What is the maximum exit travel distance allowed in buildings equipped with an automatic wet sprinkler system?
What is the maximum exit travel distance allowed in buildings equipped with an automatic wet sprinkler system?
- 250 ft
- 300 ft
- 200 ft (correct)
- 150 ft
What happens if the OS&Y valve is closed when attempting to use the fire department connection?
What happens if the OS&Y valve is closed when attempting to use the fire department connection?
- The system will fill automatically.
- Water can still flow into the system.
- There will be a fluctuation in water pressure.
- Water will not be pumped into that section. (correct)
What should be done if the sprinklers are not operating during a fire attack?
What should be done if the sprinklers are not operating during a fire attack?
- Wait for the owner to arrive.
- Immediately retreat.
- Shut down all operations to reassess.
- Stretch handlines and initiate a manual attack. (correct)
What is essential to inform interior forces before supplying water to the sprinkler system?
What is essential to inform interior forces before supplying water to the sprinkler system?
During the investigation of a building with no visible fire signs and a water-flow alarm, what is the first thing to check?
During the investigation of a building with no visible fire signs and a water-flow alarm, what is the first thing to check?
What does a lack of fluctuation in discharge and intake pressures indicate when the feed gate valve is closed?
What does a lack of fluctuation in discharge and intake pressures indicate when the feed gate valve is closed?
What equipment should the reconnaissance team be equipped with when investigating sprinkler control valves?
What equipment should the reconnaissance team be equipped with when investigating sprinkler control valves?
In case of a water-flow alarm at a carpet warehouse with no visible issues, which step is NOT advisable?
In case of a water-flow alarm at a carpet warehouse with no visible issues, which step is NOT advisable?
What should be reported to the incident commander after the sprinklers are activated?
What should be reported to the incident commander after the sprinklers are activated?
What can be the potential danger of activating the sprinkler system during a fire attack?
What can be the potential danger of activating the sprinkler system during a fire attack?
What is the main purpose of a pressure tank in a sprinkler system?
What is the main purpose of a pressure tank in a sprinkler system?
What can happen if the supply from a sprinkler system runs out during a fire?
What can happen if the supply from a sprinkler system runs out during a fire?
What should be done as soon as a functioning sprinkler system is identified?
What should be done as soon as a functioning sprinkler system is identified?
What is one reason that a false alarm might occur in a wet-pipe sprinkler system?
What is one reason that a false alarm might occur in a wet-pipe sprinkler system?
What does the sight glass on a pressure tank indicate?
What does the sight glass on a pressure tank indicate?
Why is it important to note the position of sectional valves?
Why is it important to note the position of sectional valves?
Which action is justified if there are signs of fire, smoke, or water flow during the investigation?
Which action is justified if there are signs of fire, smoke, or water flow during the investigation?
What is a potential hazard when entering a building in response to an alarm?
What is a potential hazard when entering a building in response to an alarm?
What was a consequence of a sprinkler system running dry for three hours?
What was a consequence of a sprinkler system running dry for three hours?
Why might waiting for the owner before entering be a poor choice?
Why might waiting for the owner before entering be a poor choice?
How are control valves typically accessed in multistory buildings?
How are control valves typically accessed in multistory buildings?
What is a potential issue during an arson fire regarding sprinkler systems?
What is a potential issue during an arson fire regarding sprinkler systems?
What should a firefighter do if there is no sign of flowing water at the siamese connection?
What should a firefighter do if there is no sign of flowing water at the siamese connection?
Which one of the following is an important consideration regarding forced entry?
Which one of the following is an important consideration regarding forced entry?
Which of the following conditions could contribute to water damage during a false alarm?
Which of the following conditions could contribute to water damage during a false alarm?
What is the best initial response for firefighters when assessing a building after a fire alarm?
What is the best initial response for firefighters when assessing a building after a fire alarm?
Which structure type is likely to have limited water supply that firefighters must consider?
Which structure type is likely to have limited water supply that firefighters must consider?
What critical action should firefighters take before making forced entry, considering liabilities?
What critical action should firefighters take before making forced entry, considering liabilities?
What is the most effective way to determine the presence of a sprinkler system in a building?
What is the most effective way to determine the presence of a sprinkler system in a building?
Why might a sprinkler system be turned off during a fire in a commercial building?
Why might a sprinkler system be turned off during a fire in a commercial building?
What does the presence of a water motor alarm gong typically indicate?
What does the presence of a water motor alarm gong typically indicate?
Which type of alarm suggests the presence of a sprinkler system in a building?
Which type of alarm suggests the presence of a sprinkler system in a building?
What is a common misconception about responding to a fire in a building with a malfunctioning sprinkler system?
