According to Article 440, how should motor-compressors be protected against overload and failure to start?

All of the above

What is the maximum percentage at which the separate overload relay should trip for motor-compressors?

140%

Which devices are permitted to serve as the branch-circuit short-circuit and ground-fault protective device for motor-compressors?

Fuse or inverse time circuit breaker

Which standard defines a stationary unit (generator) as 'an engine generator that is intended to be hard-wired and/or permanently installed'?

UL 2200

Which type of generator must be marked with their reactances using the correct industry terms?

Portable generators

Which article covers the installation and other requirements for generators?

Article 445

Which standard provides information on the location of generators?

NFPA 37-2021

According to the text, what is the purpose of compliance with 445.18(A)?

To protect the worker servicing the generator

What is the requirement for the means of shutdown of the prime mover according to the text?

To equip provisions for backfeed protection

According to the text, what is the purpose of disabling all prime mover start control circuits?

To protect the worker servicing the generator

According to the text, what type of room air conditioners does Part VII apply to?

Room air conditioners that control temperature and humidity

According to the text, how should the enclosures of room air conditioners be connected?

To the equipment grounding conductor

According to the text, what is the maximum length of a flexible cord used to supply a room air conditioner rated 120 volts?

3.0 m (10 ft)

According to the text, what type of protection device should single-phase cord- and plug-connected room air conditioners be provided with?

Leakage-current detector-interrupter (LCDI)

Which type of generators are being manufactured with inverter-based designs?

All generators

What is the minimum ampacity of the conductors from the generator output terminals to the first distribution device(s) containing overcurrent protection?

100 percent of the nameplate current rating of the generator

What type of overcurrent protection is required for two-wire, dc generators?

All of the above

What is the ampacity requirement for neutral conductors of dc generators that must carry ground-fault currents?

Larger than the minimum required size of the largest conductor

Which of the following is true about conductors supplied from the generator output terminals?

They must have a minimum ampacity based on the nameplate current rating of the generator.

Under what conditions are tapped conductors permitted from the load side of the protected terminals of a generator set equipped with overcurrent protection?

When the generator set is equipped with a listed overcurrent protective device or a combination of a current transformer and overcurrent relay.

For which type of generators are tapped conductors not permitted?

Portable generators rated 15 kW or less where field wiring connection terminals are not accessible.

What provides short-circuit protection for the tap conductors in a generator equipped with a listed branch-circuit overcurrent protective device or a combination of a current transformer and overcurrent relay?

The listed branch-circuit overcurrent protective device or a combination of a current transformer and overcurrent relay on the tap conductor source side terminals.

Which of the following devices can be used for overload protection for motor-compressors and equipment on 15- and 20-ampere, single-phase, branch circuits?

A fuse or inverse time circuit breaker

What is the maximum continuous current that a thermal protector applied in accordance with 440.52(A)(2) should permit?

156 percent of the marked rated-load current or branch-circuit selection current

What type of protection should be provided for motor-compressors and equipment used on 15- or 20-ampere 120-volt, or 15-ampere 208- or 240-volt, single-phase branch circuits?

Overload protection

What is the maximum rating for the attachment plug and receptacle or cord connector for motor-compressors and equipment that are cord- and attachment-plug-connected and used on 15- or 20-ampere 120-volt, or 15-ampere 208- or 240-volt, single-phase branch circuits?

20 amperes at 125 volts or 15 amperes at 250 volts

According to the text, what is the purpose of the emergency engine shutdown device?

To disconnect the generator from the equipment it supplies

Which of the following is true about the engine shutdown device used as a disconnecting means?

It must be capable of being locked in the open position

When is the engine shutdown device not required to be a locking-type device?

When it is used only as the engine shutdown required by 445.19(A)

Which of the following is NOT a reason why an overcurrent device should not be installed in series with the shunt winding of an autotransformer between Points A and B?

Exception for autotransformers with input current less than 9 amperes

What is the purpose of the 2-pole disconnect switch with overcurrent devices OC-1a and OC-1b in the exhibit?

To protect the input circuit

Why is it not permitted to have an overcurrent device located in series with the shunt winding and the overcurrent device in an autotransformer?

Voltage feedback problem

According to the text, which type of generators are required to have a remote emergency stop switch?

Generators with a rating greater than 15 kW

What is the purpose of requiring shutdown of the prime mover for generators greater than 15 kilowatts?

To provide a remote shutdown means in the event of an emergency

According to the text, where should the emergency shutdown device be located for one- and two-family dwelling units?

Outside the dwelling unit at a readily accessible location

What is the requirement for ground-fault circuit-interrupter (GFCI) protection on receptacles of 15-kW or smaller portable generators?

Receptacle outlets shall have listed GFCI protection for personnel

According to Table 450.3(A), what is the maximum rating or setting of overcurrent protection for transformers rated over 1000 volts in supervised locations only?

300%

What is the maximum rating or setting of overcurrent protection for transformers rated over 1000 volts in any location with a secondary rated over 1000 volts and a transformer with 6% impedance?

