Podcast
Questions and Answers
What is the primary reason for constantly monitoring the controllers of fire pumps activated by electric automatic controllers?
What is the primary reason for constantly monitoring the controllers of fire pumps activated by electric automatic controllers?
- To maintain optimal water pressure in the system.
- To reduce wear and tear on the pump motors.
- To ensure availability of the electrical power supply in an emergency. (correct)
- To ensure the pumps activate during routine testing.
The pump room can be utilized for general plant operations in addition to fire protection functions.
The pump room can be utilized for general plant operations in addition to fire protection functions.
False (B)
According to the provided text, what could missing or defective pipe hangers cause in a sprinkler system?
According to the provided text, what could missing or defective pipe hangers cause in a sprinkler system?
the entire system to fail from piping rupturing or leaking
Unapproved hangers such as perforated ______ or bailing wire hangers are prohibited from use in supporting sprinkler systems.
Unapproved hangers such as perforated ______ or bailing wire hangers are prohibited from use in supporting sprinkler systems.
Match the type of fire pump with its primary function:
Match the type of fire pump with its primary function:
Why must timers on fire pump controllers that automatically turn the fire pump OFF when an upper pressure limit has been reached be disabled in NYC?
Why must timers on fire pump controllers that automatically turn the fire pump OFF when an upper pressure limit has been reached be disabled in NYC?
What is the primary purpose of a jockey pump in a sprinkler system?
What is the primary purpose of a jockey pump in a sprinkler system?
Booster pumps should be confused with pressure maintenance pumps (jockey pumps).
Booster pumps should be confused with pressure maintenance pumps (jockey pumps).
What is the general recommendation for using a well as the primary water supply for a vertical turbine fire pump?
What is the general recommendation for using a well as the primary water supply for a vertical turbine fire pump?
For centrifugal pumps, the water is discharged under increased pressure and flow after it reaches rotating ______.
For centrifugal pumps, the water is discharged under increased pressure and flow after it reaches rotating ______.
What is the minimum acceptable temperature, in Fahrenheit, that water inside a gravity tank should be maintained at?
What is the minimum acceptable temperature, in Fahrenheit, that water inside a gravity tank should be maintained at?
It is acceptable to allow ice to build up on a gravity tank as long as the supports are regularly inspected.
It is acceptable to allow ice to build up on a gravity tank as long as the supports are regularly inspected.
What is the potential problem with wooden tanks if they are not kept full of water?
What is the potential problem with wooden tanks if they are not kept full of water?
Electrical supervision devices monitor the water temperature and the water ______ in the gravity tank.
Electrical supervision devices monitor the water temperature and the water ______ in the gravity tank.
Match the method of gravity tank heating with its description
Match the method of gravity tank heating with its description
Why must the water available to the centrifugal pump always be under pressure?
Why must the water available to the centrifugal pump always be under pressure?
Automatic fill pumps will stop the pump when the desired water level is reached.
Automatic fill pumps will stop the pump when the desired water level is reached.
For every 1 foot the tank is above the discharge outlet, how much water pressure is generated?
For every 1 foot the tank is above the discharge outlet, how much water pressure is generated?
Pressure tanks are to be maintained at approximately two-thirds full of water and one-______ full of pressurized air.
Pressure tanks are to be maintained at approximately two-thirds full of water and one-______ full of pressurized air.
Match the alarm system with what it monitors
Match the alarm system with what it monitors
What is the air-to-water volume ratio that should be maintained in a pressure tank?
What is the air-to-water volume ratio that should be maintained in a pressure tank?
Building owners are permitted to close a control valve on a fire sprinkler system at any time to conduct maintenance.
Building owners are permitted to close a control valve on a fire sprinkler system at any time to conduct maintenance.
When is the removal of protective caps and straps on glass bulb sprinklers performed?
When is the removal of protective caps and straps on glass bulb sprinklers performed?
Sprinkler heads experiencing a build-up of foreign material are commonly called ______.