What is a common misconception about responding to a fire in a building with a malfunctioning sprinkler system?
Which system's presence can be confirmed through building or fire codes?
Which system's presence can be confirmed through building or fire codes?
What indicates that a sprinkler system may not be functioning properly?
What indicates that a sprinkler system may not be functioning properly?
Which action should be prioritized upon discovering a serious fire in a protected building?
Which action should be prioritized upon discovering a serious fire in a protected building?
What could significantly complicate firefighting efforts at a commercial sprinklered building?
What could significantly complicate firefighting efforts at a commercial sprinklered building?
What is the primary indicator of whether the OS&Y valve is open or closed?
What is the primary indicator of whether the OS&Y valve is open or closed?
Which method is most effective in locating the controls of the sprinkler system before a fire occurs?
Which method is most effective in locating the controls of the sprinkler system before a fire occurs?
What type of control valve is typically found at the base of the sprinkler riser?
What type of control valve is typically found at the base of the sprinkler riser?
What characteristic distinguishes the post indicator valve (PIV) from other valves?
What characteristic distinguishes the post indicator valve (PIV) from other valves?
What is the operating action required to close a PIV valve?
What is the operating action required to close a PIV valve?
How has the hydraulic design of sprinkler systems changed recently?
How has the hydraulic design of sprinkler systems changed recently?
What does a fully open OS&Y valve indicate in terms of stem protrusion?
What does a fully open OS&Y valve indicate in terms of stem protrusion?
What can complicate the task of locating the supply valves in modern sprinkler systems?
What can complicate the task of locating the supply valves in modern sprinkler systems?
Which statement accurately reflects the function of the wall indicator valve (WIV)?
Which statement accurately reflects the function of the wall indicator valve (WIV)?
What is the typical indicator of an OS&Y valve being closed?
What is the typical indicator of an OS&Y valve being closed?
What is the primary consequence of installing the wrong temperature sprinkler head?
What is the primary consequence of installing the wrong temperature sprinkler head?
Which of the following is NOT a marking that sprinkler heads have?
Which of the following is NOT a marking that sprinkler heads have?
What should be done to mark the location of a replaced sprinkler head?
What should be done to mark the location of a replaced sprinkler head?
Why is it important to notify the building owner in writing after replacing a sprinkler head?
Why is it important to notify the building owner in writing after replacing a sprinkler head?
Which type of contractor is recommended for inspecting replaced sprinkler heads?
Which type of contractor is recommended for inspecting replaced sprinkler heads?
What is the primary function of the WIV's spoked handwheel?
What is the primary function of the WIV's spoked handwheel?
What characterizes the main drain valve in terms of its physical design?
What characterizes the main drain valve in terms of its physical design?
What is a common challenge when trying to restore protection in a sprinklered building after a fire?
What is a common challenge when trying to restore protection in a sprinklered building after a fire?
In which scenario might a fire department decide to replace a fused sprinkler head?
In which scenario might a fire department decide to replace a fused sprinkler head?
What can be implied about the common practices regarding different sprinkler types?
What can be implied about the common practices regarding different sprinkler types?
What action is necessary to close the WIV valve?
What action is necessary to close the WIV valve?
Which of the following is NOT typically a feature of the main drain valve?
Which of the following is NOT typically a feature of the main drain valve?
What is the likely outcome of not restoring sprinkler protection after a fire?
What is the likely outcome of not restoring sprinkler protection after a fire?
What is the percentage of fires controlled by 1 or 2 sprinkler heads?
What is the percentage of fires controlled by 1 or 2 sprinkler heads?
Pg 132 says many departments only have a minimal response to sprinkler alarms based on the premise that ___ % of all fires are controlled by one or two sprinkler heads
Pg 132 says many departments only have a minimal response to sprinkler alarms based on the premise that ___ % of all fires are controlled by one or two sprinkler heads
Unlike pg 132 pg 137 says __% involve only one or two sprinkler heads
Unlike pg 132 pg 137 says __% involve only one or two sprinkler heads
Flashcards
Sprinkler System Size-Up
Sprinkler System Size-Up
Assessing auxiliary fire suppression systems (sprinklers, standpipes, foam) during initial evaluation.
Sprinkler System Signs
Sprinkler System Signs
Indicators like siamese connections, water motor alarms, or water discharge from pipes.
Sprinkler System Predictability
Sprinkler System Predictability
Automatic sprinkler systems may or may not be present in a building, unlike standpipes or foam systems.