600%

How many circuit breakers or sets of fuses are permitted for secondary overcurrent protection in transformers rated over 1000 volts?

6

What is the maximum percentage of the rated secondary current that the sum of the ratings of the circuit breakers for secondary protection in transformers rated over 1000 volts is permitted to exceed?

300%

Which type of transformers are not covered by Article 450?

Transformers used with Class 2 and Class 3 circuits

What is the purpose of the exception to 445.20(A)?

To address the problems of proper operation of a GFCI-protected 125-volt receptacle on a generator

Which sections in Article 240 and Article 245 are referenced in the informational note?

240.4 and 245.27

What is the purpose of compliance with Article 450?

To provide guidance for the installation of transformers

According to Table 450.3(B), what is the maximum rating or setting of overcurrent protection for transformers with currents less than 9 amperes?

250%

What is the maximum rating or setting of overcurrent protection for transformers with currents of 9 amperes or more, according to Table 450.3(B)?

125%

Which method of protection requires primary protection only for transformers, according to Table 450.3(B)?

Method 1

Which method of protection requires secondary side overcurrent protection at not more than 125 or 167 percent, provided the primary side overcurrent protection is not more than 250 percent of the primary side current rating, according to Table 450.3(B)?

Method 2

Which of the following is true about the primary overcurrent device for a transformer?

It provides short-circuit protection for the transformer

In which cases can the secondary circuit conductors of a transformer be protected by overcurrent devices in the primary circuit conductors?

For a transformer with a 2-wire primary and a 2-wire secondary

What methods can be used to handle the increased heating effects of nonlinear load currents on a transformer?

All of the above

For applications rated not more than 1000 volts, nominal, what article covers the overcurrent protection requirements for transformer conductors?

Article 240

Which of the following is the correct equation to calculate the voltage that would appear across the primary winding of a transformer when the load impedance is very low?

$208/32 × 208$

What is the voltage that would appear across the primary winding of a transformer when the load impedance is very low and the supply voltage is 208 volts?

$208/32 × 208$

What is the voltage that would appear across the primary winding of a transformer when the load impedance is very low and the supply voltage is 240 volts?

$240/32 × 240$

According to 450.14, where should the disconnecting means for transformers (other than Class 2 or Class 3 transformers) be located?

Either in sight of the transformer or in a remote location

According to 450.21(A), what are the separation requirements for transformers from combustible materials?

10 feet

According to 300.22(C)(3), in what type of spaces are transformers permitted to be installed?

Hollow spaces used for environmental air

Which type of protective device must be provided on the secondary side of the network transformers?

Circuit breaker and reverse-current relay

What is the purpose of the reverse-current relay in the network protector?

To prevent power from being fed back into the transformer

What type of protective device is commonly used to protect the secondary ties in the network system?

Current limiter

What is the grounding requirement for the transformer secondary supplying the grounded secondary tie system?

Grounded in accordance with 250.30 for separately derived systems

According to the text, what is the maximum rating or setting of overcurrent protection for transformers rated over 1000 volts in any location with a secondary rated over 1000 volts and a transformer with 6% impedance?

167 percent of the primary side current rating

According to the text, what is the maximum rating or setting of overcurrent protection for transformers rated over 1000 volts in supervised locations only?

250 percent of the primary side current rating

According to the text, what is the maximum rating or setting of overcurrent protection for transformers with currents less than 9 amperes?

42 percent of the primary side current rating

According to the text, what is the maximum percentage of the rated secondary current that the sum of the ratings of the circuit breakers for secondary protection in transformers rated over 1000 volts is permitted to exceed?

150 percent

Which of the following is true about the installation of grounding autotransformers on the load side of a supply system grounding connection?

It is prohibited for services, separately derived systems, and feeders and branch circuits that supply separate buildings or structures.

What type of transformer is used to create a neutral reference point on a circuit supplied from a grounded system?

Zigzag transformer

In what scenario can a line-to-ground fault in a feeder circuit cause serious damage to a zigzag transformer?

When the rating of the circuit in which the line-to-ground fault occurs exceeds the rating of the circuit in which the zigzag transformer is used.

What type of autotransformer is used to create a 3-phase, 4-wire distribution system from a 3-phase, 3-wire ungrounded system?

Grounding autotransformer

According to the text, what is the purpose of compliance with IEEE C57.12.00-2015 and IEEE C57.12.01-2020?

To dispose of transformer full-load heat losses without exceeding the transformer rating

According to the text, what is the purpose of marking the required clearances on the transformer?

To prohibit storage on the horizontal and readily accessible top surfaces of the transformer

According to the text, what is the purpose of bonding the terminal bar to the enclosure in a dry-type transformer?

To prevent the transformer enclosure from being evaluated as a grounding and bonding device

According to the text, when are dry-type transformers 1000 volts or less located in the open not required to be readily accessible?

When they meet the ventilation requirements

According to Article 450, what is the ampacity requirement for the tie circuit if loads are connected at the transformer supply points at each end of the tie and overcurrent protection is not provided in accordance with Parts I, II, and VIII of Article 240?

