduced Output

A method to control the capacity of a refrigeration compressor where the compressor runs continuously but with reduced output.

Cylinder Unloading

A method to control the capacity of a refrigeration compressor by reducing the number of cylinders working.

Signup and view all the flashcards

Cylinder Bypass

A method to control the capacity of a refrigeration compressor by bypassing some refrigerant from the compressor.

Signup and view all the flashcards

Hot Gas Bypass

A method to control the capacity of a refrigeration compressor by returning some hot gas to the suction line.

Signup and view all the flashcards

Compressor Speed Control

Adjusts the speed of the compressor to change the amount of refrigerant circulated.

Signup and view all the flashcards

Suction Throttling

Reduces the amount of refrigerant entering the compressor by restricting its flow.

Signup and view all the flashcards

Sectional Evaporator

A method of controlling evaporator capacity where the evaporator is divided into sections, each with a refrigerant flow control valve. Sections can be shut off as the cooling load decreases.

Signup and view all the flashcards

Evaporator Dampers

A device that controls the amount of air passing over the evaporator coils by opening and closing to meet the changing cooling load.

Signup and view all the flashcards

Evaporator Capacity

The amount of cooling that can be achieved by the evaporator, which is directly proportional to the amount of refrigerant flowing through it.

Signup and view all the flashcards

Refrigerant Flow Control Valve

A valve that controls the flow of refrigerant through a section of the evaporator.

Signup and view all the flashcards

Solenoid Valve

A type of valve that is operated by an electrical signal, typically used in sectional evaporators to open or close sections as needed.

Signup and view all the flashcards

Positioner

A device that positions the face damper in response to a control signal.

Signup and view all the flashcards

Refrigerant Charge

The total amount of refrigerant in the system, usually stored in a separate container.

Signup and view all the flashcards

Cooling Load Decrease

Any event or situation that causes a reduction in the cooling load, such as a decrease in the temperature of the space being cooled.

Signup and view all the flashcards

Low Oil Temperature Start Inhibit Switch

A safety mechanism that prevents a compressor from starting when lube oil temperature is below a specific threshold.

Signup and view all the flashcards

Crankcase Oil Heater

A device that heats the lube oil in the compressor crankcase, ensuring optimal lubrication and preventing damage.

Signup and view all the flashcards

Low Oil Pressure Cut-Off Switch

A type of safety device designed to stop the compressor in case of low oil pressure.

Signup and view all the flashcards

Refrigerant Circulation Rate

The amount of refrigerant that flows through a refrigeration system per unit of time.

Signup and view all the flashcards

Refrigerating Capacity

The ability of a refrigeration system to remove heat, measured in units of power (kW or tons).

Signup and view all the flashcards

Refrigerant Dilution

The process where refrigerant dissolves into the compressor oil at lower temperatures, diluting its viscosity and potentially causing wear.

Signup and view all the flashcards

Oil Foaming

The formation of refrigerant vapor bubbles within the lube oil, disrupting the oil flow and potentially causing problems.

Signup and view all the flashcards

Refrigeration System Stability

The process of maintaining constant pressures and temperatures within a refrigeration system.

Signup and view all the flashcards

Motor Demand Limiter

Limits the amount of electrical current drawn by the compressor motor during startup, preventing overload and minimizing electrical demand.

Signup and view all the flashcards

Soft Loading

A control strategy that gradually increases the compressor's capacity during startup, preventing sudden temperature drops and potential low temperature trips.

Signup and view all the flashcards

Vibration Switch

A sensor that detects excessive vibration in a compressor bearing and triggers an alarm or shutdown if a certain threshold is exceeded.

Signup and view all the flashcards

Suction Scrubber High Level Shutdown

A safety feature that monitors the liquid level in the suction scrubber. If the level rises beyond a set point, an alarm is activated and, if the level continues to rise, the compressor is shut down to prevent liquid from entering the compressor.

Signup and view all the flashcards

High Bearing Temperature Shutdown

A sensor that monitors bearing temperature. If the temperature rises above a set point, an alarm is triggered and, if the temperature continues to rise, the compressor is shut down to prevent damage from overheating.

