¿Cuántas exigencias básicas contempla el documento HS?

  • 4
  • 5
  • 6 (correct)
  • 3

Área efectiva de aberturas de admisión, en cm2, en función del caudal de ventilación (qv):

  • 5*qv
  • 2*qv (correct)
  • 3*qv
  • 4*qv (correct)

Área efectiva de aberturas mixtas, en cm2, en función del caudal de ventilación (qv):

  • 4*qv
  • 2*qv
  • 8*qv (correct)
  • 6*qv

Caudal mínimo, por m2 útil, de ventilación (en l/s) en almacenes de residuos de edificios de viviendas:

<p>10 (B)</p> Signup and view all the answers

De acuerdo con la exigencia HS 3, la evacuación de los productos de combustión de las instalaciones térmicas debe realizarse:

<p>Por la cubierta del edificio (D)</p> Signup and view all the answers

El sistema adicional de ventilación de las cocinas en viviendas debe tener un caudal mínimo de:

<p>50 l/s (B)</p> Signup and view all the answers

En aparcamientos con ventilación natural, la distancia máxima desde cualquier punto hasta una abertura es:

<p>25 m (A), 20 m (C)</p> Signup and view all the answers

En aparcamientos el sistema puede ser:

<p>Natural o mecánico (B)</p> Signup and view all the answers

En aparcamientos hay que poner detección de CO2 si el establecimiento excede de:

<p>5 plazas (C)</p> Signup and view all the answers

En cubierta, distancia mínima de aberturas de expulsión hasta elementos de entrada de ventilación:

<p>3 m (D)</p> Signup and view all the answers

En las viviendas, el sistema de ventilación puede ser:

<p>Híbrido o mecánico (A)</p> Signup and view all the answers

En los almacenes de residuos de edificios de viviendas el sistema puede ser:

<p>Natural, híbrido o mecánico (D)</p> Signup and view all the answers

En los almacenes de residuos de edificios de viviendas, en ventilación natural, cuando se utilizan aberturas mixtas, ningún punto debe distar de una de ellas más de:

<p>15 m (B)</p> Signup and view all the answers

En los locales habitables de las viviendas, el acumulado anual de CO2 que exceda de 1600 ppm no debe exceder de:

<p>500000 ppm.h (D)</p> Signup and view all the answers

En los locales habitables de las viviendas, la concentración media anual de CO2 no debe exceder:

<p>900 ppm (D)</p> Signup and view all the answers

En los locales habitables de las viviendas, la condición de eliminar los contaminantes no relacionados con la presencia humana se cumple con:

<p>1,5 l/s por local (D)</p> Signup and view all the answers

En ventilación híbrida, número de plantas, empezando por la más alta, que deben ser individuales:

<p>2 (D)</p> Signup and view all the answers

En ventilación híbrida, sección de los ramales que acometen al conducto principal:

<p>50% del conducto (B)</p> Signup and view all the answers

En ventilación mecánica de aparcamientos hay que poner, al menos, dos redes de extracción si el aparcamiento excede de:

<p>15 plazas (A), 20 plazas (D)</p> Signup and view all the answers

Holgura de conductos de extracción al atravesar forjados:

<p>20 mm (B)</p> Signup and view all the answers

La exigencia básica HS 3 se aplica a:

<p>Edificios de viviendas, en el interior de las mismas (A)</p> Signup and view all the answers

Los aireadores del sistema de admisión en viviendas deben situarse a una altura mínima de:

<p>180 cm (B)</p> Signup and view all the answers

Los conductos de chapa para ventilación mecánica se consideran aceptables si cumplen:

<p>UNE-EN 1707: 2007 (A), UNE-EN 1507:2007 (B)</p> Signup and view all the answers

Los conductos de ventilación híbrida de los almacenes de residuos:

<p>No pueden compartirse con otro uso (B)</p> Signup and view all the answers

Para garantizar el caudal en los locales habitables de las viviendas de más de 3 dormitorios, necesitamos en los locales húmedos un mínimo de:

<p>8 l/s (B)</p> Signup and view all the answers

Periodicidad de mantenimiento de revisión del estado de filtros:

