quiz image

4BE3.5 U3 C1 Obj 3 Easy

WholesomeMaroon avatar
WholesomeMaroon
·
·
Download

Start Quiz

Study Flashcards

8 Questions

How often should try lever tests be performed on steam heating boilers?

Monthly

What is the minimum pressure required for a steam heating boiler to perform a try lever test?

35 kPa

What is the primary purpose of a try lever test?

To determine if the valve is operating freely

How often should pop tests be performed on power boilers?

Annually

What is the purpose of the pop test?

To check the exact pressures at which the valve opens and closes

What should be done if the valve simmers after the try lever test?

Operate the try lever two or three times to allow the disc to seat properly

What is the minimum pressure required for a power boiler to perform a try lever test?

75% of the setting of the safety valve

When should try lever tests be performed in relation to pop tests and accumulation tests?

Before pop tests and accumulation tests

Study Notes

Pressure Relief Valve Maintenance

  • Pressure relief valves must be kept in good working condition at all times and tested regularly to ensure proper functioning.

Try Lever Test

  • The try lever test determines if a pressure relief valve is operating freely, but not if it will open at its set pressure.
  • The test is performed:
    • Monthly on steam heating boilers
    • Every three months for hot water heating boilers
    • Every six months on power boilers operating below 2760 kPa
    • Prior to pop tests and accumulation tests
  • Boiler pressure must be:
    • 35 kPa or higher for steam heating boilers
    • At least 75% of the safety valve setting for power boilers
  • The test procedure:
    • Pull the try lever to the wide-open position
    • Allow steam to discharge for 5-10 seconds
    • Release the lever
    • Allow the spring to snap the valve disc to the closed position
    • If the valve simmers, operate the try lever 2-3 times to allow the disc to seat properly

Pop Test

  • The pop test checks the full operation of the safety valve, including the exact pressures at which it opens and closes.
  • The test procedure:
    • Increase the boiler steam pressure to the safety valve set point
    • Record the opening and reseating pressures accurately
    • Compare the opening pressure and blowdown to the ASME BPVC performance tolerances
  • The pop test should be performed annually, before taking a boiler off-line for maintenance.
  • Defective valves can be identified and replaced or repaired prior to the boiler re-entering service.

Repair and Adjustment

  • Repair or adjustment of pressure relief valves must be done by the valve manufacturer or its authorized repair representative.
  • Consult the relevant ASME BPVC sections and the local Boiler Inspector to determine who is qualified to adjust or repair PRVs in a particular jurisdiction.

Learn about the importance of maintaining pressure relief valves and how to test them regularly to ensure proper functioning.

Make Your Own Quizzes and Flashcards

Convert your notes into interactive study material.

Get started for free

More Quizzes Like This

GTS Mod 3 Difficult
18 questions

GTS Mod 3 Difficult

EnterprisingMagnolia avatar
EnterprisingMagnolia
4BE3.5 U3 C1 Obj 3 Hard
8 questions
4BE3.5 U3 C1 Obj 3 Matching
8 questions
Use Quizgecko on...
Browser
Browser