Signup and view all the flashcards

Compressor Inlet Vanes

The amount of refrigerant flow into the compressor is controlled by the inlet vanes.

Signup and view all the flashcards

Compressor Motor Power Consumption

The power consumed by the compressor motor is directly related to the amount of refrigerant moved.

Signup and view all the flashcards

Variable Speed Drives (VSDs)

Variable speed drives can adjust the compressor speed, reducing electrical demand and ensuring optimal performance.

Signup and view all the flashcards

Low Flow Cut-Off Switch

This safety device prevents the compressor from starting if the water flow is below a safe minimum level. Ensures safe operation by preventing compressor start when there is insufficient water flow.

Signup and view all the flashcards

Inlet Vane Closed Switch

A proximity switch that closes when the chiller capacity control vanes are closed. This is crucial for starting a centrifugal compressor as it ensures the compressor starts under a 'no-load' condition, protecting it from strain.

Signup and view all the flashcards

Low Oil Pressure Cut-Off

This safety device shuts down the compressor when the lube oil pressure drops below a safe minimum value. This prevents catastrophic damage to the compressor and potential refrigerant leaks.

Signup and view all the flashcards

Condenser High Pressure Cut-Off

This safety switch acts as a high limit thermostat and shuts down the compressor if the condenser pressure becomes too high. This prevents overheating and potential damage to the system.

Signup and view all the flashcards

Refrigerant Low Temperature Cut-Off

This low limit thermostat senses the refrigerant temperature, shutting down the compressor if the temperature drops low enough to freeze water. This protects the cooling system from damage.

Signup and view all the flashcards

Motor Demand Limiter (Effect)

Most centrifugal chillers have a motor demand limiter to limit the maximum current flow to the compressor drive motor. This control overrides the water temperature sensor if necessary to prevent overloading the motor.

Signup and view all the flashcards

Motor Demand Limiter (Startup)

Typically, the chilled water temperature is higher than set point at startup. The motor demand limiter prevents high current flow during this initial stage, ensuring safe operation.

Signup and view all the flashcards

What determines refrigeration system capacity?

The capacity of a refrigeration system is determined by the amount of refrigerant flow through the evaporator. This flow is influenced by factors like the evaporator size, the refrigerant pressure, and the operating temperature.

Signup and view all the flashcards

What happens when a hand-operated expansion valve flows more refrigerant than the evaporator needs?

When a hand-operated expansion valve flows more refrigerant than the evaporator needs to meet the cooling load, the evaporator will become flooded with liquid refrigerant. This can lead to reduced cooling efficiency and even damage to the system, as the liquid refrigerant can block the flow of air through the evaporator.

Signup and view all the flashcards

What happens when a hand-operated expansion valve flows less refrigerant than the evaporator needs?

If a hand-operated expansion valve flows less refrigerant than the evaporator needs to meet the cooling load, the evaporator will not be able to absorb enough heat from the surrounding air. This will result in reduced cooling capacity and the evaporator may freeze up.

Signup and view all the flashcards

Why are thermostatic expansion valves called 'constant superheat' valves?

Thermostatic expansion valves (TEVs) are designed to maintain a constant superheat in the evaporator, regardless of changes in the load. This is achieved by using a sensing bulb that measures the temperature of the refrigerant leaving the evaporator, and then adjusts the flow of refrigerant accordingly.

Signup and view all the flashcards

Why do some TEVs use external equalizer piping?

TEVs use external equalizer piping for several reasons. One reason is to ensure that the sensing bulb senses the actual temperature of the refrigerant leaving the evaporator, even if the evaporator is located some distance away. Another reason is to improve the response time of the valve to changes in the load.

Signup and view all the flashcards

What type of evaporator uses a low-pressure float valve?

Low-pressure float valves are used with evaporators that operate at low pressures. This is because they are designed to maintain a constant level of liquid refrigerant in the evaporator, regardless of changes in the load.

Signup and view all the flashcards

Why is it important to control the capacity of an evaporator?