Sprinkler heads experiencing a build-up of foreign material are commonly called ______.
Match type of premise with recommended sprinkler head.
Match type of premise with recommended sprinkler head.
What is the typical physical difference that distinguishes Standard Response sprinklers from Quick Response sprinklers?
What is the typical physical difference that distinguishes Standard Response sprinklers from Quick Response sprinklers?
Fire sprinkler cover plates can be painted.
Fire sprinkler cover plates can be painted.
Roughly how many degrees lower than the fire sprinkler head detaches the heat-sensitive plate?
Roughly how many degrees lower than the fire sprinkler head detaches the heat-sensitive plate?
Unlike concealed pendent sprinklers which hide behind decorative plates, the head of a traditional pendent fire sprinkler remains ______ after installation.
Unlike concealed pendent sprinklers which hide behind decorative plates, the head of a traditional pendent fire sprinkler remains ______ after installation.
Match each sprinkler head type to the description of water spray.
Match each sprinkler head type to the description of water spray.
What is indicated by the Sprinkler Identification Number (SIN) on sprinkler heads manufactured after 1/1/2000?
What is indicated by the Sprinkler Identification Number (SIN) on sprinkler heads manufactured after 1/1/2000?
Surge type water flow switches cannot be adjusted to changing water pressures.
Surge type water flow switches cannot be adjusted to changing water pressures.
What metal alloy with a fixed melting point solders levers and links together?
What metal alloy with a fixed melting point solders levers and links together?
The tank is normally kept at ______ full of water and one third full of air
The tank is normally kept at ______ full of water and one third full of air
Match the function with component of water-flow alarms and sprinkler system.
Match the function with component of water-flow alarms and sprinkler system.
What is the purpose of the automatic ball drip device installed between the lower check valve and the outside Fire Department connection?
What is the purpose of the automatic ball drip device installed between the lower check valve and the outside Fire Department connection?
Fire Department connections must always be inaccessible.
Fire Department connections must always be inaccessible.
If the stem is all the way out, is the valve closed?
If the stem is all the way out, is the valve closed?
Auxiliary sources of water are supplied through Fire Department ______ at the building.
Auxiliary sources of water are supplied through Fire Department ______ at the building.
Match the fire compactor component with action
Match the fire compactor component with action
If any major defects are discovered in the compactor system, who must they be reported to?
If any major defects are discovered in the compactor system, who must they be reported to?
It is recommended to try to enter the compactor chute to put out a fire.
It is recommended to try to enter the compactor chute to put out a fire.
When required, the sign might read: shutoff for sprinkler system located how many feet from the sign?
When required, the sign might read: shutoff for sprinkler system located how many feet from the sign?
When a sprinkler system is supplied from a public water main, the entire system shall be shut down by closing a ______-indicating type control valve.
When a sprinkler system is supplied from a public water main, the entire system shall be shut down by closing a ______-indicating type control valve.
Match the sprinkler head system with description.
Match the sprinkler head system with description.
What is the primary purpose of a fire pump room's temperature being maintained above 40 degrees Fahrenheit?
What is the primary purpose of a fire pump room's temperature being maintained above 40 degrees Fahrenheit?
According to the provided text, it is acceptable to use nails to fasten sprinkler systems to building attachments.
According to the provided text, it is acceptable to use nails to fasten sprinkler systems to building attachments.
What immediate action should be taken by a Certificate of Fitness holder when alarms have sounded indicating a drop in pressure in gravity and/or pressure tanks?
What immediate action should be taken by a Certificate of Fitness holder when alarms have sounded indicating a drop in pressure in gravity and/or pressure tanks?
Fire pumps must have their suction under a ______ head.
Fire pumps must have their suction under a ______ head.
Match the sprinkler system type with its appropriate description:
Match the sprinkler system type with its appropriate description:
Flashcards
Operation and Supervision of Fire Pumps
Operation and Supervision of Fire Pumps
When fire pumps are activated by electric automatic controllers, they must be constantly checked so the electrical power supply is available during an emergency.
