NEC Chapter 2 Review Questions
25 Questions
102 Views

NEC Chapter 2 Review Questions

Created by
@FoolproofLemur

Questions and Answers

______ conductors are the conductors from the service point to the service disconnecting means.

service conductors

______ conductors are all circuit conductors between the service equipment and the final branch-circuit overcurrent device.

feeder

The _____ is that portion of the electrical circuit between the last overcurrent device and the outlets or utilization equipment.

branch circuit

A(n) _____ load is a load where the waveform of the steady-state current does not follow the wave shape of the applied voltage.

<p>nonlinear load</p> Signup and view all the answers

In general, the grounded conductor of a branch circuit shall be identified by a continuous white or _____ outer finish.

<p>grey</p> Signup and view all the answers

Branch circuits with not over 120 V between conductors are permitted to supply auxiliary equipment of electric-discharge lamps.

<p>True</p> Signup and view all the answers

A GFCI receptacle or circuit breaker is set to trip at 10 mA.

<p>False</p> Signup and view all the answers

For an area to qualify as a bathroom, a ____ shall be present.

<p>basin</p> Signup and view all the answers

In dwelling units, a GFCI-protected receptacle is required when located within ____ ' from the inside edge of the bowl on the sink.

<p>6</p> Signup and view all the answers

All 125 V, 15 A and 20 A receptacles installed in the dwelling bathroom shall be GFCI.

<p>True</p> Signup and view all the answers

All receptacles which serve countertops in dwelling kitchens shall be GFCI.

<p>True</p> Signup and view all the answers

Branch-circuit conductors shall be ____ AWG or larger.

<p>14</p> Signup and view all the answers

Receptacle outlets installed in a dwelling for specific appliances shall be located within _____ ' of the appliance.

<p>6</p> Signup and view all the answers

The required dwelling unit outdoor receptacles shall be not more than ____ above finished grade level.

<p>6'6''</p> Signup and view all the answers

At least one receptacle outlet shall be installed in ____' or longer hallways of dwelling units.

<p>10</p> Signup and view all the answers

The required 125 V, 1 Ø, 15 A or 20 A receptacle on rooftops for heating, air-conditioning, and refrigeration servicing shall be within ____' of the equipment.

<p>25</p> Signup and view all the answers

A wall switch shall be provided at each floor level for a lighting outlet installed in an interior dwelling stairway with ____ or more risers between floors.

<p>6</p> Signup and view all the answers

_____ is the ratio of the maximum demand of a system, or part of a system, to the total connected load of a system or the part of the system under consideration.

<p>demand factor</p> Signup and view all the answers

The main concern in ___ branch circuits is that the neutral shall never be opened while the circuit is energized.

<p>multiwire</p> Signup and view all the answers

Branch-circuit EGCs smaller than 4 AWG shall have a continuous outer finish that is either green or green with one or more _____ stripes unless it is bare.

<p>yellow</p> Signup and view all the answers

All conductors of a(n) ____ branch circuit shall originate from the same panel board.

<p>multiwire</p> Signup and view all the answers

A current flow of ____ mA will most likely cause the heart to stop pumping.

<p>100</p> Signup and view all the answers

All receptacles in dwelling unit crawl spaces at or below grade shall be GFCI-protected.

<p>True</p> Signup and view all the answers

No point along the wall line for a dwelling unit countertop shall be more than 48" from a receptacle outlet.

<p>False</p> Signup and view all the answers

At least one receptacle outlet shall be installed within 36" of the outside edge of each bathroom basin in all dwelling units.

<p>True</p> Signup and view all the answers

Study Notes

Conductors

  • Service conductors connect the service point to the service disconnecting means.
  • Feeders are circuit conductors between service equipment and the final branch-circuit overcurrent device.
  • Branch circuits are the segments of electrical circuits between the last overcurrent device and outlets or utilization equipment.

Load Types

  • A nonlinear load has a current waveform that does not conform to the applied voltage's wave shape.

Grounding and Identification

  • Grounded conductors in branch circuits are identified by a continuous white or grey outer finish.

GFCI Requirements

  • Branch circuits under 120 V can supply equipment for electric-discharge lamps.
  • GFCI receptacles or circuit breakers typically trip at higher than 10mA.
  • GFCI-protected receptacles are required near sinks within 6 feet.

Bathroom Specifications

  • A basin must be present for an area to qualify as a bathroom.
  • All 125 V, 15 A, and 20 A receptacles in bathrooms must be GFCI protected.

Kitchen and Outdoor Receptacles

  • Countertop receptacles in kitchens require GFCI protection.
  • Outdoor receptacles in dwelling units must be positioned no more than 6 feet, 6 inches above finished grade.

Hallways and Equipment

  • Hallways in dwelling units longer than 10 feet require at least one receptacle outlet.
  • Rooftop receptacles for HVAC servicing should be within 25 feet of the equipment.

Stairway Lighting

  • A wall switch must be provided at each floor level for stairways with 6 or more risers.

Circuit Characteristics

  • The demand factor is the ratio of maximum system demand to total connected load.
  • In multiwire branch circuits, the neutral must never be opened while energized.

Grounding and Conductors

  • Multiwire branch circuit conductors must originate from the same panel board.
  • EGCs (Equipment Grounding Conductors) smaller than 4 AWG must have an outer finish that is either green or green with yellow stripes unless bare.

Safety Statistics

  • A 100 mA current flow is lethal and can lead to heart stoppage.

Additional GFCI Requirements

  • GFCI protection is mandatory for all receptacles in dwelling unit crawl spaces below grade.
  • No countertop in a dwelling unit should exceed 48 inches from a receptacle outlet.

Receptacle Placement

  • At least one receptacle must be within 36 inches of the outer edge of each bathroom basin in dwelling units.

Studying That Suits You

Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

Quiz Team

Description

Test your knowledge of Chapter 2 of the National Electrical Code (NEC) with these review questions. This quiz focuses on key definitions and concepts related to service conductors and feeders. Perfect for students and professionals looking to reinforce their understanding of electrical systems.

More Quizzes Like This

NEC Chapter 9: Tables Flashcards
21 questions
NEC Chapter 9 Flashcards
8 questions

NEC Chapter 9 Flashcards

WholesomeVibrance avatar
WholesomeVibrance
NEC Chapter 5 Review Questions
35 questions
Use Quizgecko on...
Browser
Browser