Which diesel generator set will start when the voltages at the emergency bus bars drop below 0.7VN?

Both generator sets will start

Which voltage transformers are used to sense undervoltages at the emergency bus bars?

00BBC and 00BBD

What is the method of control for the pre-selected diesel generator set?

Programmable logic controller (PLC)

What happens if one of the diesel generator sets fails to start?

The pre-selection automatically changes to the other generator set

When will the second diesel generator set shutdown automatically after starting?

If it fails to synchronize within 3 minutes

What is the minimum voltage level at which the diesel generator sets will start?

0.7VN

How are the diesel generator sets connected to the 6.6kV busbar?

Through their diesel generator circuit breaker

What will happen if the second BSDG fails to start?

The other DG will be connected to the 6.6kV busbar

When will the second BSDG shutdown automatically if not synchronized?

Within 3 minutes after start

What is the condition for considering the Emergency Power Supply to be in operation?

Voltage >min for more than 5 seconds