Fire Pump Room Requirements
Fire Pump Room Requirements
Fire pumps should be in a fire-resistant or noncombustible room, close to the fire protection system, always accessible, protected against service interruptions, and kept above 40°F to prevent freezing.
Fire Pump Room Usage
Fire Pump Room Usage
No storage is allowed and the room is only for fire protection functions
Sprinkler System Support
Sprinkler System Support
Signup and view all the flashcards
Piping Support Standards
Piping Support Standards
Signup and view all the flashcards
NFPA #13 Chapter 9 Focus
NFPA #13 Chapter 9 Focus
Signup and view all the flashcards
Sprinkler System Deficiencies
Sprinkler System Deficiencies
Signup and view all the flashcards
Unapproved Hangers and Fasteners
Unapproved Hangers and Fasteners
Signup and view all the flashcards
Pump Activation
Pump Activation
Signup and view all the flashcards
Remote Push Button Function
Remote Push Button Function
Signup and view all the flashcards
Fire Pump Run Timers
Fire Pump Run Timers
Signup and view all the flashcards
Jockey Pump Role
Jockey Pump Role
Signup and view all the flashcards
Booster Pumps
Booster Pumps
Signup and view all the flashcards
Special Service Pumps
Special Service Pumps
Signup and view all the flashcards
Centrifugal Pump Specs
Centrifugal Pump Specs
Signup and view all the flashcards
Vertical Turbine Pumps
Vertical Turbine Pumps
Signup and view all the flashcards
Full Tank Benefits
Full Tank Benefits
Signup and view all the flashcards
Gravity Tank Monitoring
Gravity Tank Monitoring
Signup and view all the flashcards
Gravity Tank Issue
Gravity Tank Issue
Signup and view all the flashcards
Centrifugal Pump Traits
Centrifugal Pump Traits
Signup and view all the flashcards
Centrifugal Pump: Water Needed
Centrifugal Pump: Water Needed
Signup and view all the flashcards
Gravity Tanks
Gravity Tanks
Signup and view all the flashcards
Water Pressure Generated
Water Pressure Generated
Signup and view all the flashcards
Tank Fill System Control
Tank Fill System Control
Signup and view all the flashcards
Tank Heating Methods
Tank Heating Methods
Signup and view all the flashcards
Standard Pressure Tank Alarms
Standard Pressure Tank Alarms
Signup and view all the flashcards
Pressure tanks
Pressure tanks
Signup and view all the flashcards
Sprinkler extinguisher colour codes
Sprinkler extinguisher colour codes
Signup and view all the flashcards
Common cause of Sprinkler failure
Common cause of Sprinkler failure
Signup and view all the flashcards
Spare Sprinkler Specs
Spare Sprinkler Specs
Signup and view all the flashcards
Pressure Tank Levels
Pressure Tank Levels
Signup and view all the flashcards
Standard Response Sprinkler
Standard Response Sprinkler
Signup and view all the flashcards
Quick Response Head
Quick Response Head
Signup and view all the flashcards
Distinction of Quick Sprinklers
Distinction of Quick Sprinklers
Signup and view all the flashcards
Large Drop Heads
Large Drop Heads
Signup and view all the flashcards
Put out fires
Put out fires
Signup and view all the flashcards
Discharge of Sprinkler
Discharge of Sprinkler
Signup and view all the flashcards
Pendents
Pendents
Signup and view all the flashcards
Dry valve issues
Dry valve issues
Signup and view all the flashcards
Dry pipe systems
Dry pipe systems
Signup and view all the flashcards
Wet pipes setup!
Wet pipes setup!
Signup and view all the flashcards
Wet System Function
Wet System Function
Signup and view all the flashcards
Study Notes
- Fire pumps are activated by electric automatic controllers and must be constantly monitored to ensure the availability of electrical power.
- Supervisory devices on pumps alert the Certificate of Fitness holder and/or a central monitoring station during electrical power failure.