Controlling the capacity of an evaporator is important to ensure that the system operates efficiently and provides the required cooling. If the evaporator is too large, it may operate at a lower efficiency, while if it is too small, it may not be able to meet the cooling demand.

Signup and view all the flashcards

Why are face dampers not used in HVAC applications to control evaporator capacity?

Face dampers are not used in HVAC applications to control evaporator capacity because they are not very effective and can create uneven airflow distribution.

Signup and view all the flashcards

Study Notes

Learning Outcomes and Objectives

  • Describe the purposes and operating principles of refrigeration system operational and safety controls.
  • Describe refrigeration system controls.
  • List the safety shutdown devices specific to centrifugal compressor water chillers.
  • Describe typical refrigeration system safety shutdown devices.
  • Describe the construction and operation of refrigerant metering devices.
  • Describe the different methods used to control evaporator capacity.
  • Describe the different methods used to control the capacity of refrigeration compressors.

Refrigeration System Controls

  • Refrigeration systems operate under varying conditions.
  • Load changes and atmospheric conditions influence system operation.
  • Refrigeration systems have three types of controls: operating, actuating, and limiting/safety controls.
  • Operating controls start, stop, or regulate compressor capacity.
  • Actuating controls either indirectly control operations or regulate the cycle.
  • Limiting/safety controls protect the system from exceeding its designed limits.

Chapter Introduction

  • Refrigeration systems need controls to operate safely and efficiently.
  • Controls respond to changing conditions, such as load changes, cooling requirements, and atmospheric conditions.
  • Refrigeration systems must operate at the required cooling load.
  • System capacity (kW or TR) control involves adjusting the mass of refrigerant circulated.
  • This can be done directly or indirectly by controlling compressor capacity or evaporator capacity.

Human Machine Interfaces (HMIs)

  • HMIs are often found on packaged refrigeration units.
  • HMIs provide operators with operational data and alarms.
  • Operators use HMIs to control set points and operational expectations.
  • Some may be standalone, not reporting to a central control system.
  • Some may be linked to plant supervisory systems (SCADA).
  • Manufacturer manuals and plant data are important for site-specific practices.

Safety Controls (Centrifugal Chiller Safety)

  • Centrifugal chillers have safety devices to protect the system during startup and operation.

Low Chilled Water Temperature Cut-Off Switch

  • Prevents damage from water freezing in the evaporator.
  • Water temperature sensor detects issues and shuts down the compressor if the temperature falls too low.

High-Pressure Cut-Off

  • Occurs when condenser pressure becomes too high.
  • Causes: Insufficient condenser cooling, lack of airflow, fouling, atmospheric conditions.
  • System safety features prevent damage due to excessively high pressures and low temperatures.

Low-Pressure Cut-Off

  • Low suction pressure and temperature could damage the system.
  • Low-pressure cut-off prevents such problems by shutting down the compressor.

Low Limit Thermostat

  • Used in systems where low temperatures could cause damage.
  • The pressure switch shuts off the compressor.

Low Oil Pressure Cut-Off

  • Protects from damage if oil level is too low.
  • Signals the operator to address the issue

Refrigerant Metering Devices

  • Metering devices control refrigerant flow to the evaporator.
  • Capillary tubes, fixed orifices, and expansion valves are metering devices.
  • Automatic control is possible in larger systems with the possible exception of very large systems.

Methods to Control Evaporator Capacity

  • Use sectional evaporators or evaporator dampers.
  • Evaporator capacity control affects the amount of vapor produced.
  • This is needed for efficient, continual operation.

Compressor Capacity

  • Various techniques can adjust compressor capacity in continuous operation modes.
  • These methods include cylinder unloading, bypass, hot gas bypass, variable speed drives, and variable inlet vane controls.
  • In intermittent operation, the compressor starts and stops to control cooling load.

Knowledge Exercises

  • Include detailed questions on the subject of refrigeration system controls.

Chapter Glossary

  • Includes a list of key terms and their definitions.

Studying That Suits You

Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

Quiz Team

Related Documents

More Like This

Use Quizgecko on...
Browser
Browser