<p>2 años (A), 6 meses (C)</p> Signup and view all the answers

Sección del conducto de ventilación híbrida para 150 l/s en T-2:

<p>1 x 625 cm2 (C), 1 x 900 cm2 (D)</p> Signup and view all the answers

Sección mínima de conducto de ventilación mecánica junto a locales habitables:

<p>2,5*qvt (B)</p> Signup and view all the answers

Tiro de la penúltima planta de edificio de viviendas en Zona Térmica Z:

<p>T-4 (C)</p> Signup and view all the answers

Un conducto de ventilación híbrida colectivo no puede servir a más de:

<p>6 plantas (B)</p> Signup and view all the answers

Zona térmica de Murcia (<800 m de altitud):

<p>Z (D)</p> Signup and view all the answers

El documento HS del CTE se refiere a:

<p>Salubridad (D)</p> Signup and view all the answers

La exigencia HS3, Calidad del aire interior, pide que los edificios se ventilen para:

<p>Eliminar los contaminantes que se producen en el interior de los edificios (C)</p> Signup and view all the answers

Para garantizar que un edificio cumple las exigencias del CTE:

<p>Puedo utilizar diseños prestacionales alternativos (C)</p> Signup and view all the answers

Para los usos en los que no se aplica la Exigencia Básica HS3 se aplica:

<p>El RITE (B)</p> Signup and view all the answers

Para garantizar el caudal en los locales habitables de las viviendas, necesitamos en el dormitorio principal un mínimo de:

<p>8 l/s (A)</p> Signup and view all the answers

Caudal mínimo, por m2 útil, de ventilación en trasteros de edificios de viviendas:

<p>0,7 (A)</p> Signup and view all the answers

Caudal mínimo, por plaza, de ventilación (en l/s) en aparcamientos:

<p>120 (C)</p> Signup and view all the answers

En las viviendas el aire debe circular:

<p>De locales secos a locales húmedos (A)</p> Signup and view all the answers

Las aberturas de extracción en viviendas deben situarse a una distancia mínima de las esquinas de:

<p>100 mm (A)</p> Signup and view all the answers

En los trasteros de edificios de viviendas el sistema puede ser:

<p>Natural, híbrido o mecánico (D)</p> Signup and view all the answers

Diámetro mínimo del patio para tener aberturas de admisión:

<p>3 m (C)</p> Signup and view all the answers

Los conductos de admisión tienen que ser registrables, como máximo, cada:

<p>10 m (C)</p> Signup and view all the answers

En garajes que no excedan de 5 vehículos, para ventilación natural, se pueden disponer aberturas de admisión y extracción en el mismo cerramiento separadas como mínimo:

<p>1,5 m (B)</p> Signup and view all the answers

Área efectiva mínima de aberturas de paso:

<p>70 cm2 (D)</p> Signup and view all the answers

Sección del conducto de Ventilación Híbrida para 50 l/s en T-1:

<p>1 x 225 cm2 (D)</p> Signup and view all the answers

Periodicidad de Mantenimiento de Limpieza de Aberturas:

<p>1 año (C)</p> Signup and view all the answers

Sección mínima de conducto de ventilación mecánica junto a locales no habitables (a cubierta):

<p>1,5*qvt (D)</p> Signup and view all the answers

Superficie practicable mínima, en función del espacio al que sirven, en cocinas, comedores, dormitorios y salas de viviendas:

<p>1/20 (A)</p> Signup and view all the answers

Tiro de la última planta de edificio de viviendas en Zona Térmica W:

<p>T-3 (A)</p> Signup and view all the answers

Zona térmica de Granada (>800 m de altitud):

<p>X (C)</p> Signup and view all the answers

Flashcards

Basic ventilation requirements

Six fundamental requirements for building ventilation, outlined in the HS document.

Effective intake opening area (qv)

The area needed for ventilation openings; calculated as 2qv and 4qv depending on airflow.

Mixed openings

Ventilation openings that combine intake and exhaust.

Mixed opening area (qv)

The necessary area for mixed openings is 8*qv.