Prefire Inspection Importance
Prefire Inspection Importance
Signup and view all the flashcards
Sprinkler Alarm Response
Sprinkler Alarm Response
Signup and view all the flashcards
OOS Sprinkler Systems
OOS Sprinkler Systems
Signup and view all the flashcards
Sprinkler System Malfunction
Sprinkler System Malfunction
Signup and view all the flashcards
OOS Sprinkler Response
OOS Sprinkler Response
Signup and view all the flashcards
Multiple Riser Systems
Multiple Riser Systems
Signup and view all the flashcards
OS&Y Valve Function
OS&Y Valve Function
Signup and view all the flashcards
Sprinkler Engagement Strategy
Sprinkler Engagement Strategy
Signup and view all the flashcards
Water Discharge Monitoring
Water Discharge Monitoring
Signup and view all the flashcards
False Alarm Response
False Alarm Response
Signup and view all the flashcards
False Alarm Prefire Planning
False Alarm Prefire Planning
Signup and view all the flashcards
OS&Y Valve Location
OS&Y Valve Location
Signup and view all the flashcards
Control Valve Types
Control Valve Types
Signup and view all the flashcards
Control Valve Importance
Control Valve Importance
Signup and view all the flashcards
Water Drainage Post-Fire
Water Drainage Post-Fire
Signup and view all the flashcards
Sprinkler System Restoration
Sprinkler System Restoration
Signup and view all the flashcards
Temporary Sprinkler Repair
Temporary Sprinkler Repair
Signup and view all the flashcards
Notification of Damage
Notification of Damage
Signup and view all the flashcards
Sprinkler System Protection
Sprinkler System Protection
Signup and view all the flashcards
System Design Knowledge
System Design Knowledge
Signup and view all the flashcards
Post-Incident Restoration
Post-Incident Restoration
Signup and view all the flashcards
Study Notes
Sizing Up Sprinklered Buildings
- Assess auxiliary fire-suppression systems like sprinklers, standpipes, and foam systems during size-up.
- Verify the presence of these systems; building codes often mandate standpipes in high-rises and foam systems in specific areas.
- Automatic sprinkler systems are less predictable; many large buildings may lack them while smaller ones could be fully protected.
- Signs of a sprinkler system include siamese connections, water motor alarm gongs, and water discharge from pipes.
- Prefire inspections provide vital information about the sprinkler system’s location and operational status.
Response to Sprinkler Alarms
- Upon arrival, establish if the sprinkler system is operational; building personnel can assist with information.
- A significant percentage of sprinkler alarms indicate minor issues rather than actual fires, leading to minimal initial responses.
- Serious fires in sprinklered buildings often have systems that might be out of service (OOS).
- Malware activity might result in an arsonist turning off sprinklers, complicating firefighting efforts.
- Treat fires in OOS sprinklered buildings with the same caution as non-sprinklered buildings, as both can be equally difficult to control.
Operating Sprinkler Systems
- Multiple riser systems require attention to fire department connections (FDC) below main control valves.
- If the OS&Y valve is closed, water cannot be pumped into the system or zone.
- Maintain a strategy to engage sprinklers quickly during an incident to aid in fire suppression.
- Monitor the effects of sprinkler discharge following activation and notify interior units of water flows.
Investigating False Alarms
- Decide whether to forcibly enter a structure during a false alarm or await the owner's arrival.
- Consider prefire planning knowledge about sprinkler systems; pressures may stabilize after a false alarm.
- Signs to confirm presence or absence of fire include water flow or alarms from the system.
Locating and Operating Control Valves
- Familiarize with the OS&Y valve, located at the sprinkler riser; indicates the valve's position by the stem's protrusion.
- Several types of control valves (PIV and WIV) can indicate whether the system is open or closed.
- Locating control valves early is crucial, especially due to modern hydraulic designs complicating the identification of systems.
Restoration of Sprinkler Protection
- Firefighters typically drain water from systems post-fire to prevent flooding and assist in salvage operations.
- Restoration of the sprinkler system may vary by department policy, with some opting for minimal intervention.
- A temporary measure may involve replacing fused sprinkler heads using spare heads and tools available on-site.
- Notify building owners in writing about any damage incurred from forced entry or repair actions.
Key Considerations
- Sprinkler systems generally offer considerable protection but require ongoing operational status to be effective.
- Awareness of building layout and system design enables better management of fire incidents involving sprinkler systems.
- Always ensure restoration of protection and functionality in sprinklered buildings after an incident to facilitate ongoing safety.
Studying That Suits You
Use AI to generate personalized quizzes and flashcards to suit your learning preferences.
Description
This quiz covers the assessment of auxiliary fire-suppression systems, focusing on sprinklers, standpipes, and foam systems. It also addresses how to respond to sprinkler alarms and the importance of prefire inspections for operational status. Test your knowledge on fire safety protocols and building codes.