- When steam turbines or internal combustion engines are used, similar supervisory devices signal problems with controlling equipment.
Fire Pump Location
- Fire pumps should be in fire-resistant, noncombustible rooms.
- The pump room should be close to the fire protection system, kept clean, and accessible.
- The fire pump, driver, and controller should be protected against service interruptions.
- Pump room temperature should always be above 40 degrees Fahrenheit to prevent water freezing.
- The pump room's only use is for fire protection; no storage is allowed.
Hanging, Bracing, and Restraint of Sprinkler System Piping
- The structural support of the sprinkler system is vital for reliability.
- Missing or defective pipe hangers can cause system failure via ruptures or leaks.
- Adequacy of structural support should be carefully evaluated.
- Piping should be supported according to NYC Code and NFPA 13 (2007 edition).
- Annual visual inspection of hanging components and bracing can be difficult.
- NFPA#13 Chapter 9 details hanger design/installation and should be used as a reference for inspections.
- Deficiencies include disturbed system supports, building structure deflection, and excessive loads on components.
- Unapproved hangers like perforated strapping or bailing wire are prohibited.
- Nails can't fasten the system to the building structure.
- Hangers for plastic piping must be listed for use with the piping material.
Pump Activation
- Fire, booster, or special service pumps for fire sprinklers start automatically when system water pressure drops.
- Minor pressure drops are maintained by a pressure maintenance pump.
- If the pressure drop exceeds the maintenance pump's capacity, the main pump activates.
Manually Activated Fill Pumps
- Can be used with gravity or pressure tanks.
- Designed to operate when there is a pressure drop in the fire sprinkler system.
- Supervisory devices send a signal to a local alarm and may alert a central monitoring company.
- After alarms, the Certificate of Fitness holder must manually refill the gravity and/or pressure tanks.
- Remote push buttons start the pump, but do not stop it.
Fire Pump Controllers
- Many controllers have timers that automatically turn the pump OFF at an upper pressure limit.
- These timers must be disabled for all automatic fire pumps in NYC.
Pressure Maintenance Pumps (Jockey Pumps)
- Frequently installed on sprinkler systems.
- Designed to automatically operate when there is a slight drop in pressure due to leakage.
- The jockey pump restores pressure to the desired level.
- The main fire pump activates should the pressure continue dropping.
- Jockey pumps do not require inspection, testing, or maintenance as per NFPA 25 or the NYC Fire Code.
Booster Pumps
- Used in sprinkler systems and are typically in the basement.
- Used when water pressure at the highest sprinkler head is insufficient.
- They increase the water pressure in the sprinkler system until it reaches acceptable levels.
- Maintained according to NFPA 25 standard for fire pumps.
Special Service Pumps
- Sometimes used in sprinkler and standpipe systems.
- These are small with limited power, taking suction from gravity tanks.
- Used when available water pressure doesn't meet system needs.
- They increase water pressure and volume in the sprinkler/standpipe system until it reaches acceptable levels.
- Maintained according to NFPA 25 standard for fire pumps.
Water Tank Usage
- Water tanks may be used in tandem with a pump, if the tank supplies the pump due to gravity.
- This type of water tank is called a suction tank.
Centrifugal Pumps
- Depending on the model, pumps are capable of discharging water from 25 gpm up to 5,000 gpm.
- Most centrifugal pumps have a single impeller and are therefore commonly called single stage fire pumps.
Vertical Turbine Pump
- Has the capability to draw water from streams, ponds, wells, etc.
- Does not need the suction supply to be under pressure for it to operate.
Vertical Turbine Pump vs Wells
- Although a vertical turbine pump is capable of drawing water from wells it is generally not recommended to use a well as the main water supply source because it may dry up without warning.
- Better to draw water from the well and to fill a water storage tank, where a fire pump should then be attached as a more reliable supply source.
Suction Supply Source
- Important to ensure the water intake hose, foot valve, and screens are inspected regularly.
- Mud, gravel, leaves, and other debris may cause damage to the pump or obstruct the sprinkler system piping.
