What does a hydrostatic tube test kit do?
What does a hydrostatic tube test kit do?
Determine if a tube leaks.
What is the maximum test pressure when leak testing a low-pressure centrifugal with nitrogen?
What is the maximum test pressure when leak testing a low-pressure centrifugal with nitrogen?
10 psig
How may charged low-pressure refrigeration machines be most efficiently leak checked?
How may charged low-pressure refrigeration machines be most efficiently leak checked?
Adding heat with circulated hot water or heating blankets.
What should be done to reduce refrigerant loss from a purge unit on an R-123 chiller?
What should be done to reduce refrigerant loss from a purge unit on an R-123 chiller?
Signup and view all the answers
What is the leak rate that requires chillers containing more than 50 pounds of ozone-depleting refrigerant to be repaired?
What is the leak rate that requires chillers containing more than 50 pounds of ozone-depleting refrigerant to be repaired?
Signup and view all the answers
What is the best method to determine a chiller's normal charge for leak rate calculations?
What is the best method to determine a chiller's normal charge for leak rate calculations?
Signup and view all the answers
Who is responsible for keeping records of all leak inspections and repairs?
Who is responsible for keeping records of all leak inspections and repairs?
Signup and view all the answers
What is a typical setting for the high-pressure cut-out control on a recovery unit used for evacuating refrigerant from a low-pressure chiller?
What is a typical setting for the high-pressure cut-out control on a recovery unit used for evacuating refrigerant from a low-pressure chiller?
Signup and view all the answers
What starts the refrigerant removal process from a low-pressure system?
What starts the refrigerant removal process from a low-pressure system?
Signup and view all the answers
What must be done after recovering the liquid refrigerant from a low-pressure chiller?
What must be done after recovering the liquid refrigerant from a low-pressure chiller?
Signup and view all the answers
Approximately how much refrigerant vapor is left in an average 350-ton R-123 chiller at 0 psig once all the R-123 liquid has been removed?
Approximately how much refrigerant vapor is left in an average 350-ton R-123 chiller at 0 psig once all the R-123 liquid has been removed?
Signup and view all the answers
What could happen with the use of a severely oversized vacuum pump when evacuating a system?
What could happen with the use of a severely oversized vacuum pump when evacuating a system?
Signup and view all the answers
After system servicing and recharging, why is refrigerant vapor reintroduced to the chiller before refrigerant liquid?
After system servicing and recharging, why is refrigerant vapor reintroduced to the chiller before refrigerant liquid?
Signup and view all the answers
What should you do after reaching the required recovery vacuum on a low-pressure appliance?
What should you do after reaching the required recovery vacuum on a low-pressure appliance?
Signup and view all the answers
Which action is always considered 'major' under EPA's regulations?
Which action is always considered 'major' under EPA's regulations?
Signup and view all the answers
When should an appliance not be evacuated all the way to the prescribed level?
When should an appliance not be evacuated all the way to the prescribed level?
Signup and view all the answers
Which statements are true of recycling and recovery equipment?
Which statements are true of recycling and recovery equipment?
Signup and view all the answers
What method can be used to pressurize an R-1233zd system for the purpose of opening it for a non-major repair?
What method can be used to pressurize an R-1233zd system for the purpose of opening it for a non-major repair?
Signup and view all the answers
How long must a technician evacuating refrigerant from appliances with a full charge of more than 5 pounds and less than 50 pounds keep records of the event?
How long must a technician evacuating refrigerant from appliances with a full charge of more than 5 pounds and less than 50 pounds keep records of the event?
Signup and view all the answers
What is the primary purpose of a purge unit on a low-pressure chiller?
What is the primary purpose of a purge unit on a low-pressure chiller?
Signup and view all the answers
Where does the purge unit on a centrifugal system take its suction?
Where does the purge unit on a centrifugal system take its suction?
Signup and view all the answers
At what approximate temperature does R-123 boil at 14.7 PSIA?