67 percent of the rated secondary current of the highest rated transformer supplying the secondary tie system

What is the ampacity requirement for the tie circuit if load is connected to the tie at any point between transformer supply points and overcurrent protection is not provided in accordance with Parts I, II, and VIII of Article 240?

100 percent of the rated secondary current of the highest rated transformer supplying the secondary tie system

Under what conditions should the conductors of each phase or neutral comply with 450.6(A)(4)(a) or (A)(4)(b)?

When the tie consists of more than one conductor per phase or neutral

What is the requirement for the means of interconnection for the conductors of each phase or neutral in a tie circuit that is not interconnected?

The loads shall be connected to one or more individual conductors of a paralleled conductor tie without interconnecting the conductors of each phase or neutral

According to the text, what is the minimum separation required for dry-type transformers rated 1121⁄2 kVA or less from combustible material when installed indoors?

300 mm (12 in.)

According to the text, what is the minimum fire rating required for the transformer room for individual dry-type transformers rated over 1121⁄2 kVA?

1-hour fire rating

According to the text, which type of transformers are exempted from the requirement of being installed in a transformer room?

Transformers with Class 155 or higher insulation systems and completely enclosed except for ventilating openings

According to the text, what is the minimum insulation system rating required for dry-type transformers to be exempt from installation in transformer rooms or vaults?

Class 155

According to the text, what is the maximum primary voltage allowed for dry-type transformers to be commonly used indoors?

35,000 volts

According to the text, what is the minimum separation required for dry-type transformers rated 112½ kilovolt-amperes or less from combustible material?

12 inches

According to the text, what is the maximum distance allowed between dry-type transformers exceeding 112½ kVA and combustible materials of buildings, if the transformers have Class 155 insulation systems or higher and are completely enclosed except for ventilating openings?

12 inches

Which type of transformers have the greatest need for passive protection to prevent the spread of burning oil to other combustible materials?

Transformers insulated with mineral oil

What is the minimum fire resistance requirement for the walls and roofs of transformer vaults?

3 hours

What is the minimum thickness requirement for the concrete floors of transformer vaults in contact with the earth?

100 mm (4 in.)

What is the minimum height requirement for the door sill or curb of a transformer vault?

100 mm (4 in.)

According to the text, what is the maximum number of parts per million PCBs that classifies a transformer as a PCB transformer?

500

According to the text, what is the maximum total capacity of oil-insulated transformers that are permitted to be installed in a vault constructed of reinforced concrete?

1121/2 kVA

According to the text, what is the maximum total rating of electric furnace transformers that are permitted to be installed without a vault in a building or room of fire-resistant construction?

75 kVA

According to the text, what is the maximum total rating of a transformer that is permitted to be installed without a vault in a building or room of noncombustible or fire-resistant construction, if it is an integral part of charged-particle-accelerating equipment?

75 kVA

Which of the following information is required to be indicated on the nameplate of each phase converter according to the text?

All of the above

What is the purpose of sizing single-phase conductors to prevent a voltage drop not exceeding 3 percent from the source of supply to the phase converter according to the text?

To ensure proper starting and operation of motor loads

According to the text, what is the ampacity requirement for the single-phase supply conductors of a phase converter?

It depends on the rated input and output voltages

Which type of phase converter does not have any moving parts?

Static-phase converter

What is the minimum net area required for ventilation openings in a vault ventilated by natural circulation of air?

0.1 m2 (1 ft2)

What is the maximum rating or setting of overcurrent protection for transformers rated over 1000 volts in any location with a secondary rated over 1000 volts and a transformer with 6% impedance?

125% of the transformer full-load current

What is the purpose of installing a drain or other means for carrying off oil or water accumulation in vaults containing more than 100 kVA transformer capacity?

To facilitate maintenance

According to the text, what is the purpose of a liquid confinement area in a nonflammable-fluid-insulated transformer?

To limit the extent of a spill if the tank leaks or ruptures

According to 450.24, what is the requirement for nonflammable-fluid-insulated transformers installed indoors and rated over 35,000 volts?

They must be installed in a vault

What is the purpose of a pressure-relief vent in a nonflammable-fluid-insulated transformer?

To provide pressure relief in case of a leak or rupture

According to the text, why is a means for absorbing gases generated by arcing necessary in a nonflammable-fluid-insulated transformer?

To prevent the formation and emission of toxic or corrosive compounds

Test your knowledge on overcurrent protection for generators. Learn about the exceptions to 445.13(A) and the minimum ampacity requirements for conductors based on the nameplate current rating of the generator.

Make Your Own Quizzes and Flashcards

Convert your notes into interactive study material.

Get started for free

More Quizzes Like This

Generator Fundamentals
6 questions

Generator Fundamentals

VerifiableSugilite2612 avatar
VerifiableSugilite2612
Generator Basics
3 questions

Generator Basics

CushyCelebration avatar
CushyCelebration
Properties of Generator Potential Quiz
11 questions
Generator Balancer Set Methods
19 questions
Use Quizgecko on...
Browser
Browser