Gravity Tanks
- Must have a full water supply to ensure sprinkler system works correctly during a fire.
- Keeping a full tank also prevents wooden tanks from shrinking and keeps steel tanks from rusting.
- Should be constantly monitored to ensure the tank and its parts are working.
- Electrical supervision devices monitor the water temperature and the water level in the gravity tank.
- Devices send signals to an approved central station company, who then contact the owner.
- Called high and low alarms since they also sends audible signals to alert of a problem.
- Failures often are due to insufficient water in the tank.
Freezing in Gravity Tanks
- Ice should not be allowed to build-up.
- Weights from ice might weaken the supports of the tank, causing it to collapse.
- Falling icicles may cause damage or injury.
- Essential to properly heat, insulate, and carefully maintain the tank.
Centrifugal Fire Pump
- The standard pump currently used in fire protection systems.
- Reliable, compact, requires low maintenance, and can be powered by electric motors, diesel engines, and steam turbines.
- Water available to the centrifugal pump must always be under pressure because the pump is not designed to lift water for the supply source.
Water Storage Gravity Tanks
- Made of wood, steel, concrete, or fiberglass.
- Gravity tanks are used as a primary or secondary water supply source for sprinkler systems.
- Delivers water from the tank through the sprinkler system without pumping equipment.
Gravity Tank Height
- Should be at least 25 feet above the highest line of sprinkler heads it supplies.
- Tanks may be located on the tops of buildings or raised on tall supporting towers.
Gravity Tank Pressure
- Water pressure depends on the tank's elevation.
- For every 1 foot the tank is above the discharge outlet 0.433 psi of water pressure is generated.
- The higher the tank, the greater the water pressure.
- The gravity tank is reliably.
- Doesn't depend on the operation of mechanical equipment.
Automatic Fill Pumps
- Supply the water to most gravity tanks.
- Fill the tank at a rate of 65 gpm or more.
- Floats turn on the fill pump when the water in the tank is too low.
- The floats shut off the pump when the desired water level is reached.
- Makes sure the gravity tank always has the right amount of water to supply the sprinkler system.
Gravity Tank Overflow
- All gravity tanks have an overflow pipe that drains off excess water in the tank.
- This happens if the floats do not turn off the fill pump.
- This pump is not necessary if city water main is able to keep the tank filled.
Gravity Tank Temperature
- Exposed to very low temperatures.
- All parts of the gravity tank must be insulated or heated to keep the water from freezing.
- Several methods used to heat: Hot water is circulated by gravity, Steam is discharged directly into the tank, Steam coils placed inside tanks, and/or Heat from the sun is used.
Certificate of Fitness
- The Certificate of Fitness holder can check the water temperature with a thermometer near the heating device.
Pressure Tanks
- Primary water supply tanks are equipped with two high and low alarm systems that monitor the high and low air pressure and water levels.
- System automatically monitors the air-to-water volume ratio, which should always be 1 (air) to 2 (water).
- The Certificate of Fitness holder or Central Station operator is signaled when the water level or the air pressure is too high or too low.
The Pressure Tank May Be Supervised
- By an approved central station company which monitors the entire sprinkler system.
- These devices alert the central station company when there is a problem with the tank's water level, air pressure, and water temperature.
- The devices also alert the central station company when water has been discharged from the tank.
- When sprinkler heads have fused and water has been discharged from the tank, the borough dispatcher is notified.
- The central station company notifies the owner or the impairment coordinator when a problem is caused by an equipment failure.
Sprinkler Temperature Rating
- Sprinklers should have colored frame arms, deflector, coating material, or liquid bulb.
- Includes a temperature ratings classifications and color coding chart.
Build Up from Foreign Material on Sprinkler Heads
- Sometimes conditions exist which cause a build-up of foreign material on sprinkler heads.
- This may prevent the sprinkler head from working properly, otherwise called loading.
- The build-up of foreign material insulates the sprinkler head and prevents the sprinkler from opening at the desired temperature.