At what approximate temperature does R-123 boil at 14.7 PSIA?
Signup and view all the answers
Where does refrigerant go after it leaves the purge unit of a low-pressure centrifugal system?
Where does refrigerant go after it leaves the purge unit of a low-pressure centrifugal system?
Signup and view all the answers
What does ASHRAE Standard 15-2013 require the use of room sensors and alarms to detect?
What does ASHRAE Standard 15-2013 require the use of room sensors and alarms to detect?
Signup and view all the answers
What does ASHRAE Standard 15-2013 require in relation to refrigerant safety groups?
What does ASHRAE Standard 15-2013 require in relation to refrigerant safety groups?
Signup and view all the answers
Study Notes
Leak Testing and Refrigeration Systems
- A hydrostatic tube test kit is used to detect leaks in tubes.
- The maximum test pressure for leak testing low-pressure centrifugal systems with nitrogen is 10 psig.
- Efficient leak checking for charged low-pressure refrigeration machines involves adding heat through circulated hot water or heating blankets.
Refrigerant Management and Safety Regulations
- To minimize refrigerant loss from an R-123 chiller's purge unit, it should be piped back into the low side of the system.
- Since 2019, EPA regulations require chillers containing more than 50 pounds of ozone-depleting refrigerant to be repaired if the leak rate exceeds 10% of the charge annually.
- The normal charge for leak rate calculations on a chiller should align with the charge specified on its nameplate.
Responsibilities and Reporting
- The owner or operator of refrigeration equipment is responsible for maintaining records of leak inspections and the completion of leak repair verification tests.
Refrigerant Recovery and Evacuation Procedures
- Typical high-pressure cut-out control settings for recovery units evacuating refrigerant from low-pressure chillers is 10 psig.
- Refrigerant removal from low-pressure systems begins with liquid removal, followed by vapor recovery after the liquid is extracted.
- In an average 350-ton R-123 chiller at 0 psig, approximately 100 pounds of refrigerant vapor remains after liquid extraction.
Vacuum and Evacuation Techniques
- Using an oversized vacuum pump can result in trapped water freezing during the evacuation process.
- Vapor refrigerant is introduced to a chiller before liquid to prevent the freezing of water in the heat exchanger due to low temperatures from evaporated liquid.
- Upon reaching the required recovery vacuum in a low-pressure appliance, it's advised to wait a few minutes to check for pressure rise before charging.
Major Actions and EPA Compliance
- Major actions under EPA regulations include the replacement of an evaporator coil.
- Evacuating an appliance to prescribed levels is not recommended if leaks prevent reaching those levels.
- Recycling and recovery equipment must be labeled as certified to meet EPA requirements.
Pressurization and Record Keeping
- For non-major repairs in an R-1233zd system, the liquid refrigerant can be warmed to pressurize the system for access.
- Technicians must keep records of refrigerant evacuation from appliances with full charges of more than 5 pounds but less than 50 pounds for three years.
Purge Units and Refrigerant Properties
- The primary function of a purge unit in a low-pressure chiller is to eliminate non-condensables from the system.
- The purge unit on a centrifugal system takes suction from the top of the condenser.
- R-123 at 14.7 PSIA boils around 82°F.
Refrigerant Pathways and Standards Compliance
- After passing through the purge unit, refrigerant in a low-pressure centrifugal system flows to the evaporator.
- ASHRAE Standard 15-2013 mandates the use of room sensors and alarms to detect refrigerant leaks and applies to various refrigerant safety groups.
Studying That Suits You
Use AI to generate personalized quizzes and flashcards to suit your learning preferences.
Description
This quiz covers essential principles of leak testing in refrigeration systems, including hydrostatic testing techniques and safety regulations regarding refrigerant management. Participants will learn about EPA regulations on leak repairs and responsibilities for record-keeping. Test your knowledge on effective leak detection strategies and compliance measures.