Signup and view all the flashcards

Waste storage ventilation

Minimum ventilation for waste storage areas.

Signup and view all the flashcards

Kitchen ventilation (minimum)

Minimum airflow needed for kitchen ventilation in residences.

Signup and view all the flashcards

Parking lot ventilation max distance

Maximum distance from any point to a natural ventilation opening in parking lots.

Signup and view all the flashcards

Parking ventilation types

Parking ventilation systems can be either natural or mechanical.

Signup and view all the flashcards

CO2 detection threshold parking

Carbon dioxide detectors are required in parking lots with more than 5 parking spaces.

Signup and view all the flashcards

Parking ventilation opening separation

Minimum distance between exhaust openings and ventilation inlets in parking structures.

Signup and view all the flashcards

Residential ventilation systems

Residential ventilation can be hybrid or mechanical.

Signup and view all the flashcards

Waste storage ventilation systems

Ventilation systems for waste storage areas can be natural, hybrid, or mechanical.

Signup and view all the flashcards

Natural Ventilation distance (mixed)

Maximum distance between points and mixed openings in natural ventilation.

Signup and view all the flashcards

CO2 annual accumulation limit

Maximum allowed accumulation of CO2 in habitable spaces yearly.

Signup and view all the flashcards

Annual average CO2 limit

Maximum average annual CO2 concentration in habitable spaces.

Signup and view all the flashcards

Contaminant removal rate

Rate to remove contaminants which is 1.5 l/s per room.

Signup and view all the flashcards

Hybrid ventilation plants

Two plants need to be independent in hybrid systems.

Signup and view all the flashcards

Branch duct sizing

Branch duct size must be 50% of the main duct.

Signup and view all the flashcards

Parking mechanical ventilation

Minimum 2 extraction networks for parking lots over 15 spots using mechanical systems.

Signup and view all the flashcards

Joist duct clearance

20mm clearance for ventilation ducts passing through floors.

Signup and view all the flashcards

Mechanical ventilation standards

Mechanical ventilation must meet UNE-EN 1507:2007 and UNE-EN 1707:2007.

Signup and view all the flashcards

Air diffuser height

Minimum height of 180cm for air diffusers.

Signup and view all the flashcards

Hybrid ventilation plant limit

A hybrid ventilation duct system cannot serve more than 6 floors.

Signup and view all the flashcards

Habitable spaces mechanical duct size

2.5*qvt minimum duct size for mechanical ventilation near habitable spaces.

Signup and view all the flashcards

Filter maintenance frequency

Maintenance and filter checks are needed every 6 months or 2 years.

Signup and view all the flashcards

Study Notes

Exigencias y Ventilación en Edificios

  • El documento HS contempla 6 exigencias básicas.
  • El área efectiva de aberturas de admisión en función del caudal de ventilación es 2qv y 4qv.
  • Para aberturas mixtas, el área efectiva es 8*qv.

Ventilación en Almacenes y Cocinas

  • El caudal mínimo de ventilación en almacenes de residuos es 10 l/s por m2 útil.
  • El sistema de ventilación de cocinas en viviendas debe tener un caudal mínimo de 50 l/s.

Ventilación en Aparcamientos

  • Distancia máxima desde cualquier punto hasta una abertura de ventilación natural es 20 m y 25 m.
  • Los sistemas en aparcamientos pueden ser natural o mecánico.
  • Se requiere detección de CO2 si hay más de 5 plazas.
  • Distancia mínima de aberturas de expulsión a elementos de entrada de ventilación es 3 m.

Sistemas de Ventilación en Viviendas

  • En viviendas, el sistema de ventilación puede ser híbrido o mecánico.
  • En almacenes de residuos, el sistema puede ser natural, híbrido o mecánico.
  • En ventilación natural, la distancia máxima entre puntos y aberturas mixtas es 15 m.

Condiciones en Locales Habitables

  • El acumulado anual de CO2 en locales habitables no debe exceder 500000 ppm.h.
  • Concentración media anual de CO2 no debe exceder 900 ppm.
  • Condición para eliminar contaminantes se cumple con 1,5 l/s por local.