- Should the build up be hard, it may prevent the sprinkler from opening.
- If deposits are hard, attempts to clean the heads are likely to damage them, preventing the sprinkler heads from working properly and possibly causing the sprinkler head to leak.
- Light dust is less serious than hard deposits, only delaying the operation of the sprinkler head.
Spare Sprinkler Heads
- Sprinklers for emergency replacement must represent the sprinklers installed along with proper wrenches within the spare head cabinet.
- Sprinklers that are replaced during an emergency by unlicensed individuals require the devices used have been verified appropriate for the protected area by a Master Fire Suppression Piping Contractor.
- After activation by fire, sprinkler heads in close proximity to the affected area should be visually inspected and replaced, if required.
- A stock of spare sprinklers (not less than 6) shall be kept on the premise where the temperature does not exceed 100 Degrees F and shall include all types and ratings installed in the protected facility and provided as follows:
- Under 300 sprinklers six.
- 301 - 1000 sprinklers twelve.
- Over 1000 sprinklers twenty four.
Pressure Tanks
- Enclosed water tanks of limited size that use air pressure to forcefully discharge water into a sprinkler system.
- A pressure tank may be used as a primary or secondary water supply for a sprinkler system.
- Pressure tanks are to be maintained at approximately two-thirds full of water and one-third full of pressurized air with a minimum acceptable air pressure of 75 psi.
- Air pressure in the tank may be automatically maintained by an air compressor.
- The maximum gross capacity of pressure tanks is 9,000 gallons and some systems require more than 6,000 gallons of water.
Sprinkler Heads
- Standard Response Sprinkler Heads have a response time index (RTI) of 80 or more.
- Quick Response Sprinkler Heads have a RTI of 50 or less.
- Quick Response Sprinkler Heads are typically found in light hazard occupancies and may reduce or eliminate the requirements for smoke detection in certain light hazard occupancies.
Sprinkler Head Differences
- Quick response sprinklers got their name from their slightly faster response time when compared to standard response sprinklers.
- The only physical difference is the bulb size-- the standard response sprinkler has a 5 mm glass bulb and the quick response sprinkler has a 3 mm glass bulb.
Sprinkler Head Types
- Large drop sprinkler heads are special sprinklers designed to discharge water from the head to break through the strong updrafts of high challenge fires.
- Concealed sprinkler head activation: Cover plate falls, deflector drops, and bulb shatters when exposed.
- The best way to put out a fire is to spray the water from the sprinkler head downward and horizontally, which is determined by the umbrella shaped space pattern.
- Common head installations include: pendent, upright, and sidewall.
Sprinkler Heads in Special Situations
- Some sprinkler heads are designed to be used in special situations.
- Exposed to corrosive conditions are often covered with a protective coat of wax, or lead.
- Corrosive vapors are likely to make automatic sprinklers inoperative or slow down the speed of operation.
- Four sprinkler heads types:
- Pendent sprinklers are designed to be positioned where the water stream is directed downward against the deflector.
- Upright fire sprinklers spray water upward to a concave deflector to cover specific areas and to prevent ice and debris from collecting in the head.
- Sidewall fire sprinklers install along walls or beneath beams where ceiling piping might be unavailable and are most commonly used for protecting in smaller spaces.
- Concealed Models are installed in walls or ceilings and fully cover a pendent or sidewall sprinkler head using a concealed fire sprinkler cover plate.
Sprinkler Head Components
- Major sprinkler heads are made of metal, that are screwed in with standard valves.
Sprinkler System
- Employ automatic sprinklers that are attached to a piping system containing air or nitrogen under pressure.
- Water maintenance and regulation is key to avoiding flooding the facility accidentally.
Sprinkler Inspections
- There are multiple system types, including waterflow and the water source itself.
- The Certificate of Fitness, gravity and pressuring readings, and any modifications and malfunctions should be inspected upon.
Studying That Suits You
Use AI to generate personalized quizzes and flashcards to suit your learning preferences.