Ventilación Híbrida y Mecánica

  • En ventilación híbrida, 2 plantas deben ser individuales.
  • La sección de los ramales que van al conducto principal debe ser 50% del conducto.
  • En aparcamientos con ventilación mecánica, se necesitan al menos dos redes de extracción si el aparcamiento excede de 15 plazas o más.

Especificaciones de Conductos y Mantenimiento

  • Holgura de conductos al atravesar forjados es de 20 mm.
  • Conductos para ventilación mecánica son aceptables si cumplen UNE-EN 1507:2007 y UNE-EN 1707:2007.
  • Los aireadores deben estar situados a una altura mínima de 180 cm.

Normativas y Capacidad

  • Un conducto de ventilación híbrida no puede servir a más de 6 plantas.
  • Sección mínima de conducto de ventilación mecánica junto a locales habitables es 2,5*qvt.
  • Mantenimiento y revisión de filtros se realiza cada 6 meses o cada 2 años.

Exigencias de Salubridad en Edificios

  • El Documento HS del CTE se refiere a la salubridad en la construcción.
  • La exigencia HS3, Calidad del aire interior, busca eliminar contaminantes producidos en el interior de los edificios.

Cumplimiento de Normativas del CTE

  • Para garantizar el cumplimiento de las exigencias del CTE, se pueden usar diseños prestacionales alternativos en lugar de seguir forzosamente los Documentos Básicos.

Regulaciones Relacionadas con la Ventilación

  • Para los usos donde no se aplica la exigencia HS3, se aplica el RITE, que regula la eficiencia energética y la ventilación.
  • El caudal mínimo en el dormitorio principal debe ser de 8 l/s para asegurar una adecuada ventilación.

Ventilación en Espacios Comunes

  • En trasteros de edificios de vivienda, se requiere un caudal mínimo de 0,7 m2 útil por ventilación.
  • Para aparcamientos, el caudal mínimo por plaza de ventilación es de 120 l/s.

Circulación del Aire en Viviendas

  • El aire debe circular de locales secos a locales húmedos, lo que asegura una adecuada regulación de la humedad.

Aberturas y Conductos

  • Las aberturas de extracción deben estar situadas a una distancia mínima de 100 mm de las esquinas.
  • En trasteros, el sistema de ventilación puede ser natural, híbrido o mecánico.

Dimensiones y Mantenimiento de Sistemas de Ventilación

  • El diámetro mínimo del patio para aberturas de admisión debe ser de 3 m y los conductos de admisión deben ser registrables, como máximo, cada 10 m.
  • En garajes con hasta 5 vehículos, las aberturas de admisión y extracción deben estar separadas al menos 1,5 m.

Requisitos Adicionales

  • El área efectiva mínima de las aberturas de paso es de 70 cm2.
  • La sección del conducto de ventilación híbrida para 50 l/s debe ser de 1 x 225 cm2.
  • La periodicidad de mantenimiento de limpieza de aberturas es de 1 año.

Superficies y Tiros en Edificios

  • La superficie practicable mínima en cocinas, comedores, dormitorios y salas es de 1/20 en relación al espacio.
  • El tiro de la última planta de un edificio de viviendas en la zona térmica W corresponde a T-3, y la zona térmica de Granada, sobre 800 m, es X.

Studying That Suits You

Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

Quiz Team

Related Documents

Tema 33.docx
Tema 33 bis.docx

Description

Este cuestionario se centra en las exigencias básicas del documento HS y en cálculo de áreas efectivas de aberturas de admisión en ventilación. Responde preguntas sobre el número de exigencias y la relación entre el caudal de ventilación y el área. Pon a prueba tus conocimientos sobre estos temas importantes.

More Like This

HS/XII/A/Ed/22 2022 Education Quiz
5 questions
HS Flashcards on Pathogens and Microorganisms
16 questions
Suministro de Agua HS 4
48 questions

Suministro de Agua HS 4

CongenialSanctuary5788 avatar
CongenialSanctuary5788
Use Quizgecko on...
